background image

1.  Run a minimum of 16 gauge, 3-conductor cable, plus ground 

(4 wires) to the first alarm junction box from a power supply 
and between all smoke alarms that are to be connected together.  
Use U.L. listed Class 1 wire.

2.  Make wire connections to the supplied plug-in connector as 

follows:  black to black, white to white, 3rd conductor to the 
red-yellow wire.  The red-yellow wire should be stripped to 
make this connection.  Connect ground wire between metal 
outlet boxes.

NOTES ON TANDEM INTERCONNECTING MODELS

DO NOT connect MasterGuard Smoke Alarms to other 

manufacturers' smoke alarms.

No more than 6 MasterGuard Models 380LS-C may be connected 

in tandem.

All units connected in tandem MUST get their power from the 

same circuit, that is, all smoke alarms in tandem must be 
controlled by the same fuse or circuit breaker.

After installation to verify proper working conditions all horns 

must sound in this system.

IMPORTANT WARNING: 

Failure to observe any of the 

conditions set forth may cause system malfunction and damage to
the smoke alarm.

MOUNTING:  PLATE & SMOKE
ALARM

1.  Lace the connector through the provided mounting plate and 

secure the plate to the junction box.
NOTE:  Mounting plate is marked "THIS SIDE OUT" and slotted 

for proper positioning.

Figure 10

Figure 11

Pg. 3-5

Figure 9

IMPORTANT WARNING:

Failure to observe any of the conditions set forth may cause 

system malfunction and damage to the alarm.

CHECKOUT & TROUBLESHOOTING

1.  Turn test knob to the NORMAL position and supply house power 

to the smoke alarm.  The red indicator should flash every 15-30 
seconds, showing that the smoke alarm is operating properly.

2.  If red light is not flashing or the green LED is not on:

a.  Check that the battery is installed.
b.  Check to see that the wire connector is fully seated.
c.   If the power and wiring check out, but the red light does not 

flash or the green LED is still off, return the device to the 
manufacturer.   See TO RETURN A SMOKE ALARM.

3.  Testing with the Test Knob:

a.  Rotate the test knob counter-clockwise to the TEST 1 position 

and wait up to 20 seconds for the alarm to sound.  If the 
device does not sound after 20 seconds, return the smoke 
alarm for service.

b.  After successfully testing smoke alarm, return test knob to 

NORMAL (non-test) position and wait 20 seconds for the 
smoke alarm to stop sounding.

Figure 14

c.  To test smoke alarm for high sensitivity, turn test knob 

clockwise to TEST 2 position.  Alarm should remain silent.  
Return knob back to the normal position.  If your smoke alarm 
sounds during this test it means the device's sensitivity has 
become too high and may cause false alarms.  This could        
mean your smoke alarm is dirty and should be cleaned as 
described in the maintenance procedure below.  If the smoke   
alarm continues to alarm for TEST 2 position following 
cleaning return it to MasterGuard for service.

d.  To check for proper smoke entry into your smoke alarm's 

sensing chamber.  MasterGuard recommends using the

Home Safeguard Smoke Alarm spray.  

This test should be 

performed once a year and should be sprayed from a 
distance no closer than 12 inches from smoke alarm.

MAINTENANCE

After your smoke alarm has been in operation for a period of time

or if it was installed prior to the completion of all building 
construction, your smoke alarm may have become more sensitive
due to dirt build-up in the smoke alarm's optic sensing chamber
which could cause nuisance alarms or could cause activation from
small amounts of smoke build-up.

If this should occur, following this simple washing procedure will

restore your smoke alarm back to its original condition.

For further information, regarding frequency of cleaning and

testing, refer to NFPA 72, NFPA, Batterymarch Park, Quincy, MA

02269.

IMPORTANT: Failure to follow full cleaning instructions

could result in damage to this smoke alarm.  DO NOT remove
all alarms at the same time for cleaning.

1.  Rotate the smoke alarm counter-clockwise to remove it from its 

mounting plate.

2.  Unplug the wire connector from the smoke alarm and remove the 

battery.

2.  Plug the wire connector into the smoke alarm base.
3.  Place the smoke alarm up to the mounting plate, rotating it to 

about 10:00 o'clock then rotate it clockwise to 12:00.  It should 
"snap-lock" firmly into place.  Keep the alarm parallel to the 
mounting plate so upper and lower tabs on the plate seat into the 
smoke alarm.

Reviews: