In this mode, four-way valve electrify. 

Note:

 

In each mode, after protection and unit stop, modes switch or unit off, 4-way valve will power off after 2 minutes delay. 
7.2.3.5 Defrosting under Heat mode 
Under Heat mode, there is intelligent defrosting. 
7.2.3.6 Heating Turbo function 
When outdoor unit received heating mode Turbo function from the indoor unit, at this time, outdoor unit add certain 
frequency running. 
7.2.4 Fan mode 
When outdoor unit main mode transfer from Cool (Dehumidify) or Heat mode to Fan mode, compressor stop running, 
outdoor fan will stop running after 1min delay. 
7.2.5 Electric heat control target 
7.2.5.1 Compressor electric heat belt control 
After powered on, if T

out_amb.

 

 -5°C and compressor hasn’t start up, electric heat belt will start to work. 

After compressor started up or T

out_amb.

> -3°C, the electric heat belt will stop to work; 

If -5°C < T

out_amb

, compressor electric heat belt will keep original status. 

7.2.5.2 Chassis electric heating cord control (optional) 
From entering into Defrosting to Defrosting finish, within compressor started up 3 minutes, if ambient temp. is very low, 
chassis electric heating belt work; if ambient temperature is very high, it will not work. 
7.2.6 System protection function 
7.2.6.1 Indoor unit modes confliction protection 
If indoor unit presetting is different, will accord to the following condition for running: will accord to the first entering indoor 
unit mode for the fiducial mode, to compare with other indoor unit modes to judge whether confliction happen or not. 
1) Cool (Dehumidify) conflict with Heat mode: some indoor unit received the outdoor unit mode confliction signal later, this 
indoor unit will turn off, memorize unit off status. 
2) Fan and Heat confliction: some indoor unit received outdoor unit mode confliction signal later, this indoor unit will turn 
off, memorize unit off status. 
7.2.6.2 Air exhaust temperature protection 
If continuously 6 times, air exhaust temperature protection happened, the compressor cannot resume to run. If need to 
power off and re-power on can resume. (if compressor running time exceed 7mins, the protection time will clear 0.) 
7.2.6.3 Communication malfunction 
If continuously 3mins hasn’t received the correct signal of indoor unit and within 10s, cannot receive the correct signal 
from the drive board that is the communication malfunction, outdoor unit will stop running, auto heating or heating mode, 
blow surplus heat, in other modes, indoor unit will run at presetting fan speed. 
7.2.6.4 Power module protection and module overheat protection 
Mode protection acts, compressor stop running, after compressor stopped 3mins, will automatically resume to running 
status, if protection times continuously happened 6 times (if compressor running time exceed 7mins, the protection times 
will clear 0), unit turned off and sent wrong signal to indoor unit, cannot resume running status; It is need to re-power on 
can resume to run. 
7.2.6.5 Compressor overcurrent protection 
If detected the whole unit current value exceeded the determinative value, compressor stopped 3mins later, it will 
automatically resume to running status, protection times exceeds 6 times (if compressor running time is more than 7min, 
that the protection times will clear to 0), unit will turn of sent wrong signal to indoor unit, cannot automatically resume to 
run. At this time, it is need to power off and re-power on can resume. 
7.2.6.6 Sensor malfunction detection 

Outdoor

: at unit standby, do not test outdoor each sensor malfunction, unit turned on and compressor continuously run 

for 3mins later, start to detect air exhaust sensor malfunction; Defrosting (or heating oil return) finished, within 10mins, do 

Summary of Contents for BD2M53A3

Page 1: ...This manual has been created for informative purpose The company declines every responsibility for the results of projecting or installation based on the explanations and the technical specifications...

Page 2: ...erie Series Serie Serie TECHNICAL MANUAL SPLIT LIGHT MULTI DC Emissione Issue Ausgabe Emission 03 2013 Catalogo Catalogue Katalog Catalogue MTE01028D2820 01 Sostituise Supersade Ersetzt Remplace 04 20...

Page 3: ...6 2 Basic functions 14 6 3 Others 14 6 4 Displayer 15 7 Outdoor units Operation 17 7 1 Temperature parameters 17 7 2 System basic function 17 8 Troubleshooting 20 8 1 Malfunction Display of Indoor Un...

Page 4: ...ial Aluminum fin copper tube Rows Fin Gap mm 2 1 4 Coil length l x height H x coil width L mm 851 x 660 x 38 1 982 2 x 748 x 38 1 Fan motor apeed rpm 880 700 500 690 600 500 Output of fan motor W 60 F...

Page 5: ...odel MP24AA MP28VB Output of swing motor W 1 5 1 5 2 0 Fuse A PCB 3 15A Indoor sound level H M L dB A 39 34 28 40 35 30 43 40 35 Dimension W D H mm 790X174X265 845X180X275 940 200 298 Dimension of pac...

Page 6: ...Rotating Speed BDLM26A2 BDLM36A2 BDLM53A2 2 Outlines and dimensions 2 1 Indoor units W H D 50 85 194 694 52 172 542 131 6 1 1 8 3 45 36 8 7 0 4 40 09K Units 12K Units 18K Units 9 4 1 5 0 6 69 55 55 55...

Page 7: ...8 2 2 Outdoor units a BD2M53A3 892 341 396 963 560 700 368 U nit m m b BD3M98A3 924 370 427 1001 610 790 399 U nit m m...

Page 8: ...odel C 2 C 3 B 3 B 2 A 2 A3 Note Not available for 14K 18K model A1 A unit electronic expansion valve A2 A unit gas pipe temperature sensor A3 A unit liquid pipe temperature sensor B1 B unit electroni...

Page 9: ...AND DISPLAY BOARD BU RD HEALTH N HEALTH L GENER ATOR COOL PLASMA NOTE The parts with broken line is applicable to the models with COO L PLASMA GENERATOR EVAPORATOR BDLM53A2 M2 M1 TEMP SENSOR TEMP SENS...

Page 10: ...11 4 2 Outdoor unit BD2M53A3 BD3M98A3...

Page 11: ...A2 BDLM36A2 Top View 1 2 8 5 3 7 6 4 9 10 11 12 13 13 Protective tube No Part name 1 Interface of neutral wire 2 Interface of PG motor 3 Interface of health function live wire 4 Interface of auto butt...

Page 12: ...15 16 16 Neutral wire terminal No Part name 1 Compressor terminal 2 High pressure protection 3 Low pressure protection 4 Compressor overload protection 5 Outdoor temp sensor terminal 6 Terminal chass...

Page 13: ...oor fan switching into low speed will stops after 1 min delay 5 Anti cold air After heating compressor runs indoor fan runs according to the following conditions If compressor runs within 90s and Tin_...

Page 14: ...ontrol order of last setting and it will run at that mode 6 3 5 I Feel function When controller received the orders that the controller will work according to ambient temperature which is sent by remo...

Page 15: ...he fan speed is high and set temperature is 16 C The horizontal louver will be at the smallest angle Action of exit refrigerant recovery mode the indoor fan will operate according to the last remote c...

Page 16: ...mode four way valve off cannot electrify 7 2 1 5 Control logic in detail According to the difference of indoor unit evaporator inlet and outlet temperature called actual overheat degree and goal over...

Page 17: ...indoor unit received outdoor unit mode confliction signal later this indoor unit will turn off memorize unit off status 7 2 6 2 Air exhaust temperature protection If continuously 6 times air exhaust t...

Page 18: ...otection Due to each protection malfunction arrived at the temperature after compressor stopped running when restart up there will be 3mins delay power off exception 7 2 6 9 Compressor high pressure p...

Page 19: ...ction b7 Flash 22 times Short open circuit of the of the IPM module temp sensor P7 Flash 18 times Short open circuit of the outdoor ambient temp sensor F3 Flash 3 times Short open circuit of the tempe...

Page 20: ...ble causes 1 There is no jumper cap on the controller 2 Jumper cap is not inserted properly and tightly 3 Jumper cap is damaged 4 Controller is damaged See the flow chart below U8 is displayed on the...

Page 21: ...retart up the unit test if the voltage between on contral terminal board for PG motor is more than 50V within 1 min after the louvers are opened Replace the mainboard with the same model Insert the w...

Page 22: ...hing jumper cap Is the jumper cap inserted incorrectly or improperly Is the malfunction eliminated Replace the jumper cap Is the malfunction eliminated The mainboard is defined abnormal replace it End...

Page 23: ...it and check if the connecting wire of indoor and outdoor unit and wiring of electric box are correct Is wire connected correctly Does the broken down indoor unit resume normal Replace the broken down...

Page 24: ...ing wire damaged Check if there is power input between neutral wire and live wire of outdoor unit Is there power input Replace mainboard of outdoor unit Does communication resume normal End Connect wi...

Page 25: ...or protection 28 Outdoor tube temperature sensor protection 29 Discharge temperature sensor protection 30 IPM thermal resistance malfunction 31 Unit A liquid pipe temperature sensor malfunction 32 Uni...

Page 26: ...checking and elimination Note Discharge the position in below pictures with discharge resistance after open the top cover and check if the voltage is below 20V with universal meter then begin to check...

Page 27: ...the radiation 2 if the indoor and outdoor fans are running normally 3 if the pressure of the system is too high 4 if the refrigerant is too much which causes the high level of pressure If the wire of...

Page 28: ...nboard End Turn on the unit after the power supply resumes to normal situation Replace the induction Malfunction is eliminated No Yes No Yes Yes Energize the unit and wait for 1min Test the voltage be...

Page 29: ...e outdoor fan is working normally Replace outdoor mainboard End It is a normal protection please operate the unit after the outdoor ambient temperature has changed Improve the radiation environment of...

Page 30: ...tion wire of the compressor is connected well and correctly If the refrigerant charging amount is too much Charge the refrigerant according to the service manual Eliminate the malfunction Replace the...

Page 31: ...e check the connection wire of indoor and outdoor unit and the wire of the electric box is connected correctly Connected correctly De energize change the communication wire of the well communicated in...

Page 32: ...The connection wire is broken Check if there is power input between the neutral wire and live wire of the outdoor mainboard There is power input Replace the outdoor mainboard Resume communication End...

Page 33: ...Judge the condition of the electronic expansion valve through detecting this resistance Start If the overload protector is connected well Check the resistance between the two ends of the overload pro...

Page 34: ...ynchronizing as soon as energizing and starting The stop duration of the compressor is longer than 3min The wiring of the compressor is connected properly The electric expansion valve is broken Replac...

Page 35: ...34 10 2 73 2 358 112 0 717 4 60 23 35 9 779 74 2 28 113 0 697 3 57 18 36 9 382 75 2 206 114 0 678 2 54 31 37 9 003 76 2 133 115 0 66 1 51 59 38 8 642 77 2 064 116 0 642 0 49 02 39 8 297 78 1 997 117 0...

Page 36: ...3 3 144 112 0 956 4 80 31 35 13 04 74 3 04 113 0 93 3 76 24 36 12 51 75 2 94 114 0 904 2 72 41 37 12 76 2 844 115 0 88 1 68 79 38 11 52 77 2 752 116 0 856 0 65 37 39 11 06 78 2 663 117 0 833 1 62 13 4...

Page 37: ...63 10 93 102 3 129 14 342 8 25 49 19 64 10 54 103 3 04 13 323 9 26 47 08 65 10 18 104 2 955 12 306 2 27 45 07 66 9 827 105 2 872 11 289 6 28 43 16 67 9 489 106 2 792 10 274 29 41 34 68 9 165 107 2 715...

Page 38: ...39...

Page 39: ......

Page 40: ...Via Gettuglio Mansoldo Loc La Macia 37040 Arcole Verona Italy Tel 39 045 76 36 585 r a Fax 39 045 76 36 551 r a www maxa it e mail maxa maxa it...

Reviews: