McQuay MicroTech II N2 Installation And Maintenance Manual Download Page 12

13600 Industrial Park Boulevard, Minneapolis, MN 55440 USA (763) 553-5330 (www.mcquay.com)

Service Information

Test Procedures

If you can control the unit from the keypad but are unable to communicate with it via the network,
try the following:

 

Verify the network (bus) wiring

 

Check the integrity of the cable harness to the network terminals

 

Verify that the N2 address (SW1) is set to a unique binary number between 1 and 253.

If the MicroTech II N2 Open communication module still doesn’t respond, replace the
communication module.

List of Replaceable Parts

Network Connection Plug

Generic Replacement Parts

The three-contact network connector plug has custom markings, but if you lose this terminal block
you can replace it with a standard block without the markings from a manufacturer. The list below
contains manufacturers part numbers for equivalent parts without the custom markings.

Manufacturer

Telephone

Order Number

Phoenix Contact

(800) 888-7388

17 57 02 2

Altech Corp

(908) 806-9400

37.003

Direct Replacement Parts

You can order direct replacement parts for these connector plugs from McQuay International
(1-800-37-PARTS).

Part Number

Description

AS-TBKIT-0

5 terminal blocks marked REF, N2- and N2+

Kit 

Component

Description

Part No.

Kit

N2 communication module for unit ventilators with standoffs

107293125

Summary of Contents for MicroTech II N2

Page 1: ...Installation and Maintenance Manual IM 730 0 Group McQuay Controls Date July 2002 2002 McQuay International MicroTech II AAF HermanNelson Unit Ventilator Controller N2 Open Communication Modules...

Page 2: ...ese steps 9 To replace a MicroTech II N2 communication module on a MicroTech II Unit Controller board follow these steps 10 SERVICE INFORMATION 12 TEST PROCEDURES 12 LIST OF REPLACEABLE PARTS 12 Netwo...

Page 3: ...Model 12 OM756 www McQuay com 4 pipe Heat Cool Valve Control Software Model 13 4 pipe Heat Cool F BP Damper Control Software Model 14 OM757 www McQuay com 2 pipe Cooling Only Valve Control Software Mo...

Page 4: ...e control panel before performing any service work Never unplug cables circuit board terminal blocks or power plugs while power is applied to the panel NOTICE This equipment generates uses and can rad...

Page 5: ...e of N2 points between the network and the Unit Controller Component Data Figure 2 shows the major components of the communication module Figure 2 MicroTech II N2 communication module major components...

Page 6: ...s 1 through 253 Figure 3 Address switch S1 Dip switch settings and how they work When a switch is in the up open position its value is 0 So when all the switches are in the up there is no module addre...

Page 7: ...Bus Information The N2 communication Bus is a local network that links controllers and point interfaces to the Network Control module NCM The N2 Bus uses a master slave protocol in which the master d...

Page 8: ...o the bus when you reach 49 devices Count each repeater as one device Any path from the NCM to an N2 device cannot go through more than two repeaters or two pairs of fiber modems i e cascaded repeater...

Page 9: ...e locking standoffs into the holes on the board Then locate the empty connector for the MicroTech II N2 communication module on the Unit Controller board see Figure 8 4 Orient the communication module...

Page 10: ...module from each standoff and pull the module over the standoffs 7 Gently lift the MicroTech II N2 communication module from the Unit Controller board 8 Locate the empty connector pins and three stand...

Page 11: ...IM 730 0 11 Figure 8 Communication module mounting detail Figure 9 N2 module typical wiring...

Page 12: ...twork Connection Plug Generic Replacement Parts The three contact network connector plug has custom markings but if you lose this terminal block you can replace it with a standard block without the ma...

Reviews: