TT7S00-HR 

 

CALIBRATION 

 

Configuration of the transmitter should always 
be carried out before calibration. 

 
It is suggested that the calibration is checked at 
least once a year. When a new calibration is 
necessary, use calibration instruments with an 
accuracy of at least 5 times better than wanted 
accuracy for the calibration.  
 
The transmitter is polarity protected and will not be 
damaged by connecting the power supply with the 
wrong polarity, but the output will be 0 mA. 
1.  Connect input and output signals according to 
figureIn connections. Apply an input signal to give an 
output of  approximate 12 mA. 
2.  If the output signal has stabilized after 15 
minutes, The transmitter is ready for calibration. 
3.  Apply Temp. input corresponding to desired 
minimum input signal. 
4. Calibrate Zero-potentiometer until Iout= 4.00 mA. 
5. Apply Temp. input corresponding to desired 
maximum input signal.  
6.  Calibrate Span-potentiometer until Iout= 20.00   
mA. 
7.  Repeat steps 3 to 6 until readings converge. 
8.  Secure the potentiometer with lacquer. 
Calibration is completed. 

 

Subject to recalibrate if range change

 

 

O

RDERING 

C

ODE

 

Ordering Code

 

Model

 

Range Setting

 

TT7S00-HR

 

X

 

 

 

 

S

 

Standard without Range Setting & 
without calibration certificate 

 

M

 

Customer Specified Range 
Setting & Calibration Certificate 
(Option) 

 

Specify Input Range at the time of Ordering for 
range setting option 
 

TT7S00-HR-X-XX-XXX  

 

Where, 

XX: 

Zero Indication

 

XXX: 

Span Indication 

 

Example: 
For input range of 

-

50 to 200 ˚C

 

A

CCESSORIES

 

 Mounting Kit  

   

Head Mounting:  

m-MK-FH-00-1

  

Rail Mounting Kit:  

m-MK-RC-00-1

 

 

T

ROUBLE 

S

HOOTING

 

 

Unit Not Turning ON? 

The problem can be bad connection. 

First check, connections as per sticker details 

Check Jumper selection if they are proper or not? 

 

 

Unstable/Vague Reading 

 Check for loose connections. 

 The reason can be reverse input connections 

 

 

Output not matching with the expected value 

 
It  is  a  normal  tendency  to  doubt  the  instrument 
performance,  when  the  Output  is  not  matching  the 
expected  value.  Kindly  make  sure  that  the  output  is 
really  incorrect  with  respect  to  input  signal,  before 
attempting any re-calibration. 

Account  for  measuring  instrument’s  inaccuracies, 
lead  errors  and  calibration  errors.  Care  must  be 
taken when measuring Output signal.  

Use  calibrating  instrument  of  accuracy  better  than 
0.1%  for  purpose  of  calibration.  If  the  signal  is  still 
found  to  be  out  of  tolerance,  calibration  should  be 
required. 

 

 

Zero: 

-

50˚C

 

Span: 

250˚C 

 

TT7S00-HR-S-(-50)-250 

 

Do  not  install  the  unit  where  it  is  subjected  to 
continuous vibration. 
Do not subject the unit to physical impact.    