Masoneilan SVI II ESD Installation and Maintenance Manual
=
|
217
Appendix I. Determining an SVI Positioner
Compliance Voltage in a Control System
This discussion explains how to determine compliance voltage for an SVI positioner. It applies to
the SVI II AP, SVI II ESD, SVI II APN and SVi1000.
A definition of compliance voltage is: The voltage that must be available at the control system
output in order to drive the control current through the SVI II AP and all the resistive devices in
series with it.
Measuring the voltage across the SVI II AP terminals doesn't give the true available system
compliance voltage as the positioner self-regulates voltage as current flows through it.
Additionally, it also doesn't confirm what system voltage is available under load conditions.
Therefore, if compliance testing needs to be done, it is best done before installation.
Use a 1K potentiometer as this is the maximum for most analog output cards and as at 20 mA
this equals 20 VDC, which is a sufficient maximum.
Compliance Test Setup
1. Configure a test setup as in Figure 94.
Figure 94 Compliance Voltage Test Setup
Summary of Contents for SVI II ESD
Page 4: ...This page intentionally left blank ...
Page 10: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 100: ...This page intentionally left blank ...
Page 120: ...This page intentionally left blank ...
Page 126: ...This page intentionally left blank ...
Page 160: ...This page intentionally left blank ...
Page 194: ...This page intentionally left blank ...
Page 200: ...This page intentionally left blank ...
Page 204: ...This page intentionally left blank ...
Page 206: ...This page intentionally left blank ...
Page 208: ...This page intentionally left blank ...