Technical Manual Switch Actuator 3-fold, FanCoil
MDT technologies GmbH
•
51766 Engelskirchen
•
Papiermühle 1
Tel.: +49-2263-
880 • Fax: +49
-2263-4588
• [email protected] • www.m
dt.de
54
Off-Delay of the Fan:
For using the residual energy off the heating/cooling circuit at switching the FanCoil off, the FanCoil
can run after for a defined time. The valve is closed directly at the point off switching, but the FanCoil
is switched after the Off-Delay is elapsed:
Figure 42: Off-Delay
The following table shows the available communication objects for these parameters:
Number
Name
Length
Usage
6
Switch heating valve
1 Bit
Switching the heating valve
6
Switch heating/cooling
valve
1 Bit
Switching the heating/cooling valve; at 2-Pipe
heating/cooling systems
7
Switch cooling valve
1 Bit
Switching the cooling valve
Table 45: Communication objects - FanCoil general
6.1.3 Blocking Functions
The following figure shows the available blocking functions:
Figure 43: Blocking Functions
Summary of Contents for AKK-03UP.02
Page 6: ......