Maxitrol filters are suitable for multipoise mounting.    

(Preferably with the lid facing down or to the side.)  In-

stall the filter properly with gas flowing as indicated by 

the arrow on the casting.  It is also important to leave 

sufficient space above the cover to allow for removal 

in order to change the filter insert.

Frequency of filter insert maintenance is depen-

dent upon both the maximum operating pressure of 

your equipment application, and the associated pres-

sure drop at the filter.  Although, it is recommended 

that the filter insert  be replaced at least once a year.  

See the adjoining pressure drop chart.

Shut off all gas before servicing the filter insert.  

When loosening the screws secure the cover, proceed 

slowly in case of any residual gas pressure.  Remove 

the cover and withdraw the filter insert.  

place the filter insert so that it abuts correctly in rela-

tion to the flanges and base of the housing.  The filter 

insert should not extend into the area between the 

o-ring and cover - slightly bend down the corners of 

the matting to prevent o-ring obstruction.  Replace the 

cover and tighten the screws.

Check carefully for gas leaks immediately after the 

filter has been installed or serviced and the gas turned 

on.  Do this before attempting to operate the appliance 

or other gas-fired device.  Use a rich liquid soap solu-

tion or other accepted leak tester on the area between 

the cover and housing, and at the pipe connections.  

Never use if leakage is detected.

Pressure Drop Curves 

 (0.64 sp gr gas)

Filter Replacement Material

Replacement filter matting material is available. 

GF40 models - part number 101706-1 

GF60 models - part number 101706-2 

GF80 models - part number 101706-3

Pipe Size 

NPT Model 

ISO 7-1 Model

1/2" 

 

GF40-1-44 

GF40M-1-44

3/4" 

 

GF60-1-66 

GF60M-1-66

1" 

 

GF60-1-88 

GF60M-1-88

1-1/4"   

GF80-1-1010 

GF80M-1-1010

1-1/2"   

GF80-1-1212 

GF80M-1-1212

2" 

 

GF80-1-1616 

GF80M-1-1616

10

30

100

1000

2000

.3

1

10

100

3     

(m

3

/hr)

Volumetric Flow Rate

100

(cfh)

1000

10000

100000

0.1

1

10

100

(inches W

.C.)

(mbar)

Pressure Drop (

r

P)

GF40-1-44GF60-1-66FG60-1-88

GF80-1-1010

GF80-1-1212

GF80-1-1616

Replace the filter insert with the side imprinted 

'Austritt' (outlet) facing the outlet.  Inspect the o-ring 

and replace if necessary.  To ensure an effective seal, 