Page 6
Optima 320 Series
1.7 Product Ratings
By model number, the following are the corresponding inlet and outlet ratings.
Model
Inlet Rating
Outlet Ratings
320001
320002
320009
120 Vac, 1
ɸ
, 50/60 Hz
12 A continuous
(15 A maximum)
•
120 Vac, 1
ɸ
, 12 A continuous (15 A max.) per 5-15R receptacle
•
12 A continuous (15 A max.) total per unit (regardless of receptacle
count used)
320005
120 Vac, 1
ɸ
, 50/60 Hz
12 A continuous
(15 A maximum)
•
120 Vac, 1
ɸ
, 12 A continuous (15 A max.) per 5-15R receptacle
•
12 A continuous (15 A max.) total per outlet group / circuit breaker
(regardless of receptacle count used)
•
12 A continuous (15 A max.) total per unit (regardless of receptacle
count used)
•
Note: the front and rear circuits are for flexibility, not double capacity.
320003
320010
120 Vac, 1
ɸ
, 50/60 Hz
16 A continuous
(20 A maximum)
•
120 Vac, 1
ɸ
, 16 A continuous (20 A max.) per 5-20R receptacle
•
16 A continuous (20 A max.) total per unit (regardless of receptacle
count used)
320004
320011
100–240 Vac, 1
ɸ
, 50/60 Hz
16 A maximum
•
100–240 Vac, 1
ɸ
, 10 A maximum per C13 receptacle
•
16 A maximum total per unit (regardless of receptacle count used)
320006
120 Vac, 1
ɸ
, 50/60 Hz
24 A continuous
(30 A maximum)
•
120 Vac, 1
ɸ
, 16 A continuous (20 A max.) per 5-20R receptacle
•
16 A continuous (20 A max.) total per outlet group / circuit breaker
(regardless of receptacle count used)
•
24 A continuous (30 A max.) total per unit (regardless of receptacle
count used)
320007
100–240 Vac, 1
ɸ
, 50/60 Hz
16 A maximum
•
100–240 Vac, 1
ɸ
, 10 A maximum per C13 receptacle
•
16 A maximum total per outlet group / circuit breaker (regardless of
receptacle count used)
•
16 A maximum total per unit (regardless of receptacle count used)
•
Note: the front and rear circuits are for flexibility, not double capacity.
320008
100–240 Vac, 1
ɸ
, 50/60 Hz
24 A continuous
(30 A maximum)
•
100–240 Vac, 1
ɸ
, 10 A maximum per C13 receptacle
•
100–240 Vac, 1
ɸ
, 16 A maximum per C19 receptacle
•
16 A continuous (20 A max.) total per outlet group (regardless of
receptacle count used)
•
24 A continuous (30 A max.) total per unit (regardless of receptacle
count used)