Mascot FT, Heating Only, Boiler

Page 59

5.6  Status Display Mode

 Status display mode

Digital Display

Status Display Parameter 

Description

O: ot

Outdoor temperature

Current outdoor sensor temperature

A: In

0-10 V display

Current voltage of (0-10V input)

b: tt

CH target temperature in cascade system

Current CH target temperature or Current 
System target temperature in a cascade system

C: It

CH return water temperature 

Current CH  return water temperature

d: Fr

FAN speed ( rpm)

Current FAN speed ( RPM)

E: oP

CH supply  temperature (Operating temperature)

Current heating temperature

F: Eh

Exhaust  gas temperature

Current exhaust gas temperature

H: dH

Indirect DHW tank temperature
* If temperature sensor is not connected 
then it will display with 0°F  (0°C).

Current DHW tank temperature

I: oH

Overheat water temperature

Current  Overheat water temperature

L: rt

1: PH

Burner Operation 
Time

Time for supply power

L: rt on display 
on  sub menu

Unit : 1000hour

2: rh

Time for burner 
operation

Unit : 1hour

3: rH

Time for burner 
operation

Unit : 1,000hour

4: It

Cycle for ignition

Cycle : 10 times the 
displayed unit

5: IH

Cycle for ignition

Cycle : 10,000 times  the 
displayed unit

M: 
CC

SELF

Percentage of self units running.  Percentage of self units running.

ALL

Capacity for all operating 
cascade units

Percentage of  all cascade units running.
This screen shows the overal cascade power output. The 
range of this value of boilers communicating with theMaster 
x 100. For example, if 8 boilers are connected and 
communicating, the maximum cascade power is 800%.  
Range: 0-100%

F1 – F 
19

Capacity for individual boilers

Percentage of  each cascade units running.
Ex. F1, F2, ….

N: St

System Temperature (cascade 
mode)   * If system temperature 
sensor is not connected then it will 
display with 0°F  (0°C).

Current System Temperature (cascade mode)

To change any Status Parameter, 

Press and Hold Button B 

 to get into the Status Display Mode. 

Rotate Dial E until you fi nd the Parameter that you wish to change.  Tap Dial E to enter that Parameter.

Adjust to the setting that you require and then press (tap) Dial E to save and to Exit.  

   

B

C

E

A

D

Summary of Contents for MFTHW

Page 1: ...njury property damage or death Improper installation and or operation will void the warranty AVERTISSEMENT Assurez vous de bien suivres les instructions donn es dans cette notice pour r duire au minim...

Page 2: ...LAY COVER HINGES UPWARD NO Name of Component 1 Air Vent air eliminator 2 Air Intake Collar 3 Air Gas Mixing Pipe 4 Gas Inlet Pipe 2 5 Gas Valve 6 Exhaust Duct 7 Low Water Temperature Sensor 8 OP Senso...

Page 3: ...User s Manual Mascot FT Heating Only Boiler Page 3 Shown is the Mascot FT Heating Only 140 MBH All sizes are very similar in component layout...

Page 4: ...orethylene perchlorethylene chlorine etc Keep bottom and top openings on the boiler free for proper ventilation of interior components Do not obstruct or block a free flow of air to the boiler to ensu...

Page 5: ...r CH set point change mode Maxium 82 C 180 F D Time Date Set No Change To SET Year Month Week Day Time Min E Scroll Select Menu select or value up down or setting dial The Control Display has a Contro...

Page 6: ...nication state indication Time setting mode Time Dispaly Install mode indication Fan operating mode Fan operating mode indication Flame signal Flame Signal indication CH pump mode CH pump mode indicat...

Page 7: ...user and service modes that have speci c LCD output and dedicated controls Set point change mode Lock mode Error mode Status display mode Outside Temperature mode Installer mode Control Display will n...

Page 8: ...the MON Month by turning the dial E to the desired month number Then press the dial E to Save c Set the DATE 1 31 Day of the Month by turning the dial E Then press the dial E to Save d Set the HOUR 1...

Page 9: ...ame is detected Date and Time indicator If CH pump is operating If there currently a Demand for Central Heat CH Default CH set point is 180 F 82 C CH set point range is 86 F 180 F 30 0 C 82 0 C To cha...

Page 10: ...u Unit 1000hour 2 rh Time for burner operation Unit 1hour 3 rH Time for burner operation Unit 1 000hour 4 It Cycle for ignition Cycle 10 times the displayed unit 5 IH Cycle for ignition Cycle 10 000 t...

Page 11: ...User s Manual Mascot FT Heating Only Boiler Page 11 Notes...

Page 12: ...ester NH USA 03867 603 335 6300 Fax 603 335 3355 1869 Sismet Road Mississauga Ontario Canada L4W 1W8 905 238 0100 Fax 905 366 0130 www Laars com Litho in U S A Laars Heating Systems 1607 Document 1343...

Reviews: