MayPole MP7423 Instruction Manual Download Page 5

 

SUMMARY OF OPERATION: 

 

Step 1 

Step 2 

Step 3 

Step 4 

Step 5 

Pulse charging 

Soft 
start 

Auto-Select Current & Bulk 
Charging 

Absorption 

Float charging 

12V 

STD 

mode 

 

Connect  the  charger  to  the 
battery, the charger will detect 
the 

battery’s 

voltage 

automatically. 
 

(1)

 If a voltage of more than 7.5 

V  is  detected,  the  charger 
recognizes  battery as 12V  

(2)

 If a voltage of 7.5V-10.5V is 

found,  maintenance  charge  is 
activated ( 0.8A pulse charging 
until voltage exceeds 10.5V)

 

(3)

 If the voltage doesn’t reach 

10.5V  within  30minutes,  a 
battery fault is indicated. 

 
 
 

 

 
 

1A 

charging 

until the 

voltage 

reaches 

12.8V

 

 
 

Every 15-20min the 
charger will check the 
battery voltage. If the 
voltage has increased by 
0.2V or more the charging 
current will remain the 
same. 
If the voltage has not 
increased by 0.2V the 
charger will increase the 
charging current by 1 
Amp. to 2A. The cycle will 
be repeated every 15-
20min. and the charging 
current can be increased 
to 3A or 4A. This charging 
cycle will continue until the 
battery voltage reaches 
the maximum value. 

Maximum 

voltage 

14.4V 

14.4V

 constant 

voltage 

Charging current 

steps down by 1A at 

a time until 1Amp is 

reached 

Charger will detect 
the battery’s voltage 
again  

(1)

 If the voltage falls 

below 12V. Battery 
fault is shown. 

(2)

 If voltage is 12-

13.2V, charger will 
switch to 
maintenance 
charging

  

(3)

 If the voltage is 

more than 13.2V 
charger will wait for 
the voltage to fall 
before starting a 
maintenance charge. 

12V

 

AGM 

mode 

 

Maximum 

voltage 

14.8V 

14.8V

 constant 

voltage Charging 

current steps down 

by 1A at a time until 

1Amp is reached 

12V 

Winter 

mode

 

Maximum 

voltage 

14.8V 

14.8V

 constant 

voltage Charging 

current is falling until 

1A 

6V 

STD 

mode

 

Connect  the  charger  to  the 
battery, the charger will detect 
the 

battery’s 

voltage 

automatically;   

(1)

 If voltage of less than 7.5V 

is 

detected 

the 

charger 

recognizes the battery as 6V  

(2)

  If  voltage  of  1.5V-5V  is 

found,  maintenance  charge  is 
activated ( 0.8A pulse charging 
until voltage exceeds 5.25V) 

(3)

  if  voltage  doesn’t  reach 

10.5V  within  30minutes,  a 
battery fault is indicated

 

 
 
 
 

1A

 

charging 

until the 

voltage 

reaches 

6.4 V

 

Every 15-20min the 
charger will check the 
battery voltage. If the 
voltage has increased by 
0.2V or more the charging 
current will remain the 
same. 
If the voltage has not 
increased by 0.2V the 
charger will increase the 
charging current by 1 
Amp. to 2A. The cycle will 
be repeated every 15-
20min. and the charging 
current can be increased 
to 3A or 4A. This charging 
cycle will continue until the 
battery voltage reaches 
7.2V 

Maximum 

voltage 

7.2V 

7.2V

 constant 

voltage; Charging 

current steps down 

by 1A at a time until 

1Amp is reached 

Charger will detect 
the battery’s voltage 
again 

(1)

 If the voltage falls 

below 6V. Battery 
fault is shown. 

(2)

 If the voltage is 6-

6.6V, charger will 
switch to 
maintenance 
charging

(3)

 If the voltage is 

more than 6.6V 
charger will wait for 
the voltage to fall 
before starting a 
maintenance charge 

 
TROUBLESHOOTING

  

Display 

Fault 

Action 

Battery polarity reversal symbol 
displayed. 

Battery clamps reversed 

Disconnect & reconnect correctly 

Clamp indication and voltage symbols 
displayed 

Dirty or oxidized battery terminals. Low or 
unstable charging current 

Clean terminals 

No Display 

Mains supply not connected 

Check socket 

Display back light on, display showing 
0.0V and clamp symbol. 

Battery not connected  

Check clamps, replace battery 

Output lead fuses should be checked and replaced as necessary (5A blade) in connection with all faults. Also check the fuse in the 
mains plug, which should only be replaced with a 3A BS1362 fuse. 
Persistent fuse replacement may indicate a fault with the charger or leads. Check these before each use and do not use if worn or 
damaged. 

 

DECLARATION OF CONFORMITY 

We declare that this product conforms to the following standards EN60335-1, EN60335-2-29, EN55014, EN61000, 
and the following Directives 73/23 CEE, 93/68 CEE, 2004/108/EC, 2002/95/EC (ROHS) 
 
 

Technical Manager 

Maypole Ltd, August, 2015 

 

Reviews: