Use of the Masterlink MICC with the Mass Combi
Mastervolt International B.V,
P.O.Box 22947, NL-1100 DK Amsterdam, The Netherlands.
Tel.:
+31-20-3422100
Email:
Web:
www.mastervolt.com v1.2 071206EN
5
INITIAL DIP-SWITCH SETTINGS AT THE MASS COMBI
Power sharing level
The Power Sharing Level can be adjusted by means of the Masterlink MICC (see step 7). The absolute maximum
level for this setting can be fixed by means of DIP-switches B SW1, SW2 and SW3.
See sections 3.3.3 and 6.2.1 of the user’s manual of the Mass Combi for more information.
230V Models
DIP switch B
SW1
SW2
SW3
25 Amps.
OFF
OFF
OFF
16 Amps.
ON
OFF
OFF
10 Amps.
OFF
ON
OFF
6 Amps.
ON
ON
OFF
Disabled ---
---
ON
120V Models
DIP switch B
SW1
SW2
SW3
50 Amps.
---
---
ON
30 Amps.
OFF
OFF
OFF
25 Amps.
ON
OFF
OFF
15 Amps.
OFF
ON
OFF
10 Amps.
ON
ON
OFF
Please turn page
2
NOTES
•
The Mass Combi can also be operated without any remote control panel connected;
•
When using the Masterlink MICC panel, it is not possible to use the APC remote panel.
1
This sheet describes the installation, initial settings and daily use of the Masterlink MICC remote
control panel in combination with the Mass Combi. Please review the entire manual of both the
Mass Combi and the Masterlink MICC for additional features and connections and to ensure best
performance and years of trouble-free service.
4
INSTALLATION
1
Install the Mass Combi as described in the manual of the Mass Combi;
2
Install the Masterlink MICC as described in the manual of the Masterlink MICC, but do not connect
the modular communication cables;
3
Connect the Masterlink MICC to the Mass Combi as indicated below, using the modular
communication cable.
RJ12 modular communication
cable cross wired
Connection compartment of the Mass Combi
Rear view of the
Masterlink MICC
panel
GEN / SHORE
POWER
SHORT BREAK
L
N
PE
SHORT BREAK
L
N
PE
L
N
PE
INPUT
AC CONNECTIONS
PUSH TO RESET
OUTPUT
OUTPUT
25A
50A MAX
50A MAX
25A MAX
MASTERBUS
REMOTE
QRS232
+5A
NEG
TEMP. SENS
BATTERY
1 - 2 - 3 - 4
POS
+
QRS232 port
NOTE: If two Mass Combi’s are installed in parallel, the
Masterlink MICC must be connected to the QRS232 port of the
Mass Combi that is configured as “Master”.
3
WARNING
During installation the Safety Guidelines & Measures are applicable at all times. See chapter 2 of
the manual of the Mass Combi and the Masterlink MICC.