background image

 

 

 

                                                                                                                                      Doc. Ref No.: m15/om/101 

 

                                                                                                                                         

Issue No.:01

 

 

1 | 

P a g e

 

 

MAS-AO-08-D                      

 

 
 
 

 

 
 

 

A

PPLICATION

 

 

Eliminate Ground Loop problems

 

 

Protect Expensive control systems against Field Faults

 

 

Isolate and Translate System Signals

 

 

Field Interface for PLC/DCS/SCADA systems

 

 

 

Masibus Analog Output Field Interface Board has 8 channels that accepts 
various types of current/voltage signals and converts them to isolated 
current/voltage signals. It is compact universal DIN rail mounted with labeled 
input and output connections. Independent zero & span adjustment for each 
channel is possible. 

 

8-Channel Analog Output Module 

 

 

8-C

HANNEL 

A

NALOG 

O

UTPUT 

M

ODULE

 

 

 

 

 

8 channel configurations 

 

Wide range of DC inputs and outputs 

 

Independent zero & span for each 
channel 

 

Easy to calibrate 

 

Accepts non-std. signal input option 

     DIN rail mounted 
 

Compact Size 

 

1. Dimension 
 

225(L) x 90(W) x 90(D)

 

 

 

 

  All Dimension in mm. 

 

S

PECIFICATION

 

 

Input 

 

No. of Channels & Type 

8 Channel DC Volt/Current (Factory Set)

 

Input Range

 

For Voltage : 1-5VDC,0-5VDC,0-10VDC 
For Current : 4-20mA,0-20mA 

Input Impedance 

Current I/P: 100 Ohms, Voltage I/P :> 5M 

I/P connection         

 

 

MKDS or 25pin D Type connector 

 

Output

 

 

 

Output  Type

 

 

Voltage/ Current 

Output  Range 

 

For Voltage : 1-5VDC,0-5VDC,0-10VDC 
For Current : 4-20mA,0-20mA 

Output Load resistance 

 

0/1 to 5V@ 1K

 min, 

0 to 10V@ 3K

 min 

0/4mA to 20mA@750

 max 

 

Fault LED Indication 

 

Red LED for over/under range(1-5V/4-20mA only) 

Response Time 

20milisecond 

Accuracy      

0.1% of output span 

Drift 

0.1% per Year  

Calibration 

Zero & Span Individual per channel by multi-turn trim pots 

O/P connection 

MKDS connector 

 

Power supply 

 

 

Power Supply 

24VDC ±10% 

 

Power Consumption 

< 12VA 

Fuse Rating 

2Amp (Fast Blown) 

LED Indication 

Green LED – Healthy Status, Red LED –Fault Status 

Isolation 

 

1.5KV AC Input  to Power, Output  to Output and 
Input  to Output , Output to Power 

 

Environmenta

 

 

Operating temperature 

Operating at 0 to 50

°

 

Temp. Co-efficient 

 

 100  PPM  

 

Relative humidity  

 

30 to 95% RH non- condense 

 

Environmental Protection 

 

Conformal Coating on PCB 

 

Physical 

 

Mounting Type 

DIN Rail (35 mm width)

 

Dimensions 

225(L) x 90(W) x 90(D)

 

Weight 

Approx 400 gm

 

 

Terminal Detail 

 

 

Terminal Block 

 

UL , CSA standard

 

 

Terminal Cable Size 

 

Upto 2.5mm² conductor

 

 

 

 

Reviews: