SERVICE PROCEDURES

Continued

PUMP ROTOR

(Procedure if Rotor is Binding)

1. Remove upper shell (see page 7).

2. Remove 

 lter end cover screws using5/16” nut-driver.

3. Remove 

 lter end cover and air 

 lters.

4.Remove pump plate screws using 5/16”nut-driver.

5. Remove pump plate.

6. Remove rotor, insert, and blades.

7. Check for debris in pump. If debris is found, blow out with 

compressed air.

8.Install insert and rotor.

9. Check gap on rotor. Adjust to .076/.101 mm (.003”/.004”) if 

needed (see Figure 25).

Note:

  Rotate rotor one full turn to ensure the gap is .076/.101 

mm (.003”/.004”) at tightest position. Adjust if needed.

10.Install blades, pump plate, air 

 lters and 

 lter end cover.

11.Replace fan guard and upper shell.

12.Adjust pump pressure (see page 8).

Note:

 If rotor is still binding, proceed asfollows.

13.Perform steps 1 through 6 above.

14.Place 

 ne grade sandpaper (600 grit) on 

 at surface. Sand 

rotor lightly in “

 gure 8” motion four times (see Figure 26)

15.Reinstall insert and rotor.

16.Perform steps 10 through 12 above.

A.

B.

C.

D.

E.

F.

G.

H.

A.

B.

C.

D.

E.

F.

G.

H.

SERVICE PROCEDURES

A.

B.

C.

A.

A

. gap adjusting 

screw

B

. .076/.101 mm 

(.003”/.004”) Gap 

Measured With 

Feeler Gauge

C

. Blade

Figure 25 – Gap adjusting screw locations.

A.

A

. sandpaper

Figure 26 – Sanding rotor.

A

.Blade, 

B

.Pump plate, 

C

.Air intake 

 lter, 

D

.Filter end cover, 

E

.Fan guard, 

F

.Air output 

 lter, 

G

.Rotor, 

H

.Insert.

Figure 24 – Rotor location, 100.000 and 150.000 Btu/Hr.

Figure 23 – Rotor location, 35.000 btu/Hr, 64.000 btu/Hr and 

70.000 Btu/Hr.

A

.Blade, 

B

.Pump plate, 

C

.Air intake 

 lter, 

D

.Filter end cover, 

E

.Fan guard, 

F

.Air output 

 lter, 

G

.Rotor, 

H

.Insert.

Summary of Contents for B 65 CEL

Page 1: ...DUELS AIR FORC DE TRAGBARE HOCHDRUCK EISSLUFTTURBINEN NL VERPLAATSBARE HETELUCHTKANONNEN IT GENERATORE D ARIA CALDA A RISCALDAMENTO DIRETTO ES CALENTADORES PORTATILES DE AIRE FORZADO SV PORTABEL V RME...

Page 2: ...L MAX 10 kW 35 000 Btu h 18 5 kW 64 000 Btu h 20 kW 70 000 Btu h 29 kW 100 000 Btu h 44 kW 150 000 Btu h 280 m h 400 m h 400 m h 800 m h 900 m h 0 86 Kg h 1 55 Kg h 1 7 Kg h 2 45 Kg h 3 72 Kg h DIESEL...

Page 3: ...DULE 5 TROUBLESHOOTING 5 SERVICE PROCEDURES 6 ACCESSORIES 12 WARRANTY INFORMATION 12 Heater Sizes 10 18 5 20 29 44 kW Models 35 000 64 000 70 000 100 000 150 000 Btu Hr IMPORTANT Read and understand t...

Page 4: ...uel storage shall be located a minimum of 762cm 25 feet from heaters torches welding equipment and similar sources of ignition exception the fuel reservoir integral with the heater unit g Whenever pos...

Page 5: ...u Hr models only These models are furnished with wheels and handles Wheels handles and the mounting hardware are found in the shipping carton Tools Needed Medium Phillips Screwdriver 3 8 Open or Adjus...

Page 6: ...er N Fuel Filter O Nozzle P Fuel Tank Q Air For Fuel System R Air For Combustion And Heating S Fuel OPERATION WARNING Review and understand the warnings in the Safety Information section page 2 They a...

Page 7: ...plugged in operating or hot Severe burns and electrical shock can occur HEATER WITH FUSED OR NON FUSED IGNITION CONTROL ASSEMBLY ATTENTION The ignition control has built in protection against current...

Page 8: ...ing and connections See Wiring Diagram page 17 3 Check ignitor wiring If no problems are found replace ignitor see page 7 ON OFF switch light comes on when switch is turned to the ON Position but turn...

Page 9: ...in lbs Do not over torque 10 Replace combustion chamber 11 Route the ignitor wires back down through the hole in the lower shell Connect wires to the ignition control assembly 12 Replace side cover se...

Page 10: ...NOZZLE ASSEMBLY 1 Remove upper shell see page 7 2 Remove fan see page 11 3 Remove fuel and air line hoses from nozzle assembly see Figure 17 18 or 19 4 Turn nozzle assembly 1 4 turn to left and pull...

Page 11: ...ses are not to be touching photocell bracket For 150 000 Btu Hr model heater route air and fuel lines approximately as shown in Figure 19 Note Hoses are not to be touching photocell bracket 6 Replace...

Page 12: ...and upper shell 12 Adjust pump pressure see page 8 Note If rotor is still binding proceed asfollows 13 Perform steps 1 through 6 above 14 Place ne grade sandpaper 600 grit on at surface Sand rotor lig...

Page 13: ...embly CAUTION Ignition control assembly contains electrostatic components Handle the assembly by the edges of the printed circuit board Do not touch any of the quick connect terminals or electronic co...

Page 14: ...anted only for the remainder of this Warranty as if such parts were original components of said Product DESA ITALIA MAKES NOOTHER EXPRESS WARRANTY TO THE EXTENT PERMITTED BY LAW DESA ITALIA MAKES NO I...

Reviews: