Mains Electricity Connection
Warning! this appliance must be earthed
We recommend that the appliance is connected by a qualified electrician, who is a member of the N.I.C.E.I.C. and who will
comply with the I.E.E. and local regulations.
This appliance is intended to be connected to fixed wiring and is not suitable for connection to a 13a plug or 13a
supply.
This appliance is intended to be connected to fixed wiring by a double pole switch, having a contact separation of at least
3mm in all poles. The switch must be positioned no further than 2m from the appliance.
Please note:
•
The mains cable must only be replaced by a qualified electrician or service engineer and must be of equivalent or
better rating (i.e. 2.5mm
2
, HO5RR-F).
•
This appliance is intended to be connected to the mains supply with a cable of cross section area 2.5 mm². A larger
cable will not fit the terminal connections.
•
The marking of the current rating of the fuse or circuit breaker protecting this appliance should be marked on the
socket outlet.
•
Assembly and electrical connection should be carried out by specialised personnel.
•
When installing this product we recommend you seek the help of another individual.
TECHNICAL DATA:
The table opposite shows the rated output of each hotplate:
Mains electrical voltage: 230 - 240Vac, 50Hz
Total rated electrical input: 5kW
Hotplate Size
Nominal Rating (kW)
Heat setting
Description
180mm
1.5kW (FL) / 2.0kW (BR)
145mm
1.0kW (BL) / 1.5kW (FR)
7