7
ELECTRICAL CONNECTION
This appliance complies with EU requirements for radio electrical suppression in accordane
with directive Standard 82/499/CEE.
The freezer should be plugged into an outlet that has the correct voltage and frequency.
These data are specified on the lable located on the back of the freezer.
The standard voltage in the US is 115V/60Hz allowed voltage var/- 10%. The above
variations may cause damage to the freezer and if so, the factory warranty would be invalid.
Protection measures must be taken in addition to using the freezer according to applicable
electrical codes, even in the case of replacement of an existing freezer that had no been
worth the extra protection needed. The aim of this additional protection is to protect users
from dangerous electrical shok in case of failures.
-
To protect your electrical, use a load center of 25Amps at 115Volts.
-
If not possible to obtain the nominal voltage indicated by a variation of +/- 10% (power
supply instability), install a voltage regulator (1500VA).
-
Connet the equipment into a dedicated outlet.
-
The installation must be made only if the outlet has the nominal output voltage with a
tol/- 10%. The caliber of the installation cables must follow the below table:
Distance
Callber
(mm²)
115V
220V
2,5
(12 AWG)
-
UP
91 METERS
4,0
(10 AWG)
UP
19 METERS
92 A145
METERS
6,0
(8 AWG)
20 A 30
METERS
146 A 218
METERS
10,0
(6 AWG)
31 A 48
METERS
-
* The replacement of power cords should be performed by an authorized service provider*