i-32V5C MIDI
Inverter Air/Water chillers with axial fan
23
7. HYDRONIC GROUP DATA
7.1
USEFUL HEAD
The characteristic head-flow curves net of pressure drops of the hydronic kit are shown below. On each curve the optimal working point corre-
sponding to condition (1) of the technical data table is highlighted.
The system must be designed in such a way as to guarantee the nominal flow rate relative to the working points shown below.
Flow rate m [l/s]
Useful head p models 0121, 0126 [kPa]
Useful head p models 0128, 0132 [kPa]
0,5
107,5
111,2
0,6
103,6
108,8
0,7
98,8
105,6
0,8
93,0
101,6
0,9
86,2
96,9
1,0
78,4
91,3
1,1
69,7
85,0
1,2
60,0
78,0
1,3
49,3
70,1
1,4
37,4
61,5
1,5
24,4
52,1
1,6
10,5
42,0
0,0
10,0
20,0
30,0
40,0
50,0
60,0
70,0
80,0
90,0
100,0
110,0
120,0
0,0
0,2
0,4
0,6
0,8
1,0
1,2
1,4
1,6
1,8
2,0
2,2
p
[kP
a]
m [l/s]
p 0121, 0126
0121
0126
p 0128, 0132
0128
0132
7.2 PRESSURE DROP Y-FILTER ACCESSORIES
Flow rate [l/s]
Pressure drop Y-filter models 0121, 0126
[kPa]
Pressure drop Y-filter models 0128, 0132
[kPa]
0,5
1,92
1,44
0,6
2,76
2,07
0,7
3,76
2,82
0,8
4,91
3,69