Electrical Connection
A grounded 115 volt, 15 amp dedicated circuit is required.
This product is factory equipped with a power supply
cord that has a three-pronged, grounded plug. It must be
plugged into a mating grounding type receptacle in accor-
dance with the National Electrical Code and applicable lo-
cal codes and ordinances (see Figure 4). If the circuit does
not have a grounding type receptacle, it is the responsibility
and obligation of the customer to provide the proper power
supply. The third ground prong should not, under any cir-
cumstances, be cut or removed.
Figure 4
NOTE
Ground Fault Circuit Interrupters (GFCI) are prone to nui-
sance tripping which will cause the appliance to shut down.
GFCI’s are generally not used on circuits with power equip-
ment that must run unattended for long periods of time, un-
less required to meet local building codes and ordinances.
ELECTRICAL
Figure 2
Do not remove
ground prong
Figure 3
Electrical Shock Hazard
•
Do not use an extension cord with this appliance.
They can be hazardous and can degrade product
performance.
• This appliance should not, under any circumstanc-
es, be installed to an un-grounded electrical supply.
• Do not remove the grounding prong from the power
cord. (See Figure 2).
• Do not use an adapter. (See Figure 3).
• Do not splash or spray water from a hose on the
appliance. Doing so may cause an electrical shock,
which may result in severe injury or death.
!
WARNING
6
Summary of Contents for MLRI224
Page 31: ...Z Z D D d x s x t K x d K x Z WD t ZE E W d KE K h D K D KE 31...
Page 32: ...D d d d t s d K d t d W Z Z dK d Zs d d E d D Z Ks Z KZ d KE E KZD d KE d d 32...
Page 33: ...D Z d d d Z d W d t 33...
Page 34: ...D D Z D d D Z d D x E x E x K t x K t x D s d t d W t W d E E W 34...
Page 35: ...D x Z Z 35...
Page 36: ...Z Z t t W 36...
Page 37: ...Z Z 37...
Page 38: ...W W W d 38...
Page 39: ...W t 39...
Page 40: ...40...
Page 41: ...41...