i-MAX 

Industrial inverter air/water heat pump with axial fans 

13 

Example in cooling operation: 

If the difference in temperature between water inlet and outlet is greater than 

P09 + P10

, the pump will run at maximum speed. 

If the difference temperature between water inlet and outlet is less than 

P09 - 0.2°C

, the pump will run the minimum speed. 

In the other cases, the pump modulates trying to match the temperature difference with 

P09

. For the heating mode, the same 

considerations are valid with replace only 

P06

 with 

P09

. Please see paragraph 11.6 for changing the parameters. 

Warning: During the DHW production mode, the pump is constrained to operate at its maximum speed. 

 

In domestic hot water production mode, the pump will operate at the maximum speed. 

7.2.6

 

AIR PURGING OF THE SYSTEM 

This function allows the air purging of the system, during this operation, the circulator runs at its maximum speed. 

To enable the function: 

 

Put the controller in 

OFF 

mode 

 

Enter at the parameters PRG

PSS

 PRG

(introduce the maintainer password) 

 

Press simultaneously for 

3

 

seconds 

the buttons 

UP and DOWN.

 

The circulator of the plant will run at the maximum speed for 

5 minutes

 then it stops the operation. 

It is possible to stop manually the air purge cycle function of the system by pressing the 

MODE

/

ESC 

button, or by pressing 

simultaneously the 

UP

 and 

DOWN 

buttons for 3 seconds. 

During this function, the flow-switch alarm is deactivated. 

7.3

 

COMPRESSORS CONTROL 

The i-Max system uses two refrigerant circuits; each circuit is composed by an inverter compressor and by one or two other on/off 

compressors. Follow the activation logic of compressors. 

7.3.1

 

TRANSITORY OF STARTING 

When the compressors are all off, in conjunction with the pre-opening of the expansion valve, the reversing valve is commutated 

in the opposite direction to that required by the actual mode for 5 seconds in order to allow the equilibrium of the optimal 

pressures for starting the first capacity step. 

The modulating compressor will always be the first compressor to be start and the last one to stop operation. 

The activation and control logic of the modulating compressor follows the thermoregulation curve. 

Below are reported the phases of activation and shutdown logic of the other compressors and the behaviour of the modulating 

compressor during these phases 

7.3.2

 

ON-OFF compressors activation logic 

The ON/OFF compressor starts operation when the required power consumption for the modulating compressor is higher than 

90% for a continuous duration given by b16 (default 60 seconds). 

The activation of the compressor can occur in 3 steps: 

1.

 

Reduction of the output capacity of the modulating compressor to the minimum frequency. 

2.

 

Activation of the first ON/OFF compressor when the frequency of the modulating compressor has achieved 45Hz. 

3.

 

Activation of second ON/OFF compressor after 10 seconds. 

4.

 

The compressor  restarts  modulation by mean of the thermoregulator after 30 seconds from the ON/OFF compressor 

start up. 

The unavailability of activation of an On/Off compressor could be also caused by the logic related to the protection or capacity 

limitations of the compressor. 

7.3.3

 

Release logic of the ON/OFF compressors 

If the thermoregulation that is required for the modulating compressor is corresponding to the minimum needed output capacity 

for a period less than 60s, an ON/OFF compressor will stop operation and once the shutdown is completed, the next ON/OFF 

compressor will stop also operation after the usual duration of 60 seconds. 

Note

: In the case in which the regulation temperature is found to be lower than 

Set - b05

, the release of the running compressors 

occurs simultaneously. 

Summary of Contents for i-MAX 0466

Page 1: ......

Page 2: ...e Series Serie Serie S rie i MAX SSL 0466 06115 Industrial inverter air water heat pump with axial fans Possible wasted electrical or electronic devices products should not be located together with no...

Page 3: ...12 7 2 3 OPERATION WITH ACTIVE ELECTRIC HEATER 12 7 2 4 CONTINUOUS OPERATION 12 7 2 5 LINEAR REGULATION OF THE CIRCULATOR DOUBLE TWater 12 7 2 6 AIR PURGING OF THE SYSTEM 13 7 3 COMPRESSORS CONTROL 1...

Page 4: ...9 10 6 AUXILIARY SYSTEMS OFFSET MANAGEMENT 26 9 11 DOUBLE SET POINT MANAGEMENT 26 9 11 1 SETTINGS 26 9 11 2 ADJUSTABLE SETPOINTS 27 9 11 3 COMMUTATIONS 27 9 12 SECONDARY CIRCULATOR MANAGEMENT RELAUNC...

Page 5: ...personnel and competent in the existing rules in the country in which the appliance will be installed 3 GENERAL SAFETY GUIDELINES Before beginning to operate on the units every user has to be perfectl...

Page 6: ...nt under voltage To touch the equipment if you are not allowed If the lightning risk is high the unit must be protected the risk assessment must comply with the CEI EN 62305 2 regulation If there is a...

Page 7: ...djust the summer set point value UP button In the setting mode this button allows you to move up to a higher menu or to increase the value of a parameter when you are in the edit mode DOWN button In t...

Page 8: ...cond setpoint in the summer C 18 0 Coo H03 He2 Second setpoint in the winter C 35 0 H02 Hea 5 2 2 Password menu Enter the password for the desired access level The controller will automatically open t...

Page 9: ...sequence 6 Once the update is completed the board returns to normal operation and the appliance is ready to start operation 7 Turn off the unit by placing the main switch in OFF position 8 Remove the...

Page 10: ...tion 24 Alarm signalization 31 Plant season signalization 47 Lockout signalization DO3 phase DO3N neutral Under voltage output 230Vac 50Hz 2A AC1 For the sizes of 0466 0475 and 0485 Wherever the GI op...

Page 11: ...n Continuous operation The circulator will immediately switch off if You have a pump circulator locking alarm including the manual reset flow switch alarm The unit is in stand by mode or when it s swi...

Page 12: ...it will be activated periodically for a duration given by the parameter P17 in seconds after a counting time set by the parameter P16 in minutes activated when the thermoregulation is fulfilled and th...

Page 13: ...the expansion valve the reversing valve is commutated in the opposite direction to that required by the actual mode for 5 seconds in order to allow the equilibrium of the optimal pressures for startin...

Page 14: ...15 b05 C 0 5 0 5 0 5 0 5 0 5 0 5 b25 C 2 5 2 5 2 5 2 0 2 0 2 0 7 3 5 INVERTER COMPRESSORS CONTROL IN HEATING MODE The compressors are active in heating mode if the heat pump is enabled H09 Configurati...

Page 15: ...ee the paragraph related to auxiliary electric heaters 7 5 HEAT DISSIPATION FAN MOTOR CONTROL The control of the dissipation is as a function of the condensing pressure in chiller mode operation where...

Page 16: ...rtant decreasing of the thermal efficiency of the unit it can lead also to the risk of damaging the unit itself The adjustable parameter d01 enables the defrost operation 1 enabled defrosting Please s...

Page 17: ...ated above on the DO3 DO3N terminals Parameter H81 it s possible to configure a 230Vac signal output voltage by setting the following user parameters introducing the installer password in the control...

Page 18: ...water production DHW 3 The function is active in heating mode The remote switching on off function doesn t deactivate the domestic hot water production DHW 4 The function is active in heating mode Th...

Page 19: ...hole system Note It is possible to invert the polarity of the digital input to do that please contact our technical office 9 5 3 HEATING MODE ON DOMESTIC HOT WATER TANK If the following setting H83 1...

Page 20: ...eater r24 Num 1 o 3 Type of utilization of the electric heaters 9 8 2 AUXILIARY ELECTRIC HEATER OF THE PLANT IN DEFROST CYCLE During defrost cycle see Paragraph 7 6 by setting r21 1 in addition to r10...

Page 21: ...h DHW and plant sides no priority intervention for electric heaters Settings of the parameter r32 when the boiler is being installed r32 0 boiler without a circulating pump with thermoregulation to be...

Page 22: ...his remote sensor is less than the setpoint Hea the boiler will be activated and then will be deactivated when the measured temperature by the remote sensor is greater than setpoint Hea The boiler wil...

Page 23: ...0 1 0 1 2 2 3 5 6 0 1 7 1 Auxiliary electric heater of sanitary 2 After r15 minutes boiler HEAT SAN SANITARY 0 1 1 Set up of minutes 2 3 2 3 8 1 Boiler 2 After r15 minutes auxiliary electric heater o...

Page 24: ...ter r12 minutes later heat pump HEAT HEAT SAN HEAT 1 0 1 2 Set up of minutes 1 3 1 3 3 1 Boiler 2 After r12 minutes heat pump 3 After r12 minutes later auxiliary electric heater of plant HEAT HEAT SAN...

Page 25: ...AN HEAT 0 1 0 1 2 Set up of minutes 1 3 4 6 0 2 8 1 Auxiliary electric heater of plant HEAT HEAT SAN HEAT 0 1 0 1 2 Set up of minutes 0 2 5 1 3 9 1 Boiler HEAT SAN SANITARY 0 1 0 1 2 Set up of minutes...

Page 26: ...to the open state the auxiliary electric heater of the plant will turned off It works as indicated in the TABLE 1 2 3 and 4 3 COOL SAN SANITARY Not available It works as indicated in the TABLE 5 4 COO...

Page 27: ...ng pump for the plant circuit utilizations An ambient thermostat must be appropriately configured NC state connected on the terminals DI3E DI3E by the installer Thermostat contact normally open Active...

Page 28: ...eeze alarm activation setting C 2 127 127 INSTALLER A09 Antifreeze alarm hysteresis C 3 0 0 0 25 5 INSTALLER A16 Low pressure set in cooling operation Bar Based on the model 4 0 80 0 INSTALLER A27 Low...

Page 29: ...periodic mode min 20 0 600 INSTALLER P17 Time of operation of the pump in periodic mode sec 90 0 255 INSTALLER 0 deactivation of periodic mode P18 Enabling of unique pump operation in network 0 0 1 I...

Page 30: ...activated function 1 enabled function 2 Operation of auxiliary plant side electric only if H83 1 r16 DHW auxiliary heater heat pump activation delay min 15 0 255 INSTALLER r19 Activation time of drain...

Page 31: ...matically reset for the first 2 times and goes off after 5 seconds If the alarm occurs more than 3 times per hour the manual reset of the alarm is required The alarm is not active for 10 seconds after...

Page 32: ...pump E041 Misfitted temperature alarm Heat pump E101 Communication Timeout GI module error Heat pump E611 Inlet water temp sensor error Heat pump E682 Plant water plant temperature remote sensor if e...