maxon motor
4-Q-DC Servoamplifier ADS 50/5
Operating Instructions
6.2
Adjustments potentiometer P8 I
cont
and current limit mode DIP switch S6
It is standard that a maximum current limiter is activated (DIP switch
S6
OFF).
In this way the motor current is limited to the value set on potentiometer
P4
I
max
(0.5 ... 10 A).
If DIP switch
S6
is turned to ON, a cyclical current limiter is also activated. This
current limiter method makes a certain level of motor protection against thermal
overload possible.
For 0.1 seconds the motor current is limited to the value set on potentiometer
P4
I
max
(0.5 ... 10 A) and then for 0.9 seconds current is limited to the value set
on potentiometer
P8
I
cont
(0.5 ... 10 A). After one second the cycle will repeat it-
self.
Pre-adjustment
P8
I
cont
= 50%.
DIP switch
S6
ON
↑
DIP switch
S6
OFF
↓
cyclical current limiter active
maximum current limit active
11
6.3
Maximal encoder frequency DIP switch S5
DIP switch
S5
permits selection of the maximum encoder input frequency.
A max. encoder frequency of 100 kHz is standard.
DIP switch
S5
ON
↑
DIP switch
S5
OFF
↓
Max. Input frequency is 10 kHz
Max. Input frequency is 100 kHz
Encoder pulse
per turn
maximum
motor speed
Encoder pulse
per turn
maximum
motor speed
16
37 500 rpm
32
18 750 rpm
64
9 375 rpm
128
4 688 rpm
128
46 875 rpm
256
2 344 rpm
256
23 438 rpm
500
1 200 rpm
500
12 000 rpm
512
1 721 rpm
512
11 719 rpm
1000
600 rpm
1000
6 000 rpm
1024 586
rpm
1024
5 859 rpm
Note
To achieve good control characteristics, encoders with low impulse counts per
turn should be run with the DIP switch
S5
ON
↑
.
July 2009 Edition / Doc. No. 538837-07 / Subject to change