background image

 

3. Additional Placement Information 

   
MasterGuard recommends complete home fire protection, achieved by installing a combination of 
Smoke and Heat Alarms in their appropriate locations throughout the house.  Do not install Heat 
Alarms in bedrooms without accompanying Smoke Alarms. 
 
Heat from a fire rises to the ceiling, spreads out across the ceiling surface and begins to bank 
down from the ceiling. The corner where the ceiling and the wall meet is an air space into which 
heat has difficulty penetrating.  This is dead air space!  Alarms must not be placed in the dead air 
space.  (See drawing below) 
 

• 

Install the Heat Alarm on the ceiling, as close to the center of the room as possible.  If this is not 
practical, mount the alarm no closer than 4 inches from a wall or corner.  If possible the alarm 
should be moved in the direction of potential fire sources. Do not install on ceilings that have 
radiant heating.  (See drawing below) 

 

• 

If mounting on the ceiling is not an option, and if local codes allow wall mounting, install the 
Heat Alarm on the wall no closer than 4 inches but no more than 12 inches from a ceiling/wall 
intersection.   (See drawing below) 

 

• 

Install Heat Alarms on peaked, cathedral, or gabled ceilings within 3 feet from the highest point 
(measured horizontally). 

 

• 

DO NOT install Heat Alarms within 3 feet of heating and cooling supply vents. 

 

• 

DO NOT install alarms behind drapes, doors or other objects that will impede airflow. 

 

• 

Heat Alarms shall be installed within the strict limitation of their listed spacing in rooms with 
smooth, level ceilings.  The QR50 has a Space Rating of 50 feet. 

 

• 

The maximum installed spacing shall be 50 percent of the listed spacing in the uphill direction 
from a detector in a room with a ceiling slope greater than one-foot rise per 8 feet horizontally. 

 

• 

On level ceilings with open joists or beams, all alarms shall be mounted on the bottom of such 
joists or beams.  (See drawing below) 

 

• 

Reduced spacing may be required due to structural characteristics of the protected area, 
possible drafts, or other conditions affecting detector operation.  Alarms installed on a joisted 
ceiling shall have their smooth ceiling spacing reduced where this spacing is measured at right 
angles to solid joists; in the case of Heat Alarms, this spacing shall not exceed one-half of the 
listed spacing. 

 
Additional Placements Guides: 

 

 

AVOID DEAD AIR SPACES 

WALL

DEAD AIR SPACE – DO NOT USE 

4 IN.

TOP OF ALARM

ACCEPTABLE IN

THIS AREA

4 IN.

ACCEPTABLE 

DO NOT INSTALL 
INBETWEEN JOISTS
OR RAFTERS 

12 IN.

ACCEPTABLE 
ALARM PLACEMENT  

CEILING 

 
 
 
 
 
 
 
 
 

OPEN JOISTS, BEAMS OR RAFTERS 

 

DO NOT USE 

 
 
 
 

 

4

Summary of Contents for QR-50

Page 1: ...MasterGuard COVER ART PHOTOGRAPH OF ALARM Heat Activated Fire Alarm Model QR 50 Owner s Manual ...

Page 2: ...ate Prov Zip PC _______________________________________________________________ Telephone Number _______________________________________________________________ Sales Representative _______________________________________________________________ Address City State Prov Zip PC _______________________________________________________________ Telephone Number NOTICE Be sure the installer tests each al...

Page 3: ...ld locations not typically suitable for a traditional smoke alarm Space rating of 50 feet Alarm audibility and functionality can be tested by simply removing the Heat Sensor 2 Proper Placement of the Heat Alarm The QR 50 Heat Alarm adds an extra level of fire protection to most household settings Although the primary form of fire warning is properly located and maintained smoke alarms complete fir...

Page 4: ...r gabled ceilings within 3 feet from the highest point measured horizontally DO NOT install Heat Alarms within 3 feet of heating and cooling supply vents DO NOT install alarms behind drapes doors or other objects that will impede airflow Heat Alarms shall be installed within the strict limitation of their listed spacing in rooms with smooth level ceilings The QR50 has a Space Rating of 50 feet The...

Page 5: ...lled as follows 1 In all sleeping rooms Exception Smoke alarms shall not be required in sleeping rooms in existing one and two family dwelling units 2 Outside each separate sleeping area in the immediate vicinity of the sleeping rooms 3 On each level of the dwelling unit including basements Exception In existing one and two family dwelling units approved smoke alarms powered by batteries shall be ...

Page 6: ...e center of the front face of the alarm should now be free to be depressed to the level of the chrome snap If not double check to be sure the alarm is fully wound While holding the Heat Alarm in your left hand insert the winding wrench located in pocket on back of the alarm into the slot and wind the alarm in the clockwise direction until it will advance no further 38 turns Hold this position 5 Ho...

Page 7: ...Check attic alarms periodically to ensure the alarm has not been triggered Problem How do I know if the alarm has been activated when we were out of the house Solution When the Heat Alarm has been activated a round bright orange warning becomes visible in the center of the Heat Sensor If the entire Heat Sensor has been removed a larger bright orange warning label is visible If either warning is vi...

Page 8: ...es Use the stairs Never the elevator during a fire If exits are locked or blocked report the problem to your building s management Escape Tips Close doors behind you as you escape to slow the spread of fire and smoke If you have to escape through smoke crawl on your hands and knees keeping your head one to two feet above the floor where the air will be cleanest Never open closed doors before testi...

Page 9: ...in the house Do you have the chimney cleaned and checked regularly For safety against chimney and other sparks is roof covering fire retardant GOOD HOUSEKEEPING Do you keep rubbish cleaned out Is paint kept in tightly closed metal containers Are flammable liquids stored in safety cans and kept away from heat and children Have you made it a rule never to use flammable liquids for cleaning clothes o...

Page 10: ...ictated by state or local laws accompanied by a completed activation report and verification in the form of a newspaper report and or site photo to qualify for this half price replacement This replacement specifically excludes units that have been damaged by abuse gross neglect or disassembly CALIFORNIA DEPARTMENT OF FORESTRY FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING DIVISI...

Page 11: ... not modify any implied warranty of the alarm to the original retail purchaser EXCEPT THAT ANY SUCH IMPLIED WARRANTY SHALL BE LIMITED TO 25 YEARS FROM THE DATE OF DELIVERY TO THE ORIGINAL RETAIL PURCHASER YOUR SOLE AND EXCLUSIVE REMEDY AGAINST MASTERGUARD L P SHALL BE FOR THE REPAIR OR REPLACEMENT OF ANY PART OF THE ALARM WHICH SHALL BE DEFECTIVE IN MATERIAL OR WORKMANSHIP AS PROVIDED HEREIN NO OT...

Page 12: ...BACK COVER MASTERGUARD L P 801 HAMMOND STREET SUITE 200 COPPELL TEXAS 75019 PHONE 972 393 1700 FAX 972 393 1701 www masterguard com 90 1024 00 12 ...

Reviews: