Operating instructions SG-EFS 104/2W
Page 18/19
Technical data
SG-EFS 104/2W
AC 24 V
DC 24 V
Testing basis
EN 12978, EN 61000-6-3, ISO 13849-1, ISO 13856-1, ISO 13856-2,
ISO 13856-3
Connecting voltage U
S
Nominal voltage
AC 24 V
DC 24 V
Voltage tolerance
−10% to +10%
−10% to +10%
Nominal current
70 mA
60 mA
Nominal frequency
50 to 60 Hz
–
External fuse protection
200 mA time-lag
200 mA time-lag
Power consumption
< 4 VA
< 3 W
Times
Reaction time t
a
< 15 ms
< 15 ms
Restart time t
w
< 50 ms
< 50 ms
Safety classifications
ISO 13856: reset function
With/without
With/without
ISO 13849-1:2015
Category 3 PL d
Category 3 PL d
MTTF
D
257 a
257 a
DC
avg
60%
60%
B
10D
(load: DC 24 V / 1 A)
1.8× 10
6
1.8× 10
6
n
op
(assumption)
52560/a
52560/a
CCF
Requirements met
Requirements met
IEC 60664-1: creep distance and
air gap
Pollution degree 2, overvoltage cat-
egory III / 250 V, basic insulation
Pollution degree 2, overvoltage cat-
egory III / 250 V, basic insulation
Inputs
Sensor
Y1, Y2
Y1, Y3
Y1, Y2
Y1, Y3
Monitoring resistor
1k2 Ohm 8k2 Ohm
1k2 Ohm 8k2 Ohm
Short-circuit resistance
≤ 400 ohms
≤ 400 ohms
≤ 400 ohms
≤ 400 ohms
Line resistance
≤ 10 ohms
≤ 10 ohms
≤ 10 ohms
≤ 10 ohms
Line length (max.)
100 m
100 m
100 m
100 m
Switching thresholds
Sensor activated
< 0.6 kiloohms
< 4 kiloohms
< 0.6 kiloohms
< 4 kiloohms
Cable break
> 1k8 ohms
> 12 kiloohms
> 1k8 ohms
> 12 kiloohms
Reset
Automatic
S1, S2
S1, S2
Manual
S1, S3
S1, S3
Line length (max.)
30 m
30 m
Technical data