Marvel MLFZ224 Owner'S Manual Download Page 19

Evacuate/reclaim via the piecing pliers to ensure the 
system is empty of  R-600a before any system work is 
performed. 

GAS 

LEAi< 

LOCATOII 

The recovery cylinder must be evacuated  (no air inside) 
prior to accepting  R-600a. 

The recovery cylinder must not be filled more than 45% 
safe fill level and refrigerants must not be mixed. 

The  recovery cylinder  must  be clearly  marked  with  R-
600a  and  Flammable  Warning  labels. 

Ensure proper ventilation during recovery/reclaiming of  R-

600a. 

Start vacuum pump/recovery pump prior to piercing the 
compressor process tube. 

Follow recovery/reclaim OEM  instructions for the specific 

equipment used. 

SYSTEM  REPAIR 

Ensure no residual  R-600a refrigerant is left within the 
system prior to repair  (simple venting is not sufficient). 

Evacuate and charge with dry nitrogen for leak checks. 

Repair leaks or replace system parts as required. 

R-600A Specifications

When re-brazing,  the system must be purged with dry 
nitrogen and at least one access point open to the 
atmosphere. 

When re-brazing,  proper ventilation is required along with 
constant monitoring for the presence of R600a refrigerant. 

The filter dryer must be replaced any time the sealed 
system is serviced. 

No system should be open to the atmosphere for longer 

than  15 minutes to avoid moisture migration into the 
system components. 

LEAK  DETECTION 

After removal of the  R-600a,  the unit can be charged with 
dry nitrogen or helium. 

Electronic leak detection or soap solution can be used to 
check for  nitrogen/helium  leaks. 

Never use a halide torch or lighted match to check the 

system for leaks at any time. 

The high side of the refrigeration system  (compressor 
discharge to outlet of drier) must be leak tested with the 
compressor running. 

19

Summary of Contents for MLFZ224

Page 1: ...OWNERS GUIDE MARVEL UNDERCOUNTER REFRIGERATION T H E O R I G I N A L R E F R I G E R A T I O N E X P E R T S S I N C E 1 8 9 2 F O R M O D E L M L F Z 2 2 4...

Page 2: ...lem free installation and operation WARNING WARNING You can be killed or seriously injured if you do not follow these instructions WARNING State of California Proposition 65 Warning This product conta...

Page 3: ...ectrical Installing the anti tip device Integrated Panel Dimensions Integrated Panel Installation Maintenance Care and Cleaning Extended Non Use Operating Instructions Energy Savng Tips Service Obtain...

Page 4: ...lace The owners manual is shipped inside the product in a plastic bag along with the warranty registration card and other accessory items Important Keep your carton and packaging until your appliance...

Page 5: ...rrupters GFCI are prone to nui sance tripping which will cause the appliance to shut down GFCI s are generally not used on circuits with power equip ment that must run unattended for long periods of t...

Page 6: ...ith the end of the 211 2 54 6 cm line Rear of cabinet line 5 Fasten the anti tip bracket to the floor using the supplied screw See Figure 15 6 Slide the cabinet back into position making sure the rear...

Page 7: ...nti tip bracket is used the mini mum adjusted height of the cabinet is increased by 3 8 9 mm Figure 15a V notches in bracket V notches in bracket Figure 15 211 2 54 6 cm Front of cabinet line Rear Lev...

Page 8: ...uct is pressed against the adjacent cabinet use a 5 8 thick panel The window cutout is for glass door models only Do not use a solid door panel on a glass door model INTEGRATED PANEL DIMENSIONS Top of...

Page 9: ...ket retainer extrusions 3 on each side and 2 at the top and bottom which are used to fasten the panel to the front of the door The screws are provided in the literature pack Step 3 Assemble the Panel...

Page 10: ...or swing reinstall hinges per Door Reversal Instructions Carefully slide lower hinge bushing over bottom hinge pin Install the new upper hinge bushing into adaptor plate Align hinge bushing with top h...

Page 11: ...cuit Not shared with other appliances 5 When initially loading your new product or whenever large quantities of warm contents are placed within refrigerated storage compartment minimize door openings...

Page 12: ...rsonal preference and provides the proper storage for your stored contents 11 When on vacation or away from home for extended pe riods set the appliance to warmest acceptable tem perature for the stor...

Page 13: ...low ice to thaw naturally 4 Clean and dry the interior of the unit Ensure all water has been removed from the unit 5 The door must remain open to prevent formation of mold and mildew Open door a minim...

Page 14: ...rt section In all correspondence regarding service be sure to give the service number serial number and proof of purchase Try to have information or description of nature of the problem how long the a...

Page 15: ...r and part description Some parts will require color or voltage information If Marvel requires the return of original parts we will inform you when the parts order is taken This requirement will be no...

Page 16: ...er and part description Some parts will require color or voltage information Marvel requires the return of original parts we will inform you when the parts order is taken This requirement will be note...

Page 17: ...Of PROPERTY IN ACCORDANCE WITH FEDERAL OR LOCAL REGULATIONS FLAHHABLE REFRIGERANT USED R 600A Specifications Gloves and Eye Protection must be used R 600a is considered non toxic but is flammable when...

Page 18: ...ended that a simple LPG gas detector is on site during service Ensure that all R 600a is removed from the system prior to brazing any part of the sealed system Only a clean dry leak free system should...

Page 19: ...uate and charge with dry nitrogen for leak checks Repair leaks or replace system parts as required R 600A Specifications When re brazing the system must be purged with dry nitrogen and at least one ac...

Page 20: ...microns prior to charging Weigh in the R 600a charge using a refrigerant scale run compressor an extra two minutes to clear the charging hoses Seal the Schrader Type access port a proper cap and seal...

Page 21: ...um temperature temperature cool cool No Gas 0 PSIG to 25 Room Cool to hot temperature cool System Diagnosis Guide Condenser Capillary Evaporator Wattage Tube Very hot Warm Cold Normal Hot to warm Cool...

Page 22: ...nvironment When in this mode the only functions will be the control and cabinet lights The compressor fans etc will not operate To enter exit this mode hold the light key and the power key for 5 secon...

Page 23: ...connection you should replace the thermistor and the thermistor harness Thermistor error information can be found in the Control Operations Service section This unit has two thermistors Thermistor one...

Page 24: ...nce accident or improper use maintenance instal lation service repair acts of God fire flood or other natural disasters The product must be installed operated and maintained in accordance with the Mar...

Reviews: