(6) Additional Charge
•
The refrigerant gas has already charged into the outdoor unit. For the piping length of 5m. Additional
refrigerant charge after vacuuming is not necessary.
•
When the piping length is more than 5m, please use the table below (unit in gram).
MODEL 7m 10m 15m 20m 35m
020D/ 020DR
30/50
75/125 150/250 225/375
-
025D/ 025DR
76/100
190/250 380/500 570/750
-
030D/
030DR
100 250 500 750 1500
040D/
040DR
100 250 500 750 1500
050D/
050DR
100 250 500 750 1500
061C/CR 220
550 1100 1650 3300
Diagram shows typical charging method.
CAUTION FOR R407C
Avoid prolong exposure of an opened compressor, or the internal part of refrigerant piping to moist air.
The POE oil in the compressor and piping can absorb moisture
from air.
(7) Overall Checking
•
•
•
•
Ensure the following, in particular :
1) The unit is mounted solidly and rigid in position.
2) Piping and connections are leak proof after charging.
3) Proper wiring has been done.
Drainage check - pour some water into drain pan.
Test
run
1) Conduct a test run after water drainage test and gas leakage test.
2) Watch out for the following :
a) Is the electric plug firmly inserted into the socket?
b) Is there any abnormal sound from unit?
c) Is there any abnormal vibration with regard to unit itself or piping?
d) Is there smooth drainage of water?
Check that :
1) Outdoor fan is running, with warm air blowing off the outdoor unit (cooling cycle).
2) Indoor blower is running and discharge cool air (cooling cycle).
3) Suction (low side) pressure is as per recommendations.
4) The remote controller has incorporated a 3 minutes delay in the circuit. Thus, it requires about 3
minutes before the outdoor unit can start up.
Page 73
Summary of Contents for MCM 020 D
Page 23: ...MODEL MCM020DR MLC M4LC020BR MODEL MCM025DR MLC M4LC025BR MCM030DR MLC030BR Page 22...
Page 41: ...MODEL MLC M4LC061 C CR Page 40...
Page 43: ...INDOOR UNIT MODEL MCM030D OUTDOOR UNIT MODEL MLC030B Page 42...
Page 44: ...INDOOR UNIT MODEL MCM030D OUTDOOR UNIT MODEL MLC M4LC030C Page 43...
Page 45: ...INDOOR UNIT MODEL MCM040D OUTDOOR UNIT MODEL MLC035C Page 44...
Page 46: ...INDOOR UNIT MODEL MCM040 050D OUTDOOR UNIT MODEL MLC M4LC040 050C Page 45...
Page 47: ...INDOOR UNIT MODEL MCM061 062C OUTDOOR UNIT MODEL M4LC060C Page 46...
Page 48: ...INDOOR UNIT MODEL MCM061 062C OUTDOOR UNIT MODEL MLC M4LC061C Page 47...
Page 49: ...HEAT PUMP INDOOR UNIT MODEL MCM020 025DR OUTDOOR UNIT MODEL MLC M4LC020 025BR Page 48...
Page 50: ...INDOOR UNIT MODEL MCM030DR OUTDOOR UNIT MODEL MLC030BR Page 49...
Page 51: ...INDOOR UNIT MODEL MCM030DR OUTDOOR UNIT MODEL MLC M4LC030CR Page 50...
Page 52: ...INDOOR UNIT MODEL MCM040DR OUTDOOR UNIT MODEL MLC035CR Page 51...
Page 53: ...INDOOR UNIT MODEL MCM040 050DR OUTDOOR UNIT MODEL MLC M4LC040 050CR Page 52...
Page 54: ...INDOOR UNIT MODEL MCM061 062CR OUTDOOR UNIT MODEL MLC M4LC061CR Page 53...
Page 55: ...INDOOR UNIT MODEL MCM061 062CR OUTDOOR UNIT MODEL MLC M4LC060CR Page 54...
Page 94: ...2004 McQuay International 1 800 432 1342 www mcquay com ISO 9002 REGISTERED...