McQuay LDD Installation & Maintenance Data Download Page 8

Page 8 of 24 / IM 439

2.

The system should be filled at the city water makeup
connection with all air vents open. After filling, vents should
be closed.

The contractor should start main circulator with pres-

sure reducing valve makeup open. Vents should be
checked in sequence to bleed off any trapped air to as-
sure circulation through all components of the system.

Power to the heat rejector unit should be off, and the

supplementary heat control set at 80

°

F (27

°

C).

While circulating water, the contractor should check

and repair any leaks in the piping. Drain at the lowest
point(s) in the system should be opened for initial flush
and blowdown, making sure city water fill valves are set
to make up water at the same rate. Check the pressure
gauge at pump suction and manually adjust the makeup
to hold the same positive steady pressure both before
and after opening the drain valves. Flush should con-
tinue for at least two hours, or longer if required, to see
clear, clean drain water.

3.

Supplemental heater and circulator pump should be shut
off. All drains and vents should be opened to completely
drain down the system. Short circuited supply and re-
turn runouts should now be connected to the conditioner
supply and return connections. Teflon tape is recom-
mended over pipe dope for pipe thread connections. Use
no sealers at the swivel flare connections of hoses.

4.

Trisodium phosphate was formerly recommended as a
cleaning agent during flushing. However, many states
and localities ban the introduction of phosphates into their
sewage systems. The current recommendation is to sim-
ply flush longer with warm 80

°

F (27

°

C) water.

5.

Refill the system with clean water. Test the litmus paper
for acidity, and treat as required to leave the water slightly
alkaline (pH 7.5 to 8.5). The specified percentage of anti-
freeze may also be added at this time. Use commercial
grade anti-freeze designed for HVAC systems only. Do
not use automotive grade anti-freeze.

6.

Set the system control and alarm panel heat add setpoint
to 70

°

F (21

°

C) and the heat rejection setpoint to 85

°

F

(29

°

C). Supply power to all motors and start the circulat-

ing pumps. After full flow has been established through
all components including the heat rejector (regardless of
season) and air vented and loop temperatures stabilized,
each of the conditioners will be ready for check, test and
start-up and for air and water balancing.

Start-up

1. Open all valves to full open position and turn on power to

the conditioner.

2. Set thermostat for 

Fan Only

 operation by selecting 

Off

 at

the system and 

On

 at the fan switch. If 

Auto

 fan operation

were selected, the fan would cycle with the compressor.
Check for proper air delivery.

3. All units have variable pitch motor sheaves. Reset for

correct airflow.

4. Set thermostat to 

Cool

. If the thermostat is an automatic

changeover type, simply set the cooling temperature to
the coolest position. On manual changeover types addi-
tionally select 

Cool

 at the system switch.

Again, many conditioners have time delays which

protect the compressor against short cycling. After a few
minutes of operation, check the discharge grilles for cool
air delivery. Measure the temperature difference between
entering and leaving water. It should be approximately
1

1

2

  times greater than the heating mode temperature

difference. For example, if the cooling temperature dif-
ference is 15

°

F (8

°

C), the heating temperature difference

should have been 10

°

F (5

°

C).

Without automatic flow control valves, a cooling tem-

perature difference of 10

°

F to 14

°

F (5

°

C to 8

°

C) is about

right. Adjust the combination shutoff/balancing valve in
the return line to a water flow rate which will result in the
10

°

F to 14

°

F (5

°

C to 8

°

C) degree difference in cooling.

5. Set thermostat to 

Heat

. If thermostat is the automatic

changeover type, set system switch to the 

Auto

 position

and depress the heat setting to the warmest selection.
Some conditioners have built-in time delays which pre-
vent the compressor from immediately starting. With
most control schemes, the fan will start immediately.
After a few minutes of compressor operation, check for
warm air delivery at discharge grille. If this is a “cold
building” start-up, leave unit running until return air to the
unit is at least 65

°

F (18

°

C).

Measure the temperature difference between enter-

ing and leaving air and entering and leaving water. With
entering water of 60

°

F to 80

°

F (16

°

C to 27

°

C), leaving

water should be 6

°

F to 12

°

F (3.3

°

C to 6.6

°

C) cooler, and

the air temperature rise through the machine should not
exceed 35

°

F (19

°

C). If the air temperature exceeds 35

°

F

(19

°

C), the airflow rate is probably inadequate.

If the water temperature difference is less than 6

°

F

(3.3

°

C) degrees, the water flow rate is excessive. If the

water temperature difference exceeds 12

°

F (6.6

°

C), then

the water flow rate is inadequate.

6. Check the elevation and cleanliness of the condensate

line. If the air is too dry for sufficient dehumidification,
slowly pour enough water into the condensate pan to
ensure proper drainage.

7. If the conditioner does not operate, the following points

should be checked:
a. Is proper voltage being supplied to the machine?
b. Is the proper type of thermostat being used?
c. Is the wiring to the thermostat correct?

8. If the conditioner operates but stops after a brief period,

check for:
a. Is there proper airflow? Check for dirty filter, incorrect

fan rotation (3-phase fan motors only), or incorrect
ductwork.

b. Is there proper water flow rate within temperature limits?

Check water balancing; backflush unit if dirt-clogged.

9. Check the unit for vibrating refrigerant piping, fan wheels,

etc.

10. Do not lubricate the fan motor during the first year of

operation as it is prelubricated at the factory.

Cleaning and Flushing System 

(Continued)

Summary of Contents for LDD

Page 1: ...tallation Maintenance Data IM 439 15 Group WSHP Part Number 106581103 Date June 2006 Large Vertical Water Source Heat Pumps 6 thru 25 Tons Models LDD LDE LDL LDS LME LMH LML LMS 2006 McQuay Internatio...

Page 2: ...xt Range LMH High Static Large Vertical Mark IV Std Range LDL Std Large Vertical DDC Controls Ext Range Less Board LML High Static Large Vertical Mark IV Ext Range LDS Std Large Vertical DDC Controls...

Page 3: ...on submittal drawings 7 The installing contractor will find it beneficial to confer with piping sheetmetal ceiling and electrical foremen together before installing any conditioners Note Check the un...

Page 4: ...2 114 mm 51 2 140 mm 25 8 61 mm Figure 2 Side view from piping end Each unit is shipped with a filter bracket for side filter removal Two fan discharges and piping arrangements are available With the...

Page 5: ...pitch diameter for desired speed by open ing moving parts by half or full turns from closed position Do not open more than five full turns 3 Replace external key E and securely tighten setscrews B ove...

Page 6: ...ication limits It is also general practice to close off the ventilation air system during unoccupied peri ods night setback The ventilation air system is generally a separate build ing subsystem with...

Page 7: ...he union one to hold the line and one for simultaneous tightening of the nut 4 Supply and return shutoff valves are required at each con ditioner The return valve is used for balancing and should have...

Page 8: ...ermostat to Cool If the thermostat is an automatic changeover type simply set the cooling temperature to the coolest position On manual changeover types addi tionally select Cool at the system switch...

Page 9: ...e with local codes or the National Electrical Code whichever is applicable 2 Apply correct line voltage to the unit Each unit is supplied with a 3 lug terminal block in the main control for three phas...

Page 10: ...BK 21 15 Fan Motor GN GND YE RD BK Common Comp Fan Mark IV AC Board Compressor Contactor 36 35 21 L1 37 37 Breaker Optional OR 230V RD 208V BK RD 460V BK BK YE GND Xformer REV Valve Solenoid COF LT L...

Page 11: ...itch BK WH BK WH BR BR BL BL BR53 Low Temp BR BR BL BL RD54 BR52 BK51 BL50 BL40 BK41 BR43 RD44 BR42 BK51 BL50 BL40 BK41 YE Condensate Overflow Sensor BK30 BK49 RD48 BK BK BK59 RD58 BK BK 1 2 5 3 4 BR8...

Page 12: ...troller 68 67 66 65 64 63 62 1 2 3 4 5 6 7 11 10 9 8 7 6 5 4 3 2 1 J6 2 3 4 5 7 8 9 10 11 J5 J4 Low Temp SIG Lo Press SIG Condensate Lo Temp SRC RV Out Comp Com Comp Out Fan Com Fan Out 24VAC 24V Gnd...

Page 13: ...3 4 1 2 3 4 1 J2 J1 2 1 46 Disch Air Water Out 44 42 43 Condensate Lo Temp SRC Lo Temp SIG Lo Press SIG Lo Press SRC Hi Press SIG RV Com RV Out Comp Com Comp Out Fan Com Fan Out 24VAC 24V Gnd Dischar...

Page 14: ...he reversing valve is set up to be energized in the heating mode The circuit board has a fan interlock circuit to energize the fan whenever the compressor is on if the thermostat logic fails to do so...

Page 15: ...s of the standard thermostat are then connected to the Mark IV AC board thermostat inputs and control inputs as needed Any re maining board input s may be operated by additional thermostat out puts or...

Page 16: ...application guide LIA217 for thermostat 107095901 installation details WSHP Mark IV AC Board Low Voltage Terminal Strip Circuit1 O W2 G W1 Y1 F E L U A P V R C R C W1 Y1 W2 Y2 G Thermostat Terminals W...

Page 17: ...t Sizes 180 to 290 Non Programmable Electronic Thermostat 2 Circuits P N 107095901 7 Day Programmable Electronic Thermostat 2 Circuits P N 107095901 Includes Thermostat and Wall Plate Refer to the ins...

Page 18: ...ressor operation is required the Mark IV AC P terminal will change state causing a contact closure between terminal 58 and 64 signaling the loop water control LWC panel to restart the loop pump if Off...

Page 19: ...wn below can only be used when the P terminal is not being used as a pump restart signal to other equipment If the P terminal must be used as a pump restart signal to other equipment then wire the aux...

Page 20: ...kit you attach the sheet metal enclosure to the unit as shown route the 4 wire harness through knockouts and connect to the Mark IV AC board mount and connect and insulate the water tempera ture senso...

Page 21: ...rmally open contacts will close Operation In this example the auxiliary relay is used to interface other control devices to the Mark IV AC board Using the Orange and White wires and 24vac or 24vdc ano...

Page 22: ...ot required 3 Fresh Air Damper These outputs provide a signal that can be used to control a remote fresh air damper The output will energize when the unit fan is energized and de energize when the uni...

Page 23: ...eating Check compressor wiring for defective wiring or loose connection Check thermostat for improper location Check for defective compressor internal windings with ohm meter Check for bad compressor...

Page 24: ...s will depend upon the project requirements Some applications such as motels produce a lot of lint from carpeting and linen changes and will require more frequent filter changes It is suggested that t...

Reviews: