Doc.Ref. No. m61C/QG/501 Issue No.:00
Page 2 of 2
Decrement
Key
Decrement the
Value of any
Parameter in edit
mode.
Shuffle to previous
parameter in the
Sub Menu.
Shows ambient
value for T/C
Input in RUN
mode.
Enter Key
(Menu Key)
It is used to enter
in the sub menu.
It’s used to enter
in the edit mode.
It is also used to
save the
parameters to
nonvolatile
memory, when
user setting a
proper data by
Increment and
decrement key for
parameter
configuration.
PV(Process
Value)Display
PV
4 digit 0.80 inch
RED Display
Display process
value.
Display parameter
name when user
set parameter.
Display Parameter
Value when in Edit
mode.
Display error
message when an
error occurs.
PARAMETER SETTINGS
Parameter
(PV display)
Setting Name
& Description
Default
Value
Symbol
Name
INPT
(
inpt
)
INPUT
Type
Set PV Input
Type
tC j
/
tC t
/
tC
K
/
tC r
/
tC s
/
rtd1
/
rtd.1
/
0-5v
/
1-5v
/
0-
10
(ReferTable1.1)
RTD.1
ZERO
(
zero
)
Zero
Automatically
change to the
Input Lower
Range with
changing of
Input Type
(ReferTable1.1)
Can be set to
any value within
the Input Range
& less the SPAN
Value.
-199.9
SPAN
(
spaN
)
Span
Automatically
change to the
Input Higher
Range with
changing of
Input Type
(ReferTable1.1)
Can be set to
any value within
the Input Range
& greater the
ZERO Value.
850
*DP
(
dp
)
Decimal
Point
Set position of
Decimal Point
on Display.
0
/
0.0
/
0.00
/
0.000
0:0
1:0.0
2:0.00
3:0.000
0
BRHT
(
brHt
)
Brightn-
ess
Adjust
Brightness of
the 7-segment
Display.
10 to 100
50
PASS
(
pass
)
Password
Set Device
Password
0 to 99
1
VERS
(
vers
)
Version
Shows the
Version of the
Current
Firmware
-
*parameter shows only if input type is linear.
Cal
Mode
(PV display)
Setting Name &
Description
Symbol
Name
**AMB
(
Amb
)
Ambient
Ambient Adjustment
ZERO
(
zero
)
Calibration
Zero
Calibration Zero for PV
Input(PV/SV Display :
PV)
SPAN
(
spaN
)
Calibration
Span
Calibration Span for PV
Input(PV/SV Display :
PV)
**parameter showsonly if input type is TC.
MENU LAYOUT FOR 408-M
Examples:
How to change Set Point
How to change Input Type
For operation manual please visit www.masibus.com
Specifications are subject to change without notice due to
Continuous improvements.
Masibus Automation And Instrumentation Pvt. Ltd.
B-30, GIDC Electronics Estate, Sector-25, Gandhinagar-
382044, Gujarat, India.
Tel:+91 79 23287275-79 Fax: +91 79 23287281
Web:www.masibus.comEmail:[email protected]