Installation
Comet Executive Gas
2-12
Single Phase Machines-115V
1. Bring the supply lines to the electrical
panel. Use two wires for the power supply
and a green third wire for ground.
2.
Extend the lines following local codes and
properly secure the conduit or greenfield.
3.
Connect one power wire to terminal L1
at the top of the main disconnect switch
(Figure 2-12, A) and the other power wire
to the neutral block to its right (B).
4.
Connect the green third wire to the ground-
ing block to its left (Figure 2-12, C).
WARNING
The machine must be
properly grounded to ensure
operator safety.
5.
Make sure the other end of the ground
wire is connected to a proper earth ground.
6. Close and secure the right endframe door.
CAUTION
Do not attempt to start the
machine at this time. Leave
the disconnect switch OFF.
Gas Connection
CAUTION
The gas supply must
match the specific gas
requirements shown on
the nameplate.
The nameplate (Figure 2-2), located on the
front of the left endframe, specifies the gas
requirements of the unit. The unit requires gas
supplied at the correct pressure.
Note that the nature of the atmospheric burner
used in the machine prevents it from operating
at full capacity when in use above an altitude of
approximately 2000 feet (609 meters). For use
at higher elevations, contact the factory service
department.
If the incoming gas pressure is too high or too
low, the unit will work improperly or not at all.
Confirm the pressure of the gas supply meets the
requirements shown on the nameplate.
If a high pressure gas supply is used, an
additional regulator, mounted outside the unit,
is required. The following are based on using a
water column manometer connected upstream of
the supplied pressure regulator. A high pressure
gas supply is:
•
For natural gas: more than 11” (2.75
kPa) of pressure.
•
For LP gas, more than 12” (3.0 kPa).
• For manufactured gas, contact the
Factory Service Department.
For more information on checking the pressure
of the gas supply, refer to
All labor and materials required for the gas
connection to the unit, except those items shipped
with the unit, are a local responsibility. Local
codes and regulations must be followed for proper
installation.
Figure 2-12:
Single phase connections.
C
B
A
TOC
INDEX
Summary of Contents for Comet Executive Exec-56-G
Page 1: ...INSTRUCTION MANUAL COMET EXECUTIVE Gas Heated Flatwork Ironer...
Page 42: ......
Page 58: ......
Page 80: ......
Page 164: ......
Page 166: ...SC 2 Motor Circuit 115V 1 Phase SC TOC INDEX TOC...
Page 168: ...SC 4 Motor Circuit 230V 1 Phase SC TOC INDEX TOC...
Page 170: ...SC 6 Motor Circuit 230V 3 Phase SC TOC INDEX TOC...
Page 172: ...SC 8 Motor Circuit 415V 3 Phase SC TOC INDEX TOC...
Page 174: ...SC 10 Motor Circuit 460V 3 Phase SC TOC INDEX TOC...
Page 176: ...SC 12 Main Electrical Panel 115V 1 Phase SC TOC INDEX TOC...
Page 178: ...SC 14 Main Electrical Panel 230V 1 Phase SC TOC INDEX TOC...
Page 180: ...SC 16 Main Electrical Panel 230V 3 Phase SC TOC INDEX TOC...
Page 182: ...SC 18 Main Electrical Panel 460V 3 Phase SC TOC INDEX TOC...
Page 184: ......
Page 185: ...TOC INDEX...
Page 186: ......
Page 187: ...TOC INDEX...
Page 188: ......
Page 189: ...TOC INDEX...
Page 190: ......
Page 192: ......
Page 194: ......
Page 196: ......
Page 197: ...304500 1a TOC INDEX MB TOC...
Page 198: ...TOC INDEX MB TOC...
Page 199: ...TOC INDEX MB TOC...
Page 200: ...TOC INDEX MB TOC...
Page 221: ...3045069 TOC INDEX MB TOC...
Page 222: ...TOC INDEX MB TOC...
Page 223: ...TOC INDEX MB TOC...
Page 224: ...TOC INDEX MB TOC...
Page 229: ...TOC INDEX MB TOC...
Page 230: ...TOC INDEX MB TOC...
Page 231: ...TOC INDEX MB TOC...
Page 232: ...TOC INDEX MB TOC...
Page 236: ......
Page 238: ......
Page 244: ......