background image

 
 

 

RF-ROR-135S-319-NN 
Wireless Rate of Rise Heat Detector 

 

 

Rev A 

 

Page 1 of 3 

 

 

RF-ROR – Wireless Rate of Rise Heat Detector 

 

 

Product Summary 

 
The Wireless Rate of Rise sensor uses a built-in 
thermistor to sample and report on a specific set 
temperature or a sudden rise in temperature.  

Heat – selectable 135F or 200F 
Rate of Rise – rapid temp rise 12F per      
minute 

 
Note: The device is powered by a 3V lithium 
battery providing up to 10yrs of battery life. 

 

Installation: 

 
Heat sensors are normally installed in areas that are 
prone to smoke as kitchens and garages. 
 
Avoid areas that may have rapidly increasing 
temperatures as, fireplaces, stoves, heaters, etc. 
 
When mounting the sensor should be placed on a 
ceiling at least 4 inches away from any wall. If 
placed on a wall the sensor must be within 6 inches 
if the ceiling 
 
If using as a 135F make sure the ceiling location 
does not exceed this temperature 
 

 

Setup: 

 
The sensor can be setup to detect a fixed 
temperature of either 135F or 200F. 
 
Use the jumper to select Low or Hi: 
 

 

Fixed Temperature 
Low – 135F 
High – 200F 
 
Note: if no jumper is installed the detector is set to 
200F 
 

Programming: 

 

Enrolling 

The panel must learn (program) the detector ID 
code in order to respond to detector signals. For 
complete programming information, refer to the 
specific control panel documentation.  
 

 

To add the sensor to panel memory: 
 
1.  Place the panel in program mode.  
2.  Proceed to the Learn Sensors menu. 

When the panel prompts you for a sensor 
group number, select the proper fire 
group 

3.  Select the desired sensor number. When 

the panel prompts you to trip the sensor, 
remove the battery pull tab. (If pull tab is 
already removed, press and then release 
the tamper switch until the panel beeps, 
indicating successful programming.) 

 

                                  

 

 

4.   Exit program mode 

 
 
 
 

Tamper Switch 