![McQuay AGZ 030AM Product Manual Download Page 27](http://html1.mh-extra.com/html/mcquay/agz-030am/agz-030am_product-manual_1756096027.webp)
Product Manual AGZ-2
AGZ 030A through 065A
27
Notes for “Electrical Data Single Point” Power:
1.
Unit wire size ampacity (MCA) is equal to 125% of the largest compressor-motor RLA plus
100% of RLA of all other loads in the circuit including the control transformer.
2.
If the control transformer option is furnished, no separate 115V power is required.
3.
If a separate 115V power supply is used for the control circuit, then the wire sizing amps is 10
amps for all unit sizes.
4.
Recommended power lead wire sizes for 3 conductors per conduit are based on 100% conductor
ampacity in accordance with NEC. Voltage drop has not been included. Therefore, it is
recommended that power leads be kept short. All terminal block connections must be made with
copper (type THW) wire.
5.
“Recommended Fuse Sizes” are selected at approximately 150% to 175% of the largest
compressor RLA, plus 100% of all other loads in the circuit.
6.
“Maximum Fuse or HACR breaker size” is selected at approximately 225% of the largest
compressor RLA, plus 100% of all other loads in the circuit.
7.
The recommended power lead wire sizes are based on an ambient temperature of 86°F (30°C).
Ampacity correction factors must be applied for other ambient temperatures. Refer to the
National Electrical Code Handbook.
8.
Must be electrically grounded according to national and local electrical codes.
9.
MCA may vary slightly due to fan motor options such as SpeedTrol, TEFC.
Voltage Limitations:
Within
±
10 percent of nameplate rating
Notes for “Compressor and Condenser Fan Amp Draw”:
1.
Compressor RLA values are for wiring sizing purposes only but do not reflect normal operating
current draw at rated capacity. If unit is equipped with SpeedTrol condenser fan motors, the first
motor on each refrigerant circuit is a single phase, 1hp motor, with a FLA of 2.8 amps at 460
volts, 5.6 amps at 208, 230, and 575 volts.
2.
Compressor LRA for reduced inrush start are for the first winding only. If the unit is equipped
with SpeedTrol motors, the first motor is a single phase, 1 hp motor, with a LRA of 7.3 amps at
460 volts, 14.5 amps at 208, 230, and 575 volts.
Notes for “Field Wiring Data”
1.
Requires a single disconnect to supply electrical power to the unit. This power supply must either
be fused or use an HACR type circuit breaker.
2.
All field wiring to unit power block or optional non-fused disconnect switch must be copper.
3.
All field wire size values given in table apply to 75°C rated wire per NEC.
Summary of Contents for AGZ 030AM
Page 51: ......
Page 52: ...P O Box 2510 Staunton Virginia 24402 2510 USA 540 248 0711...