Electronic Control Unit

Burner Relay Time Delay

The field-adjustable time delay (DOB) helps to 
p r event nuisance bu rner shut-dow n . The number 
of seconds water needs to be off the longest probe
b e fore the bu rner will shut down can be set
b e t ween 0 and 60 seconds.

Redundant Low Water Cut-Off

When the boiler water drops below the middle
p r o b e, a 3 minute timing circuit will be activa t e d . I f
water does not return to the middle probe within
three minu t e s, the bu rner relay will shut dow n . T h e
Red LED will flash once eve ry second if this 
condition occurs.

• Automatic Reset units will automatically reset 

when the water level is restored to the middle probe.

N OT E : The timing circuit will automatically reset 
if the water level returns to the middle probe within
3 minu t e s.

Redundant Pump Off

The pump relay will be activated, turning the pump
on after water drops below the middle probe. If the
water level is not restored to the top probe within 3
m i nutes the pump relay will be deactivated, shutting
off the pump. After the pump relay is deactiva t e d ,
n o rmal operation is resumed. Water must again
drop off the middle probe to activate the pump
r e l ay. There is no LED signal for this occura n c e.

A d j u s t a ble Pump Diffe r e n t i a l s

The water level positions for turning the pump on
and off and obtaining the needed pump diffe r e n t i a l s
are changed by cutting the length of the middle and
s h o rtest probes.

California Proposition 65 warning!  This product contains chemicals known to the

state of California to cause cancer and birth defects or other reproductive harm.

Previous controls should never be installed on a new system. Always install new

controls on a new boiler or system.

CAUTION:

A more frequent replacement interval may be necessary based on the condition of

the unit at time of inspection. McDonnell    Miller s warranty is one (1) year from date

of installation or two (2) years from the date of manufacture.

Failure to follow this warning could cause property damage, personal inj ury or death.

!

&

'

Summary of Contents for 1575 Series

Page 1: ...series with all other limit and operating controls installed on the boiler After installation check for proper operation of all of the limit and operating controls before leaving the site We recommen...

Page 2: ...er level is not restored to the top probe within 3 m i nutes the pump relay will be deactivated shutting off the pump After the pump relay is deactivated normal operation is resumed Water must again d...

Page 3: ...System Water Temperature 406 F 208 C Maximum System Water Pressure 250 psi 17 6 kg cm2 Maximum System Steam Pressure 250 psi 17 6 kg cm2 All probes in the Series 1575 units are sent from the factory p...

Page 4: ...l water level but not lower than the lowest safe permissible water level as determined by the boiler manufacturer OR If the control will be the secondary low water fuel cut off size the steam top and...

Page 5: ...erating probes to the desired length After cutting secure the probe rod to the electrode and lock the thread using the jamnut in the electrode sleeve Insert the probe into the chamber and tighten by h...

Page 6: ...over Removal and Installation Procedure a To remove cover use a flathead screwdriver to loosen screws and remove the cover K b To reconnect cover slide over brackets and tighten screws using a flathea...

Page 7: ...p Control Connect wire a from power supply to terminal H Connect wire b from neutral supply to terminal N Connect wire c from valve control circuit to terminal PNO Connect wire d from valve control ci...

Page 8: ...PCB is too hot and the unit has shut down The unit will automatically restart when the PCB has cooled sufficiently When using the TEST button the green light will flash once per second during the time...

Page 9: ...nit is factory set at 0 seconds To adjust turn the adjusting screw clockwise using a small flatblade screwdriver to the delay time desired Followthe bl owdown procedure found on page 11 to verify oper...

Page 10: ...pect probes The wiring connections for the pump may not be connected properly Check wiring at terminals Burner does not turn off when water level is below longest probe The probes may be fouled with d...

Page 11: ...ld be opened slowly The piping needs to be wa rmed up and stagant water in the drain piping needs to be pushed out Suddenly opening a blow down valve causes steam to condense which may create water ha...

Page 12: ...nue Morton Grove Illinois 60053 Phone 847 966 3700 Fax 847 965 8379 www xyleminc com brands mcdonnellmiller McDonnell Miller is a trademark of Xylem Inc or one of its subsidiaries 2013 Xylem Inc MM 28...

Reviews: