INsTALLATION INsTrUCTIONs 

THIS GABLE-MOUNTED UNIT IS DESIGNED FOR ATTICS OF AVERAGE SIZE AND OPERATES MOST EFFICIENTLY WHEN AIR 

INTAKES ARE LOCATED AROUND THE EAVES.  ALTERNATIVELY, AIR INTAKE MAY BE FROM OPPOSING GABLE VENTS, BUT 

NEVER FROM ROOF OR RIDGE VENTS.   AT LEAST 600 SQ. IN OF NET FREE AIR INTAKE IS REQUIRED PER UNIT FOR SAFE 

AND EFFICIENT OPERATION.  THE MOTOR OPERATES ON 120 V, 60 HZ, A.C. CURRENT.   SEE MOTOR LABEL FOR 

AMPERAGE.

THIs UNIT MAY BE MOUNTED BEHIND ANY sTATIC WALL VENT, Or MODELs Vx1818 Or Cx2121 AUTOMATIC sHUTTErs

.

step 

       step 

For new installation or installation behind 

existing louvers, using 2 x 4 studs, frame an 

opening at least 18 ¼-in square (depending on 

stud spacing) on center, on the attic side of the 

gable. 

step 2 

Cover the opening with a square piece of 

plywood, paneling, or sheetrock, at least  

21 ¼-in square (depending on stud spacing). 

Cut a 15-in diameter hole in the center of this 

panel, to allow the shroud of the fan to enter the 

hole.

It is important to block off any remaining open 

vent area in the gable. 

With the nuts and bolts furnished, secure the 4 

mounting brackets to the shroud and then 

fasten the unit to the frame.  

Mounting the long side of the 

L brackets to the shroud may 

better fit your installation and 

also help reduce 

vibration.

The use of a 

sound-dampening

barrier, such as 

rubber washers or foam stripping will help 

reduce resonance 

in the walls. Seal 

off any gaps 

around

the fan, 

in order for 

the fan to 

function at 

maximum 

efficiency

.

TIP

:

MUCH OF THE PrEPArATION, WIrING OF 

THErMOsTAT, TEsTING, AND MOUNTING TO THE 

FrAME CAN BE COMPLETED BEFOrE FINAL 

INsTALLATION IN THE ATTIC.  