Application Information
M5MSY
_(i)
REFRIGERANT PIPING
Piping Length & Elevation
If the pipe is too long, both capacity and reliability of the unit will drop. As the number of bends increases,
resistance to the
fl
ow of refrigerant system increases, thus lowering cooling capacity. As a result, the
compressor may become defective. Always choose the shortest path and not exceed the maximum piping
length as tabulated below.
Model
Maximum
Total Piping
Length (m)
Single Indoor
Maximum
Piping
Length(m)
Maximum
height
Difference(m)
Pre-charged
Total Piping
length (m)
Outdoor Unit
Pre-charged
(kg)
Amount of
Additional
Charge (g/m)
M5MSY18BR
(2 Ports)
L
1
+ L
2
≤
30
L
≤
20
H
≤
15
15
1.2
20
M5MSY20BR
(2 Ports)
L
1
+ L
2
≤
50
L
≤
25
H
≤
15
30
2.0
20
M5MSY25BR
(3 Ports)
L
1
+ L
2
+ L
3
≤
60
L
≤
25
H
≤
15
30
2.6
20
M5MSY30BR
(4 Ports)
L
1
+ L
2
+ L
3
+ L
4
≤
60
L
≤
25
H
≤
15
30
2.6
20
INDOOR UNIT
OUTDOOR UNIT
VERTICAL HEIGHT
DIFFERENCE MAX. H
* Remark : Applicable for Wall Mounted, Ceiling Cassette, Ceiling Concealed, Ceiling Convertible unit.
Summary of Contents for M5MSY18BR
Page 35: ...33 Outline and Dimension M5MSY_ i Indoor Unit Model M5CMY 15 20 25ER Note Dimension in mm...
Page 38: ...36 M5MSY_ i Wiring Diagram Indoor Unit Model M5WMY10 15JR LR Indoor Unit Model M5WMY20JR...
Page 39: ...37 Wiring Diagram M5MSY_ i Indoor Unit Model M5CKY10 15 20CR Indoor Unit Model M5CCY10 15CR...
Page 40: ...38 M5MSY_ i Wiring Diagram Indoor Unit Model M5CCY20CR Indoor Unit Model M5CMY15ER...
Page 41: ...39 Wiring Diagram M5MSY_ i Indoor Unit Model M5CMY20ER...