background image

i-MAX 

Industrial inverter air/water heat pump with axial fans 

15 

7.3.6

 

SAFE TIME PERIODS 

The compressors respect the minimum waiting time for the turning on and off actions (regardless of their configurations and if 

they are inverters or ON/OFF type). 

C01

 = Minimum Off time of a compressor # 240 sec (default). 

C02

 = Minimum time between two start-up of the same compressor # 360 sec (default). 

C03

 = Minimum delay time between the start-up of a compressor and the next one # 10 sec (default). 

C04

 = Minimum delay time between the shutdown of a compressor and the next one # 0 sec (default). 

7.3.7

 

EMERGENCY CONDITIONS 

If an alarm is warned by one of the inverters, the compressor corresponding to the faulty inverter cannot startup and the error 

code will be displayed, note that, the alarm of any inverter will stop the operation of the whole compressors. 

When the serviceman operates on the appliance and decides to make it operating by extruding the compressor related to the 

faulty inverter, in order to do that, he must change the value of the parameter 

N06

 from 0 to 1. 

Such setting will affect immediately the operation and will be memorized; the serviceman/installer should restore the setting 

values once the fault inverter has been repaired or replaced. 

7.3.8

 

DEACTIVATION OF THE COMPRESSORS FOR OUTDOOR TEMPERATURE 

If the outdoor temperature sensor is configured and is not in trouble, so the compressors cannot work because of low outdoor 

temperature. The function is enabled if: 

 

Outdoor temperature sensor integrated and operating. 

 

Parameter 

Pa r07

 = 1. 

7.4

 

HEAT PUMP MODE OPERATION 

This is the normal operation in which the auxiliary electric heaters turn on if the heat pump fails to meet the setpoint temperature 

within a reasonable time (see the paragraph related to auxiliary electric heaters). 

7.5

 

HEAT DISSIPATION FAN MOTOR CONTROL 

The control of the dissipation is as a function of the condensing pressure in chiller mode operation, whereas, it depends on the 

evaporation pressure in heat pump mode operation. 

The adjustment of the fan speed occurs depending on the operation of the compressor. 

The fan stop is bypassed for a duration equal 

F12 

beginning from a compressor startup of the circuit. During this period, if the 

controller requires the cut-off, the fan will run at minimum speed. Please see paragraph 12.5 for changing the parameters. 

7.5.1

 

FAN SPEED CONTROL 

The condensation control depends on the condensing pressure in chiller mode and on the evaporation pressure in case of heat 

pump mode. 

The fan speed can be independently controlled by the compressors or under the actuation of the fan motor. 

 

F05

= fan 

output

 mode 

F05 = 0

: if all the compressors of the circuit are switched off and the fan is switched off. The fan stop is bypassed for a period equal 

to 

F12 

beginning from a compressor start-up of the circuit. During this period, if the controller requires the cut-off, the fan will run 

at minimum speed. 

F05 = 1

: The fan control is independent from the compressor (the fan motor operates only according to the condensing pressure). 

Please see paragraph 11.5 for changing the parameters. 

7.5.2

 

FAN SPEED CONTROL IN COOLING MODE 

The fan speed control in cooling mode occurs according to the diagram shown below, where: 

F06 

= Minimum fan speed in cooling mode; 

F07 

= Maximum silent fan speed in cooling mode 

F08 

= Set temperature/pressure to the minimum fan speed in cooling mode 

F09 

= Fan motor linear band in cooling mode 

F10 

= Delta cut-off of the fan 

F11 

= Cut-off hysteresis and silent/maximum fan speed 

F13 

= Maximum fan speed in cooling mode 

F14 

= Set temperature/pressure to the maximum fan speed in cooling mode 

F6

-

F10 

= Set forced fan stop for low condensing pressure 

Summary of Contents for i-MAX 0466

Page 1: ......

Page 2: ...e Series Serie Serie S rie i MAX SSL 0466 06115 Industrial inverter air water heat pump with axial fans Possible wasted electrical or electronic devices products should not be located together with no...

Page 3: ...12 7 2 3 OPERATION WITH ACTIVE ELECTRIC HEATER 12 7 2 4 CONTINUOUS OPERATION 12 7 2 5 LINEAR REGULATION OF THE CIRCULATOR DOUBLE TWater 12 7 2 6 AIR PURGING OF THE SYSTEM 13 7 3 COMPRESSORS CONTROL 1...

Page 4: ...9 10 6 AUXILIARY SYSTEMS OFFSET MANAGEMENT 26 9 11 DOUBLE SET POINT MANAGEMENT 26 9 11 1 SETTINGS 26 9 11 2 ADJUSTABLE SETPOINTS 27 9 11 3 COMMUTATIONS 27 9 12 SECONDARY CIRCULATOR MANAGEMENT RELAUNC...

Page 5: ...personnel and competent in the existing rules in the country in which the appliance will be installed 3 GENERAL SAFETY GUIDELINES Before beginning to operate on the units every user has to be perfectl...

Page 6: ...nt under voltage To touch the equipment if you are not allowed If the lightning risk is high the unit must be protected the risk assessment must comply with the CEI EN 62305 2 regulation If there is a...

Page 7: ...djust the summer set point value UP button In the setting mode this button allows you to move up to a higher menu or to increase the value of a parameter when you are in the edit mode DOWN button In t...

Page 8: ...cond setpoint in the summer C 18 0 Coo H03 He2 Second setpoint in the winter C 35 0 H02 Hea 5 2 2 Password menu Enter the password for the desired access level The controller will automatically open t...

Page 9: ...sequence 6 Once the update is completed the board returns to normal operation and the appliance is ready to start operation 7 Turn off the unit by placing the main switch in OFF position 8 Remove the...

Page 10: ...tion 24 Alarm signalization 31 Plant season signalization 47 Lockout signalization DO3 phase DO3N neutral Under voltage output 230Vac 50Hz 2A AC1 For the sizes of 0466 0475 and 0485 Wherever the GI op...

Page 11: ...n Continuous operation The circulator will immediately switch off if You have a pump circulator locking alarm including the manual reset flow switch alarm The unit is in stand by mode or when it s swi...

Page 12: ...it will be activated periodically for a duration given by the parameter P17 in seconds after a counting time set by the parameter P16 in minutes activated when the thermoregulation is fulfilled and th...

Page 13: ...the expansion valve the reversing valve is commutated in the opposite direction to that required by the actual mode for 5 seconds in order to allow the equilibrium of the optimal pressures for startin...

Page 14: ...15 b05 C 0 5 0 5 0 5 0 5 0 5 0 5 b25 C 2 5 2 5 2 5 2 0 2 0 2 0 7 3 5 INVERTER COMPRESSORS CONTROL IN HEATING MODE The compressors are active in heating mode if the heat pump is enabled H09 Configurati...

Page 15: ...ee the paragraph related to auxiliary electric heaters 7 5 HEAT DISSIPATION FAN MOTOR CONTROL The control of the dissipation is as a function of the condensing pressure in chiller mode operation where...

Page 16: ...rtant decreasing of the thermal efficiency of the unit it can lead also to the risk of damaging the unit itself The adjustable parameter d01 enables the defrost operation 1 enabled defrosting Please s...

Page 17: ...ated above on the DO3 DO3N terminals Parameter H81 it s possible to configure a 230Vac signal output voltage by setting the following user parameters introducing the installer password in the control...

Page 18: ...water production DHW 3 The function is active in heating mode The remote switching on off function doesn t deactivate the domestic hot water production DHW 4 The function is active in heating mode Th...

Page 19: ...hole system Note It is possible to invert the polarity of the digital input to do that please contact our technical office 9 5 3 HEATING MODE ON DOMESTIC HOT WATER TANK If the following setting H83 1...

Page 20: ...eater r24 Num 1 o 3 Type of utilization of the electric heaters 9 8 2 AUXILIARY ELECTRIC HEATER OF THE PLANT IN DEFROST CYCLE During defrost cycle see Paragraph 7 6 by setting r21 1 in addition to r10...

Page 21: ...h DHW and plant sides no priority intervention for electric heaters Settings of the parameter r32 when the boiler is being installed r32 0 boiler without a circulating pump with thermoregulation to be...

Page 22: ...his remote sensor is less than the setpoint Hea the boiler will be activated and then will be deactivated when the measured temperature by the remote sensor is greater than setpoint Hea The boiler wil...

Page 23: ...0 1 0 1 2 2 3 5 6 0 1 7 1 Auxiliary electric heater of sanitary 2 After r15 minutes boiler HEAT SAN SANITARY 0 1 1 Set up of minutes 2 3 2 3 8 1 Boiler 2 After r15 minutes auxiliary electric heater o...

Page 24: ...ter r12 minutes later heat pump HEAT HEAT SAN HEAT 1 0 1 2 Set up of minutes 1 3 1 3 3 1 Boiler 2 After r12 minutes heat pump 3 After r12 minutes later auxiliary electric heater of plant HEAT HEAT SAN...

Page 25: ...AN HEAT 0 1 0 1 2 Set up of minutes 1 3 4 6 0 2 8 1 Auxiliary electric heater of plant HEAT HEAT SAN HEAT 0 1 0 1 2 Set up of minutes 0 2 5 1 3 9 1 Boiler HEAT SAN SANITARY 0 1 0 1 2 Set up of minutes...

Page 26: ...to the open state the auxiliary electric heater of the plant will turned off It works as indicated in the TABLE 1 2 3 and 4 3 COOL SAN SANITARY Not available It works as indicated in the TABLE 5 4 COO...

Page 27: ...ng pump for the plant circuit utilizations An ambient thermostat must be appropriately configured NC state connected on the terminals DI3E DI3E by the installer Thermostat contact normally open Active...

Page 28: ...eeze alarm activation setting C 2 127 127 INSTALLER A09 Antifreeze alarm hysteresis C 3 0 0 0 25 5 INSTALLER A16 Low pressure set in cooling operation Bar Based on the model 4 0 80 0 INSTALLER A27 Low...

Page 29: ...periodic mode min 20 0 600 INSTALLER P17 Time of operation of the pump in periodic mode sec 90 0 255 INSTALLER 0 deactivation of periodic mode P18 Enabling of unique pump operation in network 0 0 1 I...

Page 30: ...activated function 1 enabled function 2 Operation of auxiliary plant side electric only if H83 1 r16 DHW auxiliary heater heat pump activation delay min 15 0 255 INSTALLER r19 Activation time of drain...

Page 31: ...matically reset for the first 2 times and goes off after 5 seconds If the alarm occurs more than 3 times per hour the manual reset of the alarm is required The alarm is not active for 10 seconds after...

Page 32: ...pump E041 Misfitted temperature alarm Heat pump E101 Communication Timeout GI module error Heat pump E611 Inlet water temp sensor error Heat pump E682 Plant water plant temperature remote sensor if e...

Page 33: ...1 E913 Automatic All compressors are off for at least 180 sec E921 E923 Automatic All compressors are off for at least 180 sec E931 E933 Automatic All compressors are off for at least 180 sec E941 E94...

Page 34: ...i MAX Industrial inverter air water heat pump with axial fans 34...

Page 35: ......

Page 36: ...ADVANTIX SpA Via S Giuseppe Lavoratore 24 37040 Arcole VR Italy Tel 39 045 76 36 585 E mail info advantixspa it www maxa it...

Reviews: