Maximum Run and Alternation Mode

With 

DIP Switch 3

 set to “Off” the unit will alternate as usual each time a pump start condition occurs. Additionally, the 

controller will automatically alternate pump duty if a pump has been running continuously for 30 minutes (maximum run 

timer)

Setting this DIP Switch to “On” will cause the controller to operate in “Circulation Mode” where duty will only alternate 

once the pump has run for 6 hours of accumulated time.

Anti-Seize Timer

With 

DIP Switch 4 

set to “On”, the Anti-seize timer will automatically run the pumps for 6 seconds, every 7 days. This 

pump operation will completely override all inputs including the low level (if enabled). This feature will only run pumps 

that are set in Auto. This “Pump Run”, will alternate between Pump 1 and Pump 2. A pump that has been locked out due 

to a fault will not run.

-

Manual Mode Timeout

With

 DIP Switch 5

 set to “On” the pump will only remain in Manual Mode for 5 minutes, after which time, it automati

cally reverts to Auto.

High Level Alarm Reset

With 

DIP Switch 6

 set to “Off”, the High Level Alarm will automatically reset once the High Level input opens circuit. The 

controller will also use the alternate High Level Alarm Delay. Typically used for Storm Water applications. High Level Alarm 

delay in this mode is 15 minutes.
Setting this DIP Switch to “On”, will cause the High level Alarm to remain active until the controller is reset. The High 

Level Alarm will use the standard High Level Alarm activation delay. Typically used for Sewerage applications. High Level 

Alarm delay in this mode is 5 minutes.

-

Audible and Visual Alarm Test

By pressing the

 Mute/Reset 

button on the Keypad continuously for a period of 5 seconds, the Strobe, Siren and indica

tor Lights will be powered up for inspection.

 

Fault Reset

To reset all faults on the controller, press and old the 

Mute/Reset

 button on the Keypad continuously for a period of 3

seconds until an acknowledgement beep is heard.

Pump Fault

A Pump Fault is indicated for two types of faults. A Thermal Overload will be indicated by way of a steady Fault Indicator 

Light when the overload opens the contact for 3 seconds. Prime loss will be indicated by flashing the pump fault light slowly.

Level Alarms

A High Level Alarm is indicated by way of a steady Level Alarm Indicator Light.

A Low Level/Low pressure Alarm is indicated by way of a Flashing Level Alarm Light.

lly 

Auto Silencing Alarm Feature

The audible Alarm is programmed to sound for 5 minutes continuously, unless muted and will thereafter automatica

In pressure pump mode some of the optional features are disabled, including maximum run alternation, anti-seize and 

maximum idle timers.

Mode ‘Current Loop’: Level Transducer (4-20mA) Configuration

In order to activate current loop mode the enclosure must be opened and jumper J10 moved to the “current loop 

enabled” position (as shown in the following picture). By selecting current loop input mode the pump start input can be 

connected to a 4-20mA loop powered pressure transducer. The pump start, stop and high level signals can then be 

received from the pressure transmitter instead of float switches. In this mode the pump stop float switch input will be 

ignored however the high level input will still operate as per normal so that a float switch can be used as backup if 

desired.
The start, stop and high level current set points will be pre-programmed into the software and therefore cannot be 

adjusted. The levels for a 0-4m transducer are Stop= 300mm, Start= 600mm and High= 1000mm.

Figure 1: APC6 PCB Layout and Current Loop Jumper 

 

 

Current Loop

Enable Jumper

 

Dip Switch Setting

Ensure dip switch 1 and 2 are down 

in mode A for transducer operation 

Summary of Contents for FPC-32020

Page 1: ...ating Instructions P U M P C O N T R O L OWNER S OPERATION MANUAL MODEL FPC 32020 MAIN ISOLATOR OFF ON PUMP ON FAULT PUMP ON FAULT SYSTEM TEST MAINS WATER RAIN WATER SYSTEM FAULT Rain Mains Water Cont...

Page 2: ...nctional reliable and user friendly operation Please read this manual prior to installation and operation of the controller OPERATION 4 Operations Features WARNING All electrical connections must be c...

Page 3: ...OFF ON PUMP ON FAULT PUMP ON FAULT SYSTEM TEST MAINS WATER RAIN WATER SYSTEM FAULT Rain Mains Water Controller DANGER HIGH VOLTAGE DO NOT REMOVE COVER AUTHORIZED PERSONS ONLY PUMP 1 240Vac MAINS POWER...

Page 4: ...active Low Level input The Low Level input must be closed for Pump Start and Pump Stop inputs to function The High Level input however will still override the Low Level and run both pumps Input funct...

Page 5: ...rom close of Input contacts This run on occurs even if Lead Pressure switch opens circuit during this initial period If however run time exceeds 11 seconds the pump will stop immediately upon Open Cir...

Page 6: ...ll be powered up for inspection Fault Reset To reset all faults on the controller press and old the Mute Reset button on the Keypad continuously for a period of 3 seconds until an acknowledgement beep...

Page 7: ...2 AUX C NO R1 BUZZER TRANSFORMER 32amp 2 POLE PUMP 1 ISOLATOR 32amp 2 POLE PUMP 2 ISOLATOR 12Vac 240Vac INPUT 2 LEAD INPUT 3 LAG INPUT 4 LOW 12Vdc 12Vdc 1 L O T 2 L O T N E PUMP 1 1 R O T C A T N O C...

Page 8: ...resent PUMP ON ON STEADY A pump fault overload has occurred ON STEADY Pump switched on to run If selected the LED indicator will confirm if on the pump is set to Manual Pumping Mode MAN If selected th...

Reviews: