DAILY USE OF THE MASTERLINK MICC:
Adjustment of the Power sharing / Power
support level
When the available current from the AC source is
limited (for instance to avoid the shore fuse from
tripping), the maximum AC input current of the Mass
Combi can be limited. Follow the steps below:
VOLT & CHG.AMP
25.54V 0.3A
VOLT & CHG.AMP
25.54V 0.3A
Press
Charger
once
POWER SHARING.
25.0A
Ç
Hold
Select
pressed for 5 sec. to change the arrow’s
direction. If pointing upwards (
Ç
), the
Power sharing /
Power support
level can be increased; if pointing
downwards (
È
), it can be lowered.
Press
Set-up
several times to adjust the
Power
sharing / Power support
level
After adjustment, press
Select
once
EXIT LEVEL
->PRESS SET-UP
Press
Set-up
once.
Now the Select-LED stops blinking
VOLT & CHG.AMP
25.54V 0.3A
Ready!
Hold
Select
pressed until the
Select LED starts blinking
Power Support Function
The
Power Support Function
can be enabled by means
of DIP-switch B-SW4. If enabled and the total demand
for AC power is more than the
Power Sharing level
,
load connected to the
Short Break
output will be
powered by the inverter while load connected to the
Power
output will be powered by the external AC-
source. See sections 3.3.5 and 6.2.2 of the user’s
manual of the Mass Combi for more information.
DIP switch B
SW4
Power support function disabled
OFF
Power support function enabled
ON
INITIAL DIP-SWITCH SETTINGS AT THE MASS COMBI (CONTINUED)
Generator / mains support function
With the Generator / mains support function enabled,
AC power from the inverter is added to both AC outputs
if the total demand for AC power is higher than the
Power Sharing level. See section 3.3.4 and 6.2.3 of the
user’s manual of the Mass Combi for more information.
DIP switch B
SW5
Generator / mains support function disabled
OFF
Generator / mains support function enabled
ON
6
INITIAL SETTINGS AT THE MASTERLINK
MICC
Start from the initial menu to configure the
Masterlink MICC for use with the Mass Combi.
VOLT & CHG.AMP
25.54V 0.3A
Hold
Select
pressed until the
Select LED starts blinking
VOLT & CHG.AMP
25.54V 0.3A
Press
Set-up
once
SLEEP MODE
ON
HFC mode
OFF
Press
Select
3 times
Press
Set-up
once to enable the HFC mode
HFC mode
ON
Press
Select
once
EXIT LEVEL
->PRESS SET-UP
Press
Set-up
once.
Now the Select-LED stops blinking
VOLT & CHG.AMP
25.54V 0.3A
Ready!
7