McQuay PFS 155C Operation And Maintenance Manual Download Page 4

4

PFS 155C - 315C

OM 135

Alarm

The alarm light on the MicroTech control panel will be illuminated when any alarm condition exists.
Unless the alarm condition affects both compressors, the remaining compressor will operate as
required.  Refer to the control section of this manual for additional information.

Start-up

If none of the above “off” conditions are true, the MicroTech controller will initiate a start sequence
and energize the chilled water pump output relay.  If flow is not proven within 15 seconds, the alarm
output will be turned on and the keypad display will be No Evap Flow.  When evap flow is confirmed,
the controller will sample the chilled water temperature and compare it against the Leaving Chilled
Water Setpoint and the Start-up Delta Temperature, which have been programmed into the controller’s
memory.  If the leaving chilled water temperature is above the Leaving Chilled Water Setpoint plus the
adjustable Start-up Delta Temperature (which is defined outside of the control band), the controller
will then start the condenser pump.  The same time and alarm conditions exist for the condenser flow.
The compressor with the lowest number of starts will be the lead compressor.  The controller will open
the electronic expansion valves to regulate the pressure difference between the evaporator and the
condenser by pulling the evaporator pressure low once the compressor starts.  The controller will start
the lead compressor and energize the compressor suction injection and motor cooling solenoid valves.
Liquid injection is energized through the auxiliary starter contacts.  The lead compressor will increase
capacity by staging up according to the chilled water leaving evap setpoint.  The lead compressor will
stage to 100% capacity  before starting the lag compressor.  If additional cooling capacity is required,
the controller will energize the lag compressor and stage it up according to setpoint.  The compressors
capacity control solenoids will automatically be controlled as required to meet the cooling needs of
the system.

The electronic expansion valves are operated by the MicroTech controller through adaptive control
strategies (use of different system temperatures and pressures) to maintain desired refrigerant control
to the evaporator at all conditions.

Condenser Control

The condenser pump will be started in conjunction with the above logic to provide condenser water
flow.  The minimum entering condenser water temperature for full load air conditioning duty shall be
65°F with nominal cooling tower water flow of 3 GPM.  When condenser water temperatures are lower
and or chiller load is less than 100%, the condenser water flow  or entering condenser water
temperature must be controlled to maintain satisfactory operating refrigerant pressures.  The
MicroTech controller can control condenser water entering temperature by a condenser water bypass
valve based upon entering condenser water temperature.  It can also control condenser water flow by
a flow control valve based upon condenser pressure.  When using a flow control valve, a minimum
water flow through the condenser must be maintained.  This minimum water flow is based upon
system conditions and can vary with each installation.

Shutdown

As the system chilled water requirements lessen, the compressors will be unloaded.  As the system
load continues to drop, the lag compressor (compressor with the most run hours) will be stopped.  A
continuing load reduction will start the hot gas option or the chiller can shut down on the shut down
delta setpoint below the control band.

Hot gas control will allow the unit to maintain minimum operating parameters if proper condenser
control is available.  This type of control is standard and selectable from the keypad.  If hot gas
control is not selected, the unit will shut down on the shut down delta setpoint.  This feature can be
used to minimize chiller run time under light load conditions.

The condenser water pump will be stopped upon chiller shutdown and the chilled water pump output
relay will remain energized until the time schedule’s “on” time expires, the remote stop switch is
opened, the system switch is moved to the stop position, or a separate communications panel such as
the Chiller System Controller or an Open Protocol interface disables the chiller.

Summary of Contents for PFS 155C

Page 1: ...Manual OM 135 Group Chiller Part Number 629956Y Effective November 1997 Supersedes None 1997 McQuay International PFS 155C through 315C Operation and Maintenance Manual 50 and 60 Hertz Refrigerant R...

Page 2: ...11 Electronic Expansion Valve Operation 11 Evaporator 12 Condenser 12 Refrigerant Charging 12 Liquid Presence Sensor 13 High Condenser Pressure Control 13 Mechanical High Pressure Safety Control 13 C...

Page 3: ...ays The compressor heater HTR is energized through the normally closed contacts on the starter Note Before start up the compressor heater must be on for at least 12 hours to insure there is not any li...

Page 4: ...e electronic expansion valves are operated by the MicroTech controller through adaptive control strategies use of different system temperatures and pressures to maintain desired refrigerant control to...

Page 5: ...eady to start unit Place main power and control disconnect switches in on position This will energize compressor heaters Wait at least 12 hours before starting unit Note Evaporator and condenser water...

Page 6: ...n stop position 2 After compressors have shut down and electronic expansion valves have closed turn off chilled water pump 3 Turn off all power to the unit and to the chilled water and condenser water...

Page 7: ...alues in a chiller log daily The values will change as the load condenser temperature and evaporator temperature vary The operator should be able to correlate displayed information to varying load con...

Page 8: ...ar the sightglass If subcooling is normal 10 to 15 F 6 to 13 C at full load and flashing is visible in the sightglass check pressure drop across the filter dryer An element inside the sightglass indic...

Page 9: ...unit screw compressors are equipped with three solenoids to control compressor capacity The solenoids are controlled by MicroTech outputs see unit wiring diagrams The solenoids are energized at vario...

Page 10: ...e Unit condensers are sized to hold the entire refrigerant charge Use method A or B below to pump down the unit A Unit pump down using the compressor 1 Go to MicroTech menu number 16 2 Select Manual P...

Page 11: ...to shut down due to lack of liquid injection The liquid injection solenoid valve only closes when the compressor stops Electronic Expansion Valve The expansion valve is responsible for allowing the pr...

Page 12: ...all units All condensers are equipped with two relief valves and a shutoff valve Either end on the condenser can be easily removed in the field Refrigerant Charging PFS water cooled screw chillers ar...

Page 13: ...iquid Presence Sensor Each compressor is equipped with a liquid sensor to assure that liquid flows to the compressor for cooling and sealing during operation The sensor will shutdown the compressor if...

Page 14: ...hould come on If the output relay does not close perform the following tests 1 Check the voltages between L1 L2 L1 L3 and L2 L3 These voltages should be approximately equal and within 6 of the rated t...

Page 15: ...a single keypad display instead of reading gauges thermometers pots etc The display is a backlit 4 line by 40 character LCD type for easy viewing in all lighting conditions Two levels of security pro...

Page 16: ...Locations Terminal Block Low Voltage Wireway Signal Converter Signal Converter Guardister Board Guardister Board Low Voltage Wireway Transformer T3 Transformer T4 AOX Board EXV Modem Low Voltage Wirew...

Page 17: ...the electronic hardware and software required to monitor and control the unit It receives input from the ADI Board and sends commands to the Output Board to maintain the unit s optimum operating mode...

Page 18: ...ting power by closing CB 1 If the green running LED still does not turn on a hardware failure exists or the control software is corrupted Downloading new control software or replacing the 280 controll...

Page 19: ...al output board Analog Digital Input Board ADI The ADI Board provides low voltage power for the temperature and pressure sensors It also provides optical isolation between the Microprocessor Control B...

Page 20: ...put signal range of 0 10 VDC An additional output on the AOX board provides an analog signal that is proportional to compressor motor current Figure 5 AOX board Signal Converter Board The AC current s...

Page 21: ...perating power to the MicroTech controller and it s associated components T2 is a conventional ferrite core transformer that converts 120VAC from the control transformer into 24VAC T3 and T4 are trans...

Page 22: ...n indicator Keypad Display Operation General Description The MicroTech keypad consists of eighteen pressure sensitive membrane switches used to step through access and manipulate the information in th...

Page 23: ...peratures and pressures at the time the fault occurred Pressing the ALARM key at any time shifts the display to Menu 20 which is the first menu of the ALARM category Switch Key Pressing the SWITCH key...

Page 24: ...e At this point the password must be entered before the user can continue with the action Increment When changing the value of a menu item entry pressing INCR shifts the selected menu item to the next...

Page 25: ...ord access time will expire providing protection against unauthorized users Figure 13 Quick Access Group Display Format The information stored in the MicroTech controller tree structure can be viewed...

Page 26: ...on When the correct value or option is flashing press the enter key to store it into memory Pressing the Enter key a second time or pressing Clear Screens and menus cannot be changed while in the Chan...

Page 27: ...and line 3 field 2 indicates the leaving condenser water temperature Screen 2 Line 1 shows the interstage timer settings Pressing the switch key will toggle between this menu and Menu 13 Timers Item S...

Page 28: ...ps x 1 Starts 2 3 Compr Hours 1 1 Suction Line x F 1 Discharge x F 2 2 2 Suct Suprht x F 1 Dsch Suprht x F 2 Menu 3 Comp 2 Status Press the NEXT MENU key and Menu 3 will be displayed This menu has two...

