Calibration Menu
The Calibration menu shown in Figure 64 provides access to all of the calibration functions for
SVI II ESD. If a change is made in the Air-To-Open/Air-To-Close configuration option, or if you
move SVI II ESD to a different valve, or make any change to the valve position linkage, you
must run the find STOPS calibration again.
Figure 64 CALIBration Menu
SETUP
+
+
+
CALIBration Menu
STOPS
*
*
RUNNING
STOP OP
*
TUNE
*
*
*
FAILURE
STEP 1/3
STEP 2/3
+/-
*
CALIB
<VALUE>
* - +
<VALUE>
+/-
*
*
STEP 3/3
If a calibration tuning error occurs
FAILURE
message appears. Press
*
briefly and
automatically return to TUNE starting point.
FAILURE
If a calibration stops error occurs
FAILURE
message appears. Press
*
briefly and
automatically return to STOPS starting point.
+
*
CALIB
CAUTION: These functions stroke the valve over its full range of travel.
Do not perform while the valve is controlling the process.
TUNE OK
See Figure 62 on
page 107 for full menu
Summary of Contents for SVI II ESD
Page 4: ...This page intentionally left blank ...
Page 10: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 100: ...This page intentionally left blank ...
Page 120: ...This page intentionally left blank ...
Page 126: ...This page intentionally left blank ...
Page 160: ...This page intentionally left blank ...
Page 194: ...This page intentionally left blank ...
Page 200: ...This page intentionally left blank ...
Page 204: ...This page intentionally left blank ...
Page 206: ...This page intentionally left blank ...
Page 208: ...This page intentionally left blank ...