Doc.Ref. No. m61C/QG/501 Issue No.:00
Page 1 of 2
DIGITAL INDICATOR
SPECIFICATIONS
Input type
Range
PT100 (0.1
º
C)
-199.9 to 850.0
º
C
PT100 (1
º
C)
-200 to 850
º
C
J
-199.9 to 1200
º
C
K
-199.9 to 1372
º
C
T
-199.9 to 400
º
C
R
0 to 1768
º
C
S
0 to 1768
º
C
*4-20mA /1-
5VDC
-1999 to 9999
(Field Scalable)
*0-20mA /0-
5VDC
0-10VDC
*Use external 250ohms, 0.1% for current Input
Table 1.1
Inputs
Input Type
Thermocouple, RTD
(Pt100), Current, Voltage
Accuracy
T /C and RTD :
Linear:
+0.25% of FS + 1 degree
+0.1% of FS + 1 count
Resolution
ADC:16bits
Display:0.1°C/1°C
Sampling Rate
5 Samples/Sec
CJC Error
±2.0 °C Max
Sensor Burnout
current
0.25uA
RTD excitation
current
0.166mA (Approx.)
Allowable
wiring
resistance for
RTD
Maximum 15 ohms/wire
(Conductorresistance
between three wires
should be equal)
NMRR
> 40 dB
CMRR
> 120 dB
Input
Impedance
> 1MΩ (Voltage Input)
250Ω (Current Input)
Max Voltage
20VDC
Display & Keys
PV
4-Digit 7-Segment, 0.8” High,Red
Keys Enter,Increase,Decrease
Output Types
Loop Power
Supply
24VDC (±10%)
@26mAwith Inbuilt Short
Circuit Protection
Power Supply
Standard
85-265VAC/ 100-
300VDC
Optional
18-36VDC
Power
consumption
<5VA
Isolation (Withstanding voltage)
Between primary terminals* and secondary
terminals**:
At least 1500 V AC for 1 minute
Between primary terminals* and grounding
terminal:
At least 1500 V AC for 1 minute
Between grounding terminal and secondary
terminals**:
At least 1500 V AC for 1 minute
Between secondary terminals**:
At least 500 V AC for 1 minute
* Primary terminals indicate power terminals
and relay output terminals.
** Secondary terminals indicate analog I/O
signal and Communication O/P.
Insulation resistance: 20MΩ or more at 500
V DC between power terminals and grounding
terminal.
Physical
Dimension
(WxHx D)mm
96 x 48 x 85
Front Bezel(H x W)mm
48 x 96
Panel Cutout mm
92 x 46
Depth Behind Panel mm 75
Weight Approx.
260g.
Enclosure Material
ABS Plastic
Enclosure Protection
IP 20
Terminal Cable Size
2.5mm
2
Environmental Conditions
TEMPCO
< 100ppm/°C
Humidity
20% to 95% RH
(Non-Condensing)
Ambient
temperature
0 to 55°C
Storage
Temperature
0 to 80°C
Advance Feature
Input scalability for linear input
MOUNTING DETAILS
ORDERING CODE
TERMINAL CONNECTIONS
Terminal No.
Description
1 LPS+
24VDC Loop power
supply Terminal 4 is
ground Reference.
2 C+
For RTD Input Only
(Three wire
Compensation).
3 TC+/ V+
For Thermocouple, RTD
&Linear Input
4 TC- / V- / LPS-
9 L/+
Power Supply Input
10 N/-
SAFETY/WARNING PRECAUSTIONS
To ensure that the device can be operated
safely and all functions can be used, please read
these instructions carefully.
Installation and Start-up must be carried out by
qualified personnel only. The relevant county-
specific regulations must also be observed.
Before start-up it is particularly important to
ensure:
Terminal wiring: check that all cables are
correctly connected according to the connection
diagram
All wiring must confirm to appropriate
standards of good practice and local codes and
regulations. Wiring must be suitable for voltage,
current and temperature rating of the system.
Unused control terminals should not be used
as jumper points as they may be internally
connected, which may cause damage to the
unit.
FRONT PANEL DESCRIPTION
Name of
Part
Symbol Function
Increment
Key
Increment the
Value of any
Parameter in edit
mode.
Shuffle to next
parameter in the
Sub Menu
Quick User Guide
408-M
Model
Input
Auxiliary Power
Supply
408-M 1
J
U1
85-265 VAC /
100-300 VDC
2
K
3
T
U2 18-36 VDC
4
R
5
S
6
Pt-100
C 4-20mA
D 0-20mA
E
1-5 V
F
0-5 V
G 0-10 V