Page 29: ...overy system multiplied by the water flow rate and a special factor would provide the amount of heat recovered in Btu s Item Screen Line Display Field Range 1 1 Ent Evap xx xo F 1 Ent Cond xx xo F 2 2...

Page 30: ...l be valid only if the chiller is controlling the cooling tower fans Line 2 field 1 indicates the entering condenser water temperature line 3 field 1 indicates the cooling tower by pass valve position...

Page 31: ...anual Off Automatic Manual Enable Service Testing Man Cmpr Load x Stgs 2 2 Comp 1 Mode 1 Comp 1 Stage x stgs 2 3 Comp 2 Mode 1 Comp 2 Stage x stgs 2 Manual Off This mode causes the chiller to stop If...

Page 32: ...nd cannot be changed Active spt indicates the current setpoint factoring in any reset signals that is controlling the chiller and can be used to determine if the chiller is maintaining leaving chilled...

Page 33: ...t are required by ice banks Ice option requires an external 24 Vac input to change the chiller from regular operation to ice operation The local spt should be set to equal the ice temperature plus the...

Page 34: ...nel will control the schedule The slave unit should be programmed the same as the master to have consistent operation should the network communications fail Sun through Fri The start time first value...

Page 35: ...in FloodWaitTmr x se 2 2 1 IntrstgTmr xx sec 1 Start Start This value determines the minimum time between chiller starts The chiller must run the time selected before it will start again If the chille...

Page 36: ...s value is the control band for the fan staging control logic This value must be exceeded to stage up or down Stage 1 On This value determines when the first stage control will start This value plus 1...

Page 37: ...n Pos At The outside air temperature associated with the Min Start Pos Max Pos At The outside air temperature associated with the Max Start Pos Menu 16 Alarm Setpoints Press the NEXT MENU key and Menu...

Page 38: ...38 PFS 155C 315C OM 135 3 LiqL Offset 1 9 9 15 0psi...

Page 39: ...tput 14 Off 1 Off On Output 17 Off 2 Off On 4 1 Output 18 Off 1 Off On Output 21 Off 2 Off On 2 Output 19 Off 1 Off On Output 22 Off 2 Off On 3 Output 20 Off 1 Off On Output 23 Off 2 Off On 5 1 DI 0 7...

Page 40: ...r port A This is critical if there is a network Port A baud rate must be set to 9600 on the master unit Full Load Amp This value must match the compressor label value indicating the RLAs of the chille...

Page 41: ...xpsi 1 Discharge xxx x o F 2 3 Evap Aprch xxx x o F 1 Dsch Suprht xxx x o F 2 3 1 Suct Suprhtxxx x o F 1 Evap Flow 0gpm 2 2 Subcool xxx x o F 1 Cond Flow xxxxgpm 2 3 EXV Position 0 1 Motor Current x...

Page 42: ...The information displayed can provide trouble shooting information Item Screen Line Display Field Range 1 1 Alarm Buffer 1 1 2 Alarm Buffer 2 1 3 Alarm Buffer 3 1 2 1 Alarm Buffer 4 1 2 Alarm Buffer 5...

Page 43: ...otor electrical trouble 12 See 6 7 8 above 13 Loose wiring 13 Check circuits for voltage at required points Tighten all power wiring terminals Compressor Noisy or Vibrating 1 Compressor internal probl...

Page 44: ...aks Repair and add charge 13 Low suction pressure 13 See corrective Steps for low suction pressure 14 Low ambient condition 14 Check cooling tower control operation 15 Compressor operating unloaded 15...

Page 45: ...X Reset leaving chilled water control to design Observe water temp And record amps X E Internal compressor check X II CONTROLS A Operating controls Check water temp Setpoints against operating temps X...

Page 46: ...e contactors hardware and operation X B Verify overload setting and trip X C Test electrical connections X D Pump down controls verify operation X VIII OPTIONAL CONTROLS A Hot gas bypass controls veri...

Page 47: ...OM 135 PFS 155C 315C 47 Notes...

Page 48: ...48 PFS 155C 315C OM 135 Notes...

Page 49: ...OM 135 PFS 155C 315C 49 Notes...

Page 50: ...Post Office Box 2510 Staunton Virginia 24402 2510 USA 540 248 0711...

Reviews: