Doc. Ref No.: mtt/om/10
Issue No.:10
TT7S Series
I
NSTALLATION
Din Rail Mounting:
The unit can be snapped onto all DIN rails (35mm)
According to EN60715.The device must be
mounted horizontally (Supply terminal blocks
facing upper wards)
The housing is mounted on the DIN rail by
swiveling it into place.
Removal:
Release the snap-on catch using a
screwdriver and then detach the module
from the bottom edge of the DIN Rail.
Head Mounting:
The Unit can be mounted with 2 screws
given with the sensor head as shown in
figure with screw driver.
TT7S11, TT7S10
TT7S10-H
m a s i b us
TT7S 11
24V
DC
+
O/P
ON
5
6
+
7
8
V+
2
3
4
V-
C+
PGM.
PORT
1
m a s i b u s
TT7S10
1
2
3
4
5
6
N C
NC
A
CCESSORIES
Mounting Kit
Head Mounting: m-MK-FH-00-1 (Only
For TT7S10-H)
Rail Mounting Kit: m-MK-RC-10-1
(Only for TT7S10-H)
Cable Accessories
sr.
No.
Description of
Accessories
Part No.
Qty
1
Configuration cable
For TT7S10&TT7S10-H
m-cb-5-4-7-
10-0-0-1-1
01
O
RDERING
C
ODE
Model
Transmitter Type
Input
Output
Isolation
Level
TT7S
10
Loop-Powered Din
Rail Mount
1
E
1
4-
20mA
1
1.5KVAC
11
Aux-Powered Din
Rail Mount
2
J
2*
0-
20mA
2
1KVAC
10-
H
Loop-Powered
Head Mount
3
K
3*
1-5V
4
T
4*
0-
10V
5
B
5*
0-5V
6
R
7
S
8
N
9
Pt-100
3 Wire
A
#
Pt-100
4 Wire
F
#
0-5V
G
#
0-10V
H
0-
500mV
I
0-
2500
Ω
U
0-
75mV
W
#
0-
5000
Ω
*Available in Aux Powered model TT7S11 Only
# Available in Loop Powered model TT7S10 and
TT7S10-H Only
T
ROUBLE
S
HOOTING
Unit Not Turning ON?
TT7S10&TT7S10-H -
If transmitter is not
delivering loop current, check the circuit
from Power supply, two wire transmitter &
receiving device. If still transmitter is not
delivering loop current, check the supply
connections and polarity of 24Vdc terminals.
TT7S11
- If RED LED at the front side is not
turned “ON”, the device is not getting
sufficient supply or the connections are not
as per terminal details.
Output not matching with expected
value?
Make sure the load on output of device is as
per specification criteria.
Make sure the input selection using DIP
Switch is as per selection Table.
Communication with PC is not proper
(for all models)
The reason can be in pc driver is not
installed, Comport is not proper selected, Or
connection from PC to unit is loose.