Modes of Operation

Cool Mode

In Cool Mode, the compressor will start if the temperature at
the space temperature sensor is 1°F or higher than the set
point. It will stop if the space temperature sensor is 2°F or
lower than the set point, subject to timing requirements.

In the Cool Mode, the indoor fan will operate according to the
user settings for Fan Mode –  Continuous or Cycle and Speed.

Cold Start

Cold start is initiated when the control hasn’t called for cooling
for more than two (2) hours, or during a power-on-reset.

During cold start, the set point is lowered by 4°F (Tset-4°F) if
the differential calls for cooling.  The unit will operate in cold
start until the new set point is satisfied (+ or – 1°F), or until the
unit has run in cold start for at least 20 minutes.  After one or
both conditions are met, the set point will be reset to the user
setting and the unit will run in the regular cool mode.

The indoor fan will operate according to the user settings for
mode – Continuous or Cycle and Speed.

Cold start is not available with the 

Sleep

 feature.

Sleep Function

Sleep time is adjustable by the user from 1 to 15 hours in one
(1) hour increments in a closed loop. The sleep time is adjusted
and set via the touch pad and by pressing the Sleep Button
repeatedly. On the touch pad, the display will show the set
time in numbers for five (5) seconds. Before the sleep time
expires, the setting can be adjusted above the number of hours
passed by pressing the Sleep Button. Pressing the On/Off
Button can terminate the Sleep Mode.

A changeover from Heat to Cool or another Mode will reset
the Sleep Timer.

The Sleep Function will be deactivated by pressing the power-
on-reset or any button (except sleep) on the touch pad or the
Remote Control.

Cool Dry Mode

Select the Cool Dry Mode when the standard Cool Mode does
not provide sufficient dehumidification. In Cool Dry Mode,
the unit must run in Cool Mode for 12 minutes or until the
temperature differential between the room temperature and
the set point is less than 2°F. This will also occur after a Cold
Start or a Mode change from Cool to Cool Dry. During this
time the fan will operate in the Mode and Speed selected.

Until one or both of the above conditions are met, the control
will determine which Dry Mode (Zone) is initiated based on
the temperature differential between the room temperature (Tr)
and the temperature set point (Ts):

Figure 4. if Tr - Ts > 4°F, operation will be in Zone A
Figure 5. if 2°F < Tr - Ts < 4°F, operation will be in Zone B
Figure 6. if 0°F < Ts - Ts < 2°F, operation will be in Zone C
Figure 7. if Ts - Tr > 5°F, operation will be in Zone D
The other temperature ranges are dead bands for zone stability.

Figure 4. Zone A

Compressor

Low Fan

12 mins.

O n

O ff

O n

O ff

*

t

t

*

 = Zone Determination Time

Figure 5. Zone B

Figure 6. Zone C

Compressor

Low Fan

t

On

Off

On

Off

30 secs.

30 secs.

6 mins.

6 mins.

t

*

 =  Zone Determination Time

*

Figure 7. Zone D

Compressor

F an

t

O n

O ff

O n

O ff

t

12 mins.

*

*

 = Zone Determination Time

Summary of Contents for OM 813

Page 1: ...OM 813 Group PTAC Part No 106878501 Date August 2005 Digital Control For Incremental Top mounted Hydronic Heat Comfort Conditioners Operation Maintenance Data...

Page 2: ...ir Sensor Reading 7 Indoor Coil Sensor Reading 7 OutdoorAir Sensor Reading 8 Thermistor failure Code Condition 8 Compressor random restart 8 Unit Protective Logic 8 Compressor minimum run time 8 Compr...

Page 3: ...itioner and a source of heat The Digital Control is operated with a Touch Pad Inputs and Outputs The Digital Control offers the following inputs Indoor Coil Sensor ICS IndoorAir Sensor IAS OutdoorAir...

Page 4: ...SLEEP COOL COOL DRY FAN HEAT HIGH LOW CYCLE CONT LED 2 Digit Displays User Interface Touchpad and Display Low Voltage Communication Figure 2 Digital Controls on PDNS Unit Figure 3 Digital Control Touc...

Page 5: ...LED will be on and the fan will turn on at a call for heat or cooling FanCycleOperation On a call for Heating or Cooling the indoor fan and the heating source or the compressor will be activated When...

Page 6: ...rs for five 5 seconds Before the sleep time expires the setting can be adjusted above the number of hours passed by pressing the Sleep Button Pressing the On Off Button can terminate the Sleep Mode A...

Page 7: ...met the set point will be reset to the user s setting and the unit will run in regular heat mode Hot start is not available with the Sleep feature The fan will operate per the Fan Mode and Speed setti...

Page 8: ...ring room freeze conditions the temperature setting can be adjusted with the touch pad Fan modes and Sleep Operation are overridden during Room Freeze Protection Room Freeze Protection is active in al...

Reviews: