ALR 110F – 150F
Product Manual ALR2-3
Electrical Data
Table 10, ALR 110F - 150F, Electrical Data, Single Point
Fuse or HACR Breaker Size
Field Wire
Hub
(Conduit Connection)
ALR
Unit
Size
Volts
Hz
Min. Circuit
Ampacity
(MCA)
Quantity
Wire Gauge
Quantity
Size
Recommended
Maximum
208
503
6
400
1
4.00 (102)
600
600
230
492
6
350
1
4.00 (102)
600
600
460
248
3
250
1
2.50 (64)
300
300
110F
575
60
188
3
3/0
1
2.00 (51)
200
225
208
555
6
500
1
4.00 (102)
600
600
230
526
6
400
1
4.00 (102)
600
500
460
274
3
300
1
2.50 (64)
300
300
120F
575
60
200
3
4/0
1
2.00 (51)
225
225
208
592
6
500
1
4.00 (102)
700
700
230
554
6
500
1
4.00 (102)
600
600
460
293
3
350
1
2.50 (64)
300
350
130F
575
60
210
3
4/0
1
2.00 (51)
225
250
208
626
6
400
2
2.50 (64)
700
700
230
590
6
350
2
2.50 (64)
700
700
460
302
3
350
1
2.50 (64)
350
350
135F
575
60
224
3
4/0
1
2.00 (51)
250
250
208
656
6
400
2
3.00 (76)
700
700
230
622
6
400
2
3.00 (76)
700
700
460
310
3
400
1
2.50 (64)
350
350
140F
575
60
236
3
250
1
2.50 (64)
250
250
208
656
6
400
2
3.00 (76)
700
700
230
622
6
400
2
3.00 (76)
700
700
460
310
3
400
1
2.50 (64)
350
350
145F
575
60
236
3
250
1
2.50 (64)
250
250
208
690
6
500
2
3.00 (76)
800
800
230
666
6
500
2
3.00 (76)
800
800
460
334
3
400
1
3.00 (76)
350
400
150F
575
60
261
3
300
1
2.50 (64)
300
300
NOTES
1.
A "HACR" breaker is a circuit breaker designed for use on equipment with multiple motors. It stands for Heating, Air Conditioning, Refrigeration.
2.
See page 25 for other Electrical Data notes.