background image

M A T E L E C   A U S T R A L I A .   P   1 8 0 0   2 8 1   2 8 2 .   F   1 3 0 0   2 8 1   2 8 2

I N F O @ M A T E L E C A U S T R A L I A . C O M . A U .   W W W . M A T E L E C A U S T R A L I A . C O M . A U

SMOKE ALARM FSA-20000

240V A.C photoelectric smoke alarm with 9V battery backup

THIS SMOKE ALARM MUST BE INSTALLED BY A LICENSED ELECTRICAL CONTRACTOR.

TM

AC

TIVFIRE

    

   

D

E

T

S

I

L

•  220 - 240 a.c
•  9V D.C battery backup
•  Photoelectric technology
•  0°C to 40°C operating temperature
•  Operates in 10% to 90% ambient humidity

•  Nominal Sound Level output 88dB
•  Listed by Activfire
•  Complies with AS3786:2014

SUGGESTED ALARM LOCATIONS

•  As close to the centre of the ceiling as possible; or at least no closer than 60cm to any wall or corner. If mounting smoke alarm  
  on wall, always locate the top of the smoke alarm 10-30cm from the ceiling (diagram A).

•  As a minimum, smoke alarms should be located between sleeping areas and potential sources of fire such as a kitchen,    
  heated garage or basement. In single storey homes with one sleeping area, an alarm should be installed in the hallway outside  
  the bedrooms. In single story homes with two sleeping areas, a minimum of two alarms are required. One outside each  

 

  sleeping area. In multilevel homes (includes guest, hostel etc), an alarm should be installed outside and inside each sleeping  
  area, in the basement and on every level of the home.

•  Additional smoke alarms should be installed in bedrooms in anticipation of fires originating within these rooms, caused by   
  faulty wiring lamp, appliances, smoking or other hazards.

•  For best protections, smoke alarms should be installed in every room, or every level of your home.

•  Install smoke alarm in hallways at a distance no greater than 4 metres from the farthest wall and no greater than 8 metres from  
  the next alarm.

•  The distance from the apex of cathedral ceiling to the top of the smoke alarm should be 90cm minimum.

•  For mobile homes, smoke alarm must be mounted on an internal wall not external wall or ceiling as these surfaces heat up etc.

•  Including Smoke Alarms on a circuit with LED Lighting or fans, can cause signal interference, resulting in nuisance alarming or  
  beeping. A load correcting device should be installed before the first smoke alarm on a circuit to rectify any nuisance alarms  
  on installs where this has occurred.

AVOID THESE LOCATIONS

DO NOT INSTALL A SMOKE ALARM:

•  in the kitchen or the garage as this can result in nuisance triggering.
•  within 1 metre of heating and cooling vents or within one metre of
  return air or fresh air vents.
•  in areas where temperatures may fall below 0°C or rise above 40°C.
•  in areas where relative humidity may be outside the range of
  10% - 90%, for example bathrooms.
•  within 1 metre of a fluorescent light.
•  in areas where bugs or insect are present before eliminating
  or minimising the problem.
•  in the dead air space where the wall meets the ceiling.
•  on the ceiling of a caravan or mobile home.

Reviews: