The basic logic on which a High or Low Level Alarm is determined, is set out in the Table below:

If there is a Low Level Alarm, then both Pumps will be locked out until the alarm is manually reset. This lockout will only 

be over ridden upon a High Level condition where both the Pump Start and High level inputs are closed.

Note that after a High level is triggered, the pumps will both run until the Pump Start and Stop inputs are opened

Mode C: Standard Configuration plus Prime Loss

Mode D: Pressure Pumping Configuration

Typical Operation Mode D:

As per Mode A, except Input 1 is connected to a prime loss/flow switch. If at any stage, after Pump Start, or whilst a 

pump is running, the Prime Loss input opens, for a continuous 2 minute period, a fault is immediately triggered for that 

pump and duty alternates. Input functions are as follows:

Duty Pump: 

 

Lead Pump

Standby Pump:   

Lag Pump

Input functions are as follows:

•  

Pressure drops to 400kPa: Lead (for this cycle) Pump cuts in.

•  

Pressure increases and Pump cuts out.

•  

Cycle continues with duty (Lead and Lag) alternating between the two pumps.

•  

If  pressure  continues  to  drop  to  350kPa,  the  Lag  Pump  will  cut  in  and  remain  running  until  Lead  Pressure   

        Switch opens circuit. Then duty alternates.

•  

No faults are logged against the Lead Pump if the Lag Pump starts.

•  

The controller has inbuilt timers for “Delayed” Start and Stop to obviate pump chatter. Upon Input 1 contact 

 

closure, the pump will not start (delay start) for 1 second and will not stop (minimum run time) for 10 seconds  

      (or 11 seconds from close of Input contacts). This “run on” occurs even if Lead Pressure switch opens circuit 

       during this initial period. If however run time exceeds 11 seconds, the pump will stop immediately upon “Open 

        Circuit” occurring.

•  

If the Lead Pressure Switch input closes circuit as well as he Low Pressure Switch input, both pumps will be 

 

turned on and the Low Pressure Timer will begin counting. If this condition exists for a period of 60 seconds, 

        then both pumps are shut down and the system signals a level alarm. This would be typical of a Loss of Prime, 

        or Burst main situation.

•  

Pressure switches are normally Closed and Opened on High Pressure.

•  

Prime Loss functions as per mode Mode C.

Input

Function

Input 1

Prime Loss

Input 2

Pump Stop

Input 3

Pump Start

Input 4

High Level

Input

Function

Input 1

Prime Loss (BRIDGE IF NOT REQUIRED

Input 2

Lead Pump Pressure Switch (set at say 400kPa)

Input 3

Lag Pump Pressure Switch (set at say 350kPa)

Input 4

Low Pressure Switch (set at say 200kPa)

Input 1

Input 2

Input 3

Input 4

Pump

State

Alarm

Low Level

Pump Stop

Pump Start

High Level

Closed

Open/Closed

Open

Open

Off

-

Closed

Open/Closed

Closed

Open

On

-

Closed

Open/Closed

Closed

Closed

Both On

High Level (after Timeout)

Closed

Open/Closed

Open

Closed

Both On

High Level (after Timeout)

Open

Open/Closed

Open

Open

Off

-

Open

Open/Closed

Closed

Open

Off

Low Level

Open

Open/Closed

Open

Closed

Off

Low Level

Open

Open/Closed

Closed

Closed

Both On

High Level (after Timeout)

Summary of Contents for FPC-30020-CON

Page 1: ...PUMP ON FAULT PUMP ON FAULT MAIN ISOLATOR P U M P C O N T R O L OWNER S OPERATION MANUAL Dual Pump Controller Installation and Operating Instructions MODEL FPC 30020 CON VER 1 0...

Page 2: ...st be Circuit Breaker Protected Qualified Electrician to determine appropriate amp rating Electrical connection to the panel must be carried out in accordance with Connection Instructions see page 3 A...

Page 3: ...not compromise the weather proof rating of the enclosure Note Controller must be earthed and all electrical connections must be carried out by a suitably qualified Electrician For Single Working Level...

Page 4: ...minute delay On High Level Alarm can only be reset manually High Level Alarm has 5 minute delay Mode A Standard Configuration Start Stop High Level operation When the Pump Start input is closed conta...

Page 5: ...n Input 1 contact closure the pump will not start delay start for 1 second and will not stop minimum run time for 10 seconds or 11 seconds from close of Input contacts This run on occurs even if Lead...

Page 6: ...Mode Timeout With DIP Switch 5 set to On the pump will only remain in Manual Mode for 5 minutes after which time it automatically reverts to Auto High Level Alarm Reset The controller will also use th...

Page 7: ...ction PUMP UP Function PUMP DOWN Sensitivity adjustable by a potentiometer 5 100k Measuring frequency 10Hz prevents polarization of liquid and raising oxidation of measuring probes Galvanically separa...

Page 8: ...tance Voltage n electrodes Current in probes Time response Max capacity of probe cable Time delay t Time delay after switching on t1 Accuracy Accuracy in setting mechanical Output Number of contacts C...

Page 9: ...se a tank made of a conductive material you can use it as probe C In case you require monitoring of one level only it is neccessary to connect inputs H and D and connect them to one probe in this case...

Page 10: ...10 CIRCUIT DIAGRAM...

Page 11: ...11 NOTES...

Page 12: ...level alarm is present ON STEADY Pump switched on to run ON STEADY A pump fault overload has occurred FLASHING A prime loss fault has occurred Silences the siren and if held down for 3 seconds clears...

Reviews: