background image

5. 

 

 

 

 

 

 

 

6. 

 

 
 
 

7. 

 
 
 
 

8.

 

LCD display 

 

 

 

 

 

 

 

“ V

Hz” jack   

This  is  positive  input  terminal  for  volt, 
resistance,  diode,  capacitance  frequency, 
ADP  and  Continuity  test.  Connection  is 
made to it using the red test lead. 

“COM” jack   

This  is  negative  (ground)  input  terminal  for 
all measurements except current.   

Connection  is  made  to  it  using  the  black 
test lead.

 

RANGE button 

Press this button to select auto and manual 
range.  When  a  function  with  auto  and 
manual mode is selected, the meter enters

 

 6 

 

 

 

 

 

 

 

9. 

 

 

 

10. 

 
 
 
 
 
 
 

11.

 

 

 

autorange  at  first.  To  change  to  manual 
range, push this button once. 

When the meter operates in manual ranging 
mode,  push  this  button  to  change  range  to 
the higher one and hold this button for more 
than 3 seconds to return to auto range mode 

FUNC. button 

In 

           

 

range, press this button to select 

 

or        or 

 

function.  Different  symbol  of 

function will appear on the LCD. 

           

button

 

Press the button is used to turn the backlight 
on. Press the button again is used to turn the 
backlight  off.  To  turn  the  backlight  on  again, 
just press it once more. 
When  measuring  current,  press  the  button 
the  radius  lamp  near  the  clamp  is  lighted  at 
one time. 

Rigger 

Press  the  lever  to  open  the  transformer. 
When  the  lever  is  released,  the  jaws  will 
close again.

 

 7 

 

Summary of Contents for MS2026R

Page 1: ...d hand held current clamps with double insulation overvoltage category 1000V CAT II 600V CAT III and pollution 2 This meter complies with the requirements of the following European Community Directives 89 336 EEC Electromagnetic Compatibility and 73 23 EEC Low Voltage as amended by 93 68 EEC CE Marking However electrical noise or intense electromag netic fields in the vicinity of the equipment may...

Page 2: ...and test leads for 2 any sign of damage or abnormality before every use If any abnormal conditions exist i e broken test leads cracked cases display not reading etc do not attempt to take any measurements Do not expose the instrument to direct sunlight extreme temperature or moisture Never ground yourself when taking electrical measurements Keep your body isolated from ground by using dry clothing...

Page 3: ...inuity Test with battery operated There is the AC measurement to be RMS or TRUE RMS about the meter It is chosen as user buy 4 Otherwise there is a radius lamp near the clamp It is lighted in measuring current PANEL DESCRIPTION 1 2 3 Transformer jaws Pick up the AC current flowing through the conductor Rotary switch Rotary switch is used to select functions HOLD button When this button is pushed t...

Page 4: ... to manual range push this button once When the meter operates in manual ranging mode push this button to change range to the higher one and hold this button for more than 3 seconds to return to auto range mode FUNC button In range press this button to select or or function Different symbol of function will appear on the LCD button Press the button is used to turn the backlight on Press the button...

Page 5: ... touch any electrical conductors 3 4 The polarity of the red lead connection will be indicated along with the voltage value Read the measure result from the display AC VOLTAGE MEASUREMENT 1 Insert the black and red test leads into the COM and V Hz input terminals respectively 2 Set rotary switch at desired V position Connect the test lead tips in parallel with the circuit to be measured Be careful...

Page 6: ...range indication OL will be display 10 2 When checking in circuit resistance be sure the circuit under test has all power removed and that all capacitors have been discharged fully CONTINUITY TESTING 1 2 3 4 Insert the black and red test leads into the COM and V Hz input terminals respectively Set rotary switch at desired position Push FUNC button to select Connect the test lead tips in parallel w...

Page 7: ...witch to Hz position Connect the test leads across the source or load under measurement The polarity of the red lead connection is positive 12 4 Read the measure result from the display NOTE 1 2 The signal amplitude must also be greater than the sensitivity level Determine that the amplitude level of the signal to be measured is not greater than the input voltage limit 250V DC AC rms ADP MEASUREME...

Page 8: ...5mm 86mm 32mm Weight Approx 330g Operating 5 to 35 Storage temperature 10 to 50 14 DC VOLTAGE Range Resolution Accuracy 6V 1mV 0 8 of rdg 5 digits 60V 10mV 600V 0 1V 1000V 1V 1 0 of rdg 2 digits Input Impedance 10M Overload Protection 1000V DC or 700V AC RMS AC VOLTAGE Range Resolution Accuracy 6V 1mV 1 2 of rdg 5 digits 60V 10mV 600V 0 1V 700V 1V Input Impedance 10M Frequency range 40Hz to 400Hz ...

Page 9: ...0uF 1uF Overload Protection 250V dc or rms ac for all ranges 16 FREQUENCY Range Resolution Accuracy 40Hz 1Hz 0 1 of rdg 1digit 600Hz 1Hz 6kHz 1Hz 60kHz 10Hz 100kHz 0 1kHz Measurement range 1V to 10V rms 40Hz to 100kHz ADP Range Resolution Accuracy 600mV 0 1mV 3 0 of rdg 5 digits AUDIBLE CONTINUITY AND DIODE Range Description If continuity exists about less than 40 built in buzzer will sound Show t...

Page 10: ...Use the following procedure to replacing the battery 1 2 The Rotary Switch is used to select OFF Disconnect test leads from any live source and remove the test leads from the input terminals 18 3 4 5 Remove screws on the battery cover and open the cover Remove the exhausted battery and replace with three new 1 5V size AAA batteries Place battery cover and secure by a screw CAUTION Using this appli...

Page 11: ...OPERATOR S INSTRUCTION MANUAL CLAMP METER HYS005013 A1 ...

Reviews: