Heat Pump Unit (50Hz)
MODEL
MAC050CR MAC065CR MAC070CR
Btu/hr
46,100
57,000
65,500
kcal/hr
11,610
14,360
16,510
NOMINAL COOLING CAPACITY
Watt
13,500
16,700
19,200
Btu/hr
49,500
65,500
71,000
kcal/hr
12,470
16,510
17,880
NOMINAL HEATING CAPACITY
Watt
14,500
19,200
20,800
MATERIAL
Electro-galvanised Mild Steel
FINISH
Polyester Power
CASING
THICKNESS mm
1
HEIGHT (H)
mm (in)
1560 (61.4)
1700 (66.9)
WIDTH (W)
mm (in)
927 (36.5)
1135 (44.7)
TOTAL
UNIT
DIMENSION
DEPTH (D)
mm (in)
406 (16)
502 (19.7)
NET WEIGHT
kg
160 230 245
NOISE LEVEL
dB(A)
60 64 64
EVAPORATOR
TYPE
Brazed Plate Heat Exchanger
PLATE MATERIAL
Stainless Steel
HEAT EXCHANGE AREA
m
2
1.3 1.4 1.7
NOMINAL WATER FLOW
l/s
0.64 0.79
0.91
BPHE PRESSURE DROP VS NOMINAL FLOW RATE
kPa
5 34
36.5
UNIT PRESSURE DROP WS NOMINAL FLOW RATE
kPa
75 92 110
WATER LINE(HYDRAULIC KIT)
TYPE
Horizontal Multistage End-Suction
POWER SUPPLY
V/Ph/Hz
220 / 1 / 50
380 / 3 / 50
RUNNING CURRENT
Amp
2.5 1.3 1.3
PUMP
WATER FLOW RATE
GPM U.S. (l/s)
10.21 (0.64)
12.63 (0.79) 14.53
(0.91)
INSTALLATION PIPE CONNECTION
mm (in)
34 ( Rc 1)
34 ( Rc 1)
34 ( Rc 1)
PIPING
HEAD m
23 24 23
CONDENSER COIL
TYPE
Cross Finned Tubes
MATERIAL
Seamless Copper
WALL THICKNESS
mm (in)
0.35 (0.014)
TUBE
OUTER DIAMETER
mm (in)
9.52 (3/8)
MATERIAL
Aluminium
THICKNESS mm
(in)
0.127 (0.0005)
ROWS
2 2 2
FIN
FINS PER INCH
14 14 14
FACE AREA
m
2
(ft
2
)
1.23 (13.24)
1.74 (18.73)
1.74 (18.73)
CONDENSER FAN
TYPE/DRIVE
Propeller/Direct
QUANTITY
1 1 1
BLADE MATERIAL
Aluminium Alloy
BLADE DIAMETER
mm (in)
600 (23.6)
710 (28)
710 (28)
POWER SUPPLY
V/Ph/Hz
220 / 1 / 50
220 / 1 / 50
220 / 1 / 50
RATED RUNNING CURRENT
Amp
0.9 1.2 1.2
RATED INPUT
Watt
200 250 250
RATED OUTPUT
Watt
120 130 130
MOTOR POLES
8 10 10
AIR VOLUME
cmm/cfm
100 / 3530
133 / 4700
133 / 4700
COMPRESSOR
TYPE
Scroll Scroll Scroll
POWER SUPPLY
V/Ph/Hz
380 / 3 / 50
380 / 3 / 50
380 / 3 / 50
RATED RUNNING CURRENT (COOLING)
Amp
8.0
10.4 11.9
RATED RUNNING CURRENT (HEATING)
Amp
8.0
11.4 11.5
RATED INPUT (COOLING)
Watt
4,800
5,000
6,400
RATED INPUT (HEATING)
Watt
4,820
5,700
6,100
MAXIMUM STARTING CURRENT
Amp
74 101 95
PROTECTION DEVICES
Overload Protection, Flow Switch and H/L Pressure Switch
STAGE OF CAPACITY CONTROL
On/Off
REFRIGERANT
TYPE
R22
CONTROL
Capillary Tube
CHARGING MASS
kg
3.8 5.15 7
Notes:
1.
All specifications are subjected to change by manufacturer without prior notice.
2.
Nominal cooling values are based on entering/leaving chilled water temperature 12ºC/7ºC and air ambient temperature 35ºC.
3.
Nominal heating values are based on entering/leaving hot water temperature 40ºC/45ºC and air ambient temperature 7ºC.