Mastervolt 130506000 Installation Manual Download Page 7

 
 
 
 
 
 

 

INSTALLATION 

 

EN / DC Connection kit for solar electric applications / January 2011 / Copyright © 2011 Mastervolt   

  

7

 

4.6 WIRING 

INSTRUCTIONS 

 

WARNING 

High voltages (up to 600 VDC) may exist on 

the PV-strings! Connection of the DC-cabling 

may only be carried out if the DC-cables are 

voltage free. Therefore the PV-modules must 

be disconnected from the DC-cabling (for 

instance by disconnecting the MultiContact 

connectors at the PV-modules). 

 

CAUTION! 

 Short circuiting, reversing polarity or 

interchanging of PV-strings may lead to 

damage to the DC Connection kit, the 

Solar inverter, the cabling and/or the 

terminal connections.  

  The maximum output current may not 

exceed 30A for each output of the DC-

Switch. 

  If two ore more strings are connected to 

the same Solar-input, both string lengths 

must be equal.  

 Follow all steps of the installation 

instructions in order of succession as 

described.  

  During the entire installation the rotary 

switch of the DC Connection kit must stay 

in the O-position (OFF). 

  Do not change the existing wiring of the 

DC Connection kit  

 

Refer to chapter 6 for typical installation 

examples. 

 

  <<<< TEXT REMOVED >>>> 

 

4.6.1 

Things you need: 

To connect the DC Connection kit to the inverter you need 

the following cables, long enough to reach from the DC 

Connection kit to the inverter (not included with the 

delivery)  

  Three double isolated DC cables with positive (+) 

marking (e.g. red colour) ,  

  Three double isolated DC cables with negative (–) 

marking (e.g. black colour)   

 

4.6.2 

Wiring between PV-modules and the DC 
Connection kit

 

 

See figure 3. First make the connections to INPUT 1, and 

then make the connections to INPUT 2, followed by INPUT 

3.  

 

Turn the rotary switch of the DC Connection kit to the 

O-position (OFF).  

Mount the DC Connection kit in a closed cabinet. 

Strip approx. 10 mm of the DC-cables and connect 

the cables as indicated. 

 

4.6.3 

Wiring between the DC Connection kit

 

and inverter  

See figure 3. Follow in detail all steps of the installation 

instructions in order of succession as described below. 

 

Make sure the rotary switch of the DC Connection kit 

is still set to the O-position (OFF).  

Strip approx. 10 mm on both sides of the DC cables  

3  Connect the DC cable with positive marking (+) 

between the positive (+) connection of the OUTPUT 

and the positive (+) DC Solar input of the inverter.  

Repeat this for the negative (–) connection. 

Repeat steps 3 and 4 to connect the OUTPUT 2 to 

DC Solar input nr. 2 of the inverter.  

Repeat steps 3 and 4 to connect the OUTPUT 3 to 

DC Solar input nr. 3 of the inverter. 

 

4.6.4 

Connection to the safety ground (PE) 

See figure 3. Connect the earth terminals of the varistors 

to the safety ground (PE) as indicated. The wiring of this 

connection should have a minimum cross section of 16 

mm².  

Summary of Contents for 130506000

Page 1: ...ion kit for solar electric applications TRIPLE OUTPUT MODEL FOR SUNMASTER XL 10 AND XL15 MASTERVOLT Snijdersbergweg 93 1105 AN Amsterdam The Netherlands Tel 31 20 3422100 Fax 31 20 6971006 www masterv...

Page 2: ...TY GUIDELINES AND WARNINGS 4 2 1 Warnings and symbols 4 2 2 Use for intended purpose 4 2 3 Organisational measures 4 2 4 Installation maintenance and repair 4 2 5 Warning of special dangers 4 3 SPECIF...

Page 3: ...0V 30A 6p 1 4 GUARANTEE SPECIFICATIONS Mastervolt assures the product guarantee of the DC Connection kit during two years after your purchase on the condition that all instructions and warnings given...

Page 4: ...the DC Connection kit other than as mentioned in this section is not considered to be consistent with the intended purpose Mastervolt is not liable for any damage resulting from the above 2 3 ORGANIS...

Page 5: ...ing voltage 600 V AC 50 Hz Nominal discharge current 20 kA 8 20 Maximum discharge current 40 kA 8 20 Protection level Up 2 3 kV Pr pster order nr 206 602 see www proepster com Connections 3 inputs wit...

Page 6: ...rter in a closed cabinet protected against rain moist dust and condensation 4 4 PV MODULES AND STRINGS The solar or DC side of the system consists of several photovoltaic solar modules further mention...

Page 7: ...tion kit to the inverter not included with the delivery Three double isolated DC cables with positive marking e g red colour Three double isolated DC cables with negative marking e g black colour 4 6...

Page 8: ...Connections of the DC Connection kit INPUT 3 INPUT 3 INPUT 3 INPUT 1 INPUT 1 INPUT 1 INPUT 3 INPUT 1 OUTPUT 3 OUTPUT 1 INPUT 2 INPUT 2 INPUT 1 INPUT 2 OUTPUT 2 INPUT 3 INPUT 3 INPUT 3 INPUT 3 OUTPUT 3...

Page 9: ...he inverter 3 If the voltage and polarity of the strings is OK turn the rotary switch of the DC Connection kit to the 1 postion 4 Check whether the DC voltage is present at the inverter refer to the u...