background image

Component Testing Procedures

!

WARNING

To avoid electrical shock, personal injury, or death: disconnect power supply before servicing, unless testing
requires it.

©2003 Maytag Appliances Company

16022159 Rev. 0

11

5

N

4

1

6

2

3

TOP

3. Remove wiring from switch.
4. If any contacts fail continuity test, replace infinite

switch.

LO

A

D

2

LO

A

D

1

4

6

3

2

L2

L1

GROUND

5

N

1

SCHEMATIC

If the infinite switch contacts are good and the element
does not heat, check for voltage at the heating element
terminal plug block. A voltage of 240 V should be
indicated. If no voltage is indicated, check for a broken
wire or loose connection.

Dial Position

Contacts

OFF

Small

Large

3 - 4

OFF

OFF

ON

2 - 3

OFF

Cycle

Cycle

2 - 5

OFF

ON

ON

Control

1. Verify power is applied to the input on the control.
2. Verify power is present at the output on the control.
3. If power is not present at input or output of the

control, replace control.

Temperature Sensor

Sensor resistance can be checked by disconnecting the
sensor leads from the control and connecting an
ohmmeter to the sensor. A resistance reading of
approximately 1100 ohms should be indicated at
ambient room temperature (75

°

F).

If a resistance of 0 ohms or infinite ohms is indicated.
Replace the temperature sensor.

Ribbon Elements

Power Disconnected

Small Element Continuity Test
1. Disconnect power from cooktop. Connect ohmmeter

leads to element terminals.

2. Meter should indicate continuity.

Large Element Continuity Test
1. Disconnect power from cooktop. Connect ohmmeter

leads to element terminals.

2. Meter should indicate continuity.

Ribbon Elements

Power Connected

Performance Test
1. Set meter to measure at least 250 VAC. Connect

meter leads to element tabs.

2. Connect cooktop to power source.
3. Test element with no load (no pan on burner), turn

corresponding surface control to HI. Voltage should
indicate 240 VAC power supply voltage.

4. Element should glow after a few seconds. If it does

not glow check element resistance or continuity to
high limit/ hot light assembly.

5. While element is heating, observe voltage and

element. Voltage should indicate 240 VAC power
supply voltage.

6. After a delay of approximately six minute

(

±

30 seconds), the high limit switch will open its

contacts and turn power off to the element. Observe
two complete cycles prior to setting surface control to
OFF position.

Cooling Fan

Fan motor may come on at anytime to cool components.
1. Turn off power to unit.
2. See “Disassembly Procedures” to access motor.
3. Disconnect terminals to cooling fan.
4. Attach meter leads to terminals on the motor.
5. A resistance of ohms should be indicated

approximately 667 ohms, but may vary with each
motor tested. This test is to check the motor winding
for an open or shorted winding. If zero or infinite
ohms is indicated, the motor windings has failed and
the motor must be replaced.

High Limit Switch

1. Turn off power to unit.
2. See “Disassembly Procedures” to access switch.
3. Disconnect wires from switch terminal connections.
4. Attach meter leads to terminals on the switch. At

ambient room temperature (70

°

F), continuity should

be indicated.

Summary of Contents for AKT3040 Series

Page 1: ...he following AKT3040 AKT3650 CEC1430AA CEC1536AA JEC7430AA JEC8430AD JEC8536AD JEC8730AD JEC9530AD JEC9536AD MEC4430BD MEC5430BD MEC5536BA Service This manual is to be used by qualified appliance tech...

Page 2: ...ING REPAIRS WARNING To avoid risk of severe personal injury or death disconnect power before working servicing on appliance to avoid electrical shock To locate an authorized servicer please consult yo...

Page 3: ...blyProcedures Disassembly Procedures for Models Listed AKT3040F E S AKT3650F E S 12 MainTopRemoval 12 IndicatorLightReplacement 12 ElementReplacement 12 InfiniteSwitchReplacement 12 Disassembly Proced...

Page 4: ...ent Undersized utensils will expose the element to direct contact with clothing 2 Never leave surface units unattended Boilovers can cause smoking and may ignite 3 To reduce risk of burns ignition of...

Page 5: ...tertop CAUTION Do not store items of interest to children in cabinets above cooktop Children may climb on cooktop to reach these items and become seriously injured Electrical Requirements 220 volt 60...

Page 6: ...need further explanation Refer to individual technical sheets or the toll free technical support line to answer questions from authorized service technicians Cooking Nomenclature M E C 5 5 3 6 B A W...

Page 7: ...roduct call 1 800 462 9824 or visit the Web Site at www maytag com or www jennair com For product inCanada call 1 800 688 2002 or visit the Web Sites at www amana com or www maytag com or www jennair...

Page 8: ...re light does not light could be failed indicator light Possible inductance voltage separate indicator light wires running parallel with power supply wires Element making a humming noise Caused by a 6...

Page 9: ...witch Power Connection 1 See schematic diagrams for assistance in testing voltages in and out of control 2 Connect a voltmeter to the element or the terminals H1 and H2 of the surface warming control...

Page 10: ...6 Set ohmmeter on R x 1K scale Check for continuity according to the following chart Dial Position Contacts OFF LO MED HI L1 L2 O E X L1 P O X X L1 H1 O X X L1 H2 O X C X H1 H2 X E X O Open X Closed C...

Page 11: ...uity Test 1 Disconnect power from cooktop Connect ohmmeter leads to element terminals 2 Meter should indicate continuity Ribbon Elements Power Connected Performance Test 1 Set meter to measure at leas...

Page 12: ...to reassemble correctly 5 Replace element and reverse procedure to reinstall Infinite Switch Replacement 1 Remove main top see Main Top Removal procedure 2 Remove screws securing control mounting bra...

Page 13: ...TE An access panel is provided on the bottom of the burner box for component diagnosis 3 Lift plate to gain access to switch mounting screws 4 Remove screws securing switch to mounting plate and remov...

Page 14: ...screws securing mounting plate to main top NOTE An access panel is provided on the under side of the burner box for component diagnosis 3 Lift plate to access switch mounting nut 4 Remove nut securin...

Page 15: ...2003 Maytag Appliances Company 16022159 Rev 0 A 1 Appendix A...

Page 16: ...ea where local codes prohibit grounding through the neutral conductor untwist or disconnect the solid copper wire and connect the ground wire to ground in accordance with local code Connect the white...

Page 17: ...Never use a metal blade to pry knob off If knob cannot be easily removed tuck folds of a dish towel under knob skirt and pull upward with steady even pressure Preparation Of Countertop The cutout in...

Page 18: ...22159 Rev 0 2003 Maytag Appliances Company This is the first page of the Installation Instruction see part number listed in the bottom right corner for complete set of instructions Installation Instru...

Page 19: ...aytag Appliances Company 16022159 Rev 0 A 5 This is the first page of the Installation Instruction see part number listed in the bottom right corner for complete set of instructions Installation Instr...

Page 20: ...22159 Rev 0 2003 Maytag Appliances Company This is the first page of the Installation Instruction see part number listed in the bottom right corner for complete set of instructions Installation Instru...

Reviews: