MAXA
DC Fan Coil Unit
5
5. Specifications
Model
MI26A1
MI35A1
Power supply
V/Ph/H
z
Air flow (H/M/L)
m
3
/h
492/454/400
825/689/590
CFM
289/267/235
485/405/347
Cooling
1
Capacity (H/M/L)
kW
2.7/2.59/2.39
3.81/3.3/2.88
Water flow rate(H/M/L)
m
3
/h
0.48/0.46/0.42
0.67/0.57/0.51
Water pressure
drop(H/M/L)
kPa
31.61/28.63/25.3
6
56.75/41.23/33.0
2
Power input(H/M/L)
W
13/11/10
34/22/15
Heating
2
Capacity (H/M/L)
kW
2.94/2.8/2.58
4.3/3.65/3.09
Water flow rate(H/M/L)
m
3
/h
0.51/0.49/0.46
0.73/0.64/0.56
Water pressure
drop(H/M/L)
kPa
32.66/34.89/30.2
4
51.86/47.53/35.6
9
Power input(H/M/L)
W
11/11/9
31/20/14
Heating
3
Capacity (H/M/L)
kW
3.29/3.03/2.63
5.08/4.33/3.77
Water flow rate(H/M/L)
m
3
/h
0.48/0.46/0.42
0.67/0.57/0.51
Water pressure
drop(H/M/L)
kPa
37.49/30.25/26.5
3
61.94/37.88/30.3
4
Power input(H/M/L)
W
12/10/8
31/20/14
Sound pressure level (H/M/L)
dB(A)
32/30/27
45/39/35
Rated current
A
0.2
0.4
Fan motor
Type
DC Motor
DC Motor
Quantity
1
1
Fan
Type
Tangential fan
Tangential fan
Quantity
1
1
Coil
Row
2
Max. Working pressure
MPa
1.6
Coil length x height
mm
635x26.74
Fin spacing
mm
1.5
Fin type
Hydrophilic aluminium
Number of circuits
5
Diameter
mm
Φ7
Body
Net dimensions (W×H×D)
mm
915×290×230
915×290×230
Packing size (W×H×D)
mm
1020×390×315
1020×390×315
Net weight
kg
12.7
12.7
Gross weight
kg
17.3
16.3
Pipe
connection
Water inlet/outlet pipe
inch
RC3/4
Drain pipe
mm
ODΦ20
Note:
Based on Eurovent conditions:
H: High fan speed; M: Medium fan speed; L: Low fan speed.
1 :Cooling mode (2 and 4-pipe coil): entering air temperature 27°C DB/1 9°C WB, entering/leaving water temperature 7°C /12°C, high fan speed.
2 :Heating mode
(
1
)
: (2-pipe coil): entering air temperature 20°C DB, entering/leaving water temperature 45/40°C, high fan speed.
3 :Heating mode
(
2
)
: (2-pipe coil): entering air temperature 20° C DB, enter water teperaure/water flow 50
℃
/* (same water flow as in standard rating condition in
cooling)