background image

© 2011 Pentair Technical Products

89056287

- 6 -

TECHNICAL INFORMATION

Sequence of Operation

The air conditioner comes standard with two internally mounted thermostats. There are two modes of operation; 

heating and cooling. During heating and cooling modes, the evaporator fan will be running.

Heating

When the enclosure temperature is below the heating thermostat setpoint, power is applied to the heaters. 

When the enclosure temperature is 10 degrees above the setpoint, the heater is powered off.

Cooling

When the enclosure temperature is above the cooling thermostat setpoint, power is applied through the 

thermostat. The compressor is then energized either directly or through a contactor if unit requires one. The 

condenser impellers will start immediately if the unit is not equipped with an optional head pressure control 

switch. If the unit is equipped with an optional head pressure control switch, the condenser impellers will 

start once the refrigerant pressure reaches the setting of the switch. Component specific information is listed 

below.
Operating the air conditioner below the minimum ambient temperature or above the maximum ambient 

temperatures indicated on the nameplate voids all warranties. DO NOT set the enclosure thermostat to a 

temperature lower than 70 F. Doing so can increase the likelihood of frost buildup on the evaporator coil.
The moisture that the enclosure air can contain is limited. If moisture flows from the drain tube continuously 

this can only mean that ambient air is entering the enclosure. Be aware that frequent opening of the 

enclosure’s door admits humid air that the air conditioner must then dehumidify.

Standard and Optional Component Operation

Thermostat

The G52 air conditioner uses our standard 10-1061-16 thermostat. The thermostat setpoint equals the 

temperature that the air conditioner turns off. The thermostat has a 10 F differential from setpoint until it calls 

for cooling or heating. An example of operation is shown below.

For cooling (75-100 F range):

• 

Thermostat setpoint = 80 F

• 

Cooling turns on at 90 F

• 

Cooling turns off at 80 F

For heating (55-65 F range):

• 

Thermostat setpoint = 55 F

• 

Heating turns on at 55 F

• 

Heating turns off at 65  F

NOTE: For testing purposes only, the thermostat stop screw may be removed (on units so 

equipped) to allow settings below 70 F. After testing, replace the stop screw and verify that the 

thermostat cannot be set below 70 F. Extended operation below 70 F can cause coil freeze ups 

resulting in reduced load and/or unit damage.

Head Pressure Control

Unit is set at the factory, no adjustment necessary.
At a saturated condenser temperature of 85 F (95 psig), the condenser fans will power off. At a saturated 

condenser temperature of 118 F (165 psig), the condenser fans will power on.

Contactor (115V 12000 BTU/Hr.. Units only)

The contactor on this model uses a 115V coil.

Summary of Contents for SPECTRACOOL G52 1-Phase

Page 1: ...Rev D P N 10 1008 232 Protecting Electronics Exceeding Expectations Pentair Technical Products 2100 Hoffman Way Anoka MN 55303 1 763 323 8200 1 763 576 3200 www McLeanCoolingTech com INSTRUCTION MANUA...

Page 2: ...racteristics 9 Functional Data 10 SERVICE DATA 10 Components List 10 Wire Diagrams and Schematics 11 G521216GXXX Generic Wire Diagram actual unit options may vary 11 G521216GXXX Generic Schematic actu...

Page 3: ...r while it is horizontal or on its side back or front The refrigeration compressor is filled with lubricating oil This will cause permanent damage to the air conditioner and also voids the warranty CA...

Page 4: ...tions i e 12 12 000 BTU Hr at 131 131 F 3 1 115 Volt 2 230 Volt 4 460 Volt 4 6 50 60 Hz or 60 Hz only 5 Unique set of numbers for each air conditioner which identifies the accessories on a model AMBIE...

Page 5: ...ld cause rips or tears in the gasket and risk losing the water tight seal 4 Allow unit to remain upright for a minimum of five 5 minutes before starting CAUTION Air conditioner must be in upright posi...

Page 6: ...st buildup on the evaporator coil The moisture that the enclosure air can contain is limited If moisture flows from the drain tube continuously this can only mean that ambient air is entering the encl...

Page 7: ...7 6 8 75 23 9 78 20 28 9 4 80 26 7 86 7 15 26 1 0 85 29 4 95 10 23 3 2 90 32 2 105 5 20 6 4 95 35 113 3 0 17 8 7 5 100 37 8 125 5 15 9 105 40 6 135 10 12 2 12 110 43 3 146 7 15 9 4 15 115 46 1 157 5...

Page 8: ...bient BTU Hr W 6000 6800 Cooling Capacity at Max Conditions BTU Hr W 7300 8200 Maximum Ambient Temp 131 F 55 C Minimum Ambient Temp 40 F 40 C Enclosure Airflow 285 310 CFM External Airflow 650 700 CFM...

Page 9: ...ient BTU Hr W 9900 10700 Cooling Capacity at Max Conditions BTU Hr W 12000 12500 Maximum Ambient Temp 131 F 55 C Minimum Ambient Temp 40 F 40 C Enclosure Airflow 287 305 CFM External Airflow 635 650 C...

Page 10: ...2 08 Capacitor Compressor Run 52 6032 01 S 6173 52 6032 06 52 6032 01 Capacitor Impellers 3 52 6032 13 52 6032 14 52 6032 13 52 6032 14 Coil Condenser 52 6010 14 52 6010 14 52 6010 10 52 6010 10 Coil...

Page 11: ...CONNECTOR AS VIEWED FROM INSIDE OF UNIT HEATING THERMOSTAT COOLING THERMOSTAT RELAY HEATER CAPACITOR CAPACITOR ENCLOSURE AMBIENT COMPRESSOR HEAD PRESSURE CONTROL OPTIONAL RUN CAPACITOR START CAPACITOR...

Page 12: ...NSFORMER WITH TEMPERATURE DISPLAY OPTIONAL THERMOSTAT HEATING LIMIT SWITCHES AND HEATER AMBIENT IMPELLER WITH HEAD PRESSURE CONTROL OPTIONAL HARD START RELAY RUN CAPACITOR START CAPACITOR SUPPRESSOR O...

Page 13: ...D FROM INSIDE OF UNIT HEATING THERMOSTAT COOLING THERMOSTAT RELAY HEATER CAPACITOR CAPACITOR ENCLOSURE AMBIENT COMPRESSOR HEAD PRESSURE CONTROL OPTIONAL RUN CAPACITOR START CAPACITOR TO THERMAL DISPLA...

Page 14: ...sor will stop operating due to actuation of the thermal overload cut out switch located on the compressor housing As soon as the compressor temperature has dropped to within the switch s cut in settin...

Page 15: ...cial recommendations CAUTION Refrigerant Loss Each air conditioner is thoroughly tested prior to leaving the factory to insure against refrigeration leaks Shipping damage or microscopic leaks not foun...

Page 16: ...ers for airflow Is there airflow YES proceed to step 6 NO possible problem Defective thermostat Open motor winding Stuck impeller motor Obstructed wheel Repair or Replace defective part 6 Carefully ch...

Page 17: ...sor tries to start but won t run Low line voltage at start Should be 10 rated voltage Compressor motor stuck Bad contactor Bad overload switch Bad run start capacitor Unit blows breakers Undersized br...

Page 18: ...out written Pentair Technical Products approval Pentair Technical Products must be notified of a claim in writing not later than fourteen 14 days from the date when Buyer has become aware of such occu...

Page 19: ...aterial will be scrapped and all shipping expenses and corresponding analysis fees will be billed to Buyer E At Buyer s request Failure Analysis can be provided by Pentair Technical Products for warra...

Page 20: ...r Technical Products 89056287 Rev D P N 10 1008 232 Protecting Electronics Exceeding Expectations Pentair Technical Products 2100 Hoffman Way Anoka MN 55303 1 763 323 8200 1 763 576 3200 www McLeanCoo...

Reviews: