Mastervolt International Masterlink MICC Quick Start Manual Download Page 1

Use of the Masterlink MICC with the Mass Combi

 

 

 

 

 

 

 

 

 

 

 

Mastervolt International B.V,

    P.O.Box 22947,   NL-1100 DK Amsterdam,   The Netherlands.    

Tel.:

 +31-20-3422100    

Email:

 [email protected]    

Web:

 www.mastervolt.com   v1.2 071206EN 

INITIAL DIP-SWITCH SETTINGS AT THE MASS COMBI

  

Power sharing level 

The Power Sharing Level can be adjusted by means of the Masterlink MICC (see step 7). The absolute maximum 
level for this setting can be fixed by means of DIP-switches B SW1, SW2 and SW3. 
See sections 3.3.3 and 6.2.1 of the user’s manual of the Mass Combi for more information. 

230V Models 

 

DIP switch B 

SW1 

SW2 

SW3 

25 Amps. 

OFF  

OFF  

OFF  

16 Amps. 

ON  

OFF  

OFF  

10 Amps. 

OFF  

ON  

OFF  

6 Amps. 

ON  

ON  

OFF  

Disabled --- 

--- 

ON 

 

120V Models 

 

DIP switch B 

SW1 

SW2 

SW3 

50 Amps. 

--- 

--- 

ON  

30 Amps. 

OFF  

OFF  

OFF  

25 Amps. 

ON  

OFF  

OFF  

15 Amps. 

OFF  

ON  

OFF  

10 Amps. 

ON  

ON  

OFF  

Please turn page 

NOTES

  

 

The Mass Combi can also be operated without any remote control panel connected;  

 

When using the Masterlink MICC panel, it is not possible to use the APC remote panel.  

This sheet describes the installation, initial settings and daily use of the Masterlink MICC remote 
control panel in combination with the Mass Combi. Please review the entire manual of both the 
Mass Combi and the Masterlink MICC for additional features and connections and to ensure best 
performance and years of trouble-free service. 

INSTALLATION 

Install the Mass Combi as described in the manual of the Mass Combi; 

Install the Masterlink MICC as described in the manual of the Masterlink MICC, but do not connect 
the modular communication cables; 

Connect the Masterlink MICC to the Mass Combi as indicated below, using the modular 
communication cable. 

RJ12 modular communication 
cable cross wired 

Connection compartment of the Mass Combi 

Rear view of the 

Masterlink MICC

 panel 

GEN / SHORE

POWER

SHORT BREAK 

L

N

PE

SHORT BREAK

L

N

PE

L

N

PE

INPUT

AC CONNECTIONS 

PUSH TO RESET

OUTPUT

OUTPUT

25A

50A MAX 

50A MAX 

25A MAX 

MASTERBUS

REMOTE

QRS232

+5A

NEG

TEMP. SENS

BATTERY

1 - 2 - 3 - 4

POS

+

QRS232 port 

NOTE: If two Mass Combi’s are installed in parallel, the 
Masterlink MICC must be connected to the QRS232 port of the 
Mass Combi that is configured as “Master”. 

WARNING 

During installation the Safety Guidelines & Measures are applicable at all times. See chapter 2 of 
the manual of the Mass Combi and the Masterlink MICC. 

Reviews: