Introduction 

The 

matt

:

e

  of range Single Phase Electric Vehicle Charger Protection units 

are designed to protect Electric Vehicle Charging equipment when installed 

onto single phase PME infrastructures .  

 

All units incorporate an electronic detection circuit and 3 pole contactor.  The 

R version has a Type A RCBO on the incoming side of the unit.  

 

On detection of fault conditions the electronic circuit disconnects the EV 

charger from the incoming supply including CPC. The isolation contactor is 

certified to BSEN 60947 and complies with the requirements of BS: 7671 18th 

Edition. 

 

The 

matt

:

e

 SP-EVCP technology does not require earth rods or measuring 

electrodes to function correctly. 

 

The unit is designed to be installed between the distribution board and the 

Electric Vehicle Charger. 

 

The installation location should be clean, dry and well ventilated.  

 

 

 

 

matt

:

no longer use plastic bags as part of our product packaging.  

Wherever possible we utilise reusable biodegradable packaging for 

transportation.  We ask that you support our efforts to reduce un-necessary 

waste and recycle all packaging appropriately. Thank you.

 

 

 

Summary of Contents for SP-EVCP-R

Page 1: ...Electric Vehicle Charger Protection Units SP EVCP T SP EVCP R Installation Manual V1 0 Oct 2019...

Page 2: ...ections 6 Operating Instructions 8 Specifications 9 Warranty 9 Declaration of Conformity 10 PRODUCT ADVISORY NOTICE This product must be installed by a competent person in accordance with the IEE Wiri...

Page 3: ...at defined within this document WARNINGS Please read and observe the following notices carefully These warnings must be observed when installing and operating the Electric Vehicle Charger Protection u...

Page 4: ...the incoming supply including CPC The isolation contactor is certified to BSEN 60947 and complies with the requirements of BS 7671 18th Edition The matt e SP EVCP technology does not require earth ro...

Page 5: ...Single Phase EV Charger Protection unit 5 P a g e Please refer to the diagram below for the dimensions and mounting arrangements of the unit...

Page 6: ...Single Phase EV Charger Protection unit 6 P a g e Electrical Connections The user wiring connections are indicated in the diagrams below...

Page 7: ...Phase EV Charger Protection unit 7 P a g e Connect the incoming cable from the distribution board directly to either the terminals T version or the RCBO R version Connect the outgoing cable to the con...

Page 8: ...ply switched on the unit will monitor the incoming supply voltage If the incoming supply is within limits approximately 5 seconds after switching on the contactor will energise and connect the load to...

Page 9: ...X Document Revision V1 0 Oct 2019 Terminal Capacities Min Max Torque Incoming Terminals cable size tightening torque 0 5 mm 2 6 0mm 2 1 3Nm Incoming RCBO cable size tightening torque 2 5 mm 2 16 0mm 2...

Page 10: ...Object of the declaration Electric Vehicle Charger Protection units SP EVCP T SP EVCP R The object of the declaration described above is in conformity with the relevant Union harmonisation legislatio...

Reviews: