3. Electrical Characteristics & Test Condition

Testing Conditions: Ambient Temperature: 25±5ºC; Huminity: 45%~75%.

www.masterbattery.es

03

NO.

Items

Capacity

2

3

4

-20°C

Condition

Internal Impedance 

1

≤30mΩ

Test the internal resistance of 50% SOC battery pack 
with 1 kHz AC internal resistance test instrument. 

Criterion

Rest for 1 hour after fully charged, then discharge 
with 0.33C current until the battery reaches the 
discharge cutoff voltage. Repeat above process for 
three times, if the discharge time is not less than 180 
minutes, you can stop and define the Discharging 
current*time value (Ah) as battery capacity. 

≥98Ah

Discharge 
Temperature 
Characteristics

At 25±5°C discharge the battery with the current of 
0.33C to the cut-off voltage and record charge 
capacity. Store the battery at various temperatures 
for 2h and discharge the battery with 0.33C to the 
cut-off voltage.

0°C

25°C

55°C

70%

80%

100%

95%

Charge the battery to full capacity and store it for 28 
days, and then discharge it with 0.33C to the cut-off 
voltage.

Charge Retention 
ability

Remain capacity
≥90%

Short circuit protection

/

Not allowed.

Charging with this current for more than 0.5h and the 
added temperature of battery pack less than 20°C.

MAX charge Current

80A

5

Discharging with this current for more than 0.5h and 
the added temperature of battery pack less than 
35°C.

MAX discharge Current

100A

Discharge with the current of 0.5C until it can’t 
discharge, and then rest it for 1h. Charge the battery 
following CC (0.33C)/CV (14.6V) mode to full capacity, 
and then rest it for 1h. Repeat above process until full 
charged capacity is no more than 80% of normal 
value. Accumulated times is defined as cycle life.

6

Cycle life (DOD%100)

≥2500 cycles

7

